A 270 kVA transformer has primary and secondary winding resistances of 0.6Ω, and 0.0016Ω respectively. The iron loss is 2.25 KW and the primary and secondary voltages are 7kV and 320 V respectively. If the power factor of the load is 0.6 lag, find the efficiency of the transformer for 20% of full load.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.11P: For the transformer in Problem 3.10. The open-circuit test with 11.5 kV applied results in a power...
icon
Related questions
Question

A 270 kVA transformer has primary and secondary winding resistances of 0.6Ω, and 0.0016Ω
respectively. The iron loss is 2.25 KW and the primary and secondary voltages are 7kV and 320 V
respectively. If the power factor of the load is 0.6 lag, find the efficiency of the transformer for 20% of full
load.

Expert Solution
steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Knowledge Booster
Single phase transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
Electricity for Refrigeration, Heating, and Air C…
Electricity for Refrigeration, Heating, and Air C…
Mechanical Engineering
ISBN:
9781337399128
Author:
Russell E. Smith
Publisher:
Cengage Learning