A 50 MVA, 11 kV three-phase alternator was subjected to different types of faults. The fault currents are as under : 3-phase fault = 2000 A; Line-to-Line fault = 2600 A; Line-to-ground fault = 4200 A The generator neutral is solidly grounded. Find the values of the three sequence reactances of the alternator. Ignore resistances.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter7: Symmetrical Faults
Section: Chapter Questions
Problem 7.5P
icon
Related questions
Question
A 50 MVA, 11 kV three-phase alternator was subjected to different types of
faults. The fault currents are as under :
3-phase fault = 2000 A; Line-to-Line fault = 2600 A; Line-to-ground fault = 4200 A
The generator neutral is solidly grounded. Find the values of the three sequence reactances of
the alternator. Ignore resistances.
Transcribed Image Text:A 50 MVA, 11 kV three-phase alternator was subjected to different types of faults. The fault currents are as under : 3-phase fault = 2000 A; Line-to-Line fault = 2600 A; Line-to-ground fault = 4200 A The generator neutral is solidly grounded. Find the values of the three sequence reactances of the alternator. Ignore resistances.
Expert Solution
steps

Step by step

Solved in 4 steps

Blurred answer
Knowledge Booster
Single phase transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning