A 15-kVA, 2400/240-V transformer is to be tested to determine its excitation branch components, its series impedances and its voltage regulation. The following test data have been taken from the primary side of the transformer: Open- circuit test Short- circuit test Voc = 2400 V Vsc = 48 V loc = 0.25 A Isc = 6.0 A Poc = 50 W Psc = 200 W The data have been taken by using the connections of open-circuit test and short- circuit test: a)Find the equivalent circuit transformer referred to the high-voltage side. of this b)Find the equivalent circuit of this transformer referred to the low-voltage side c)Calculate the full-load voltage regulation at 0.8 lagging power factor and 0.8 leading power factor

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.16P: A single-phase, 50-kVA,2400/240-V,60-Hz distribution transformer has the following parameters:...
icon
Related questions
Question
Subject Electrical machine
A 15-kVA, 2400/240-V transformer is to be
tested to determine its excitation branch
components, its series impedances and its
voltage regulation. The following test data
have been taken from the primary side of the
transformer:
Open- circuit test
Short- circuit test
Voc = 2400 V
Vsc = 48 V
loc = 0.25 A
Isc = 6.0 A
Poc = 50 W
Psc = 200 W
су
The data have been taken by using the
connections of open-circuit test and short-
circuit test:
a)Find the
transformer referred to the high-voltage side.
equivalent circuit
of
this
b)Find the
transformer referred to the low-voltage side
equivalent circuit
of
this
c)Calculate the full-load voltage regulation at
0.8 lagging power factor and 0.8 leading
power factor
What is the efficiency of the transformer at
full load with a power factor of 0.8 lagging?
Transcribed Image Text:A 15-kVA, 2400/240-V transformer is to be tested to determine its excitation branch components, its series impedances and its voltage regulation. The following test data have been taken from the primary side of the transformer: Open- circuit test Short- circuit test Voc = 2400 V Vsc = 48 V loc = 0.25 A Isc = 6.0 A Poc = 50 W Psc = 200 W су The data have been taken by using the connections of open-circuit test and short- circuit test: a)Find the transformer referred to the high-voltage side. equivalent circuit of this b)Find the transformer referred to the low-voltage side equivalent circuit of this c)Calculate the full-load voltage regulation at 0.8 lagging power factor and 0.8 leading power factor What is the efficiency of the transformer at full load with a power factor of 0.8 lagging?
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 6 steps with 2 images

Blurred answer
Knowledge Booster
Alternating Current (AC) Series Motor and Universal Motor
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Electric Motor Control
Electric Motor Control
Electrical Engineering
ISBN:
9781133702818
Author:
Herman
Publisher:
CENGAGE L
Electricity for Refrigeration, Heating, and Air C…
Electricity for Refrigeration, Heating, and Air C…
Mechanical Engineering
ISBN:
9781337399128
Author:
Russell E. Smith
Publisher:
Cengage Learning