A 90-MVA 69.3-kV, three-phase synchronous generator has a synchronous reactance of 10 Ohms/phase and negligible armature resistance. The generator is delivering power to the bus bar at the rated voltage with its field current adjusted for a generated emf (excitation voltage) of 50 kV per phase and a power angle & = 7.1 degree. Thus, the delivered power is the generator armature current is and the power factor is

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter12: Power System Controls
Section: Chapter Questions
Problem 12.11P
icon
Related questions
Question
power before losing synchronism (stability limit).
Thus, the maximum generated power is Pmax =
+ and the armature current is la =
A 90-MVA 69.3-kV, three-phase synchronous generator has a synchronous reactance of 10 Ohms/phase and negligible
armature resistance. The generator is delivering power to the bus bar at the rated voltage with its field current adjusted
for a generated emf (excitation voltage) of 50 kV per phase and a power angle & = 7.1 degree.
Thus, the delivered power is
the generator armature current is
and the
power factor is
The three phase power and line-line ratings of the below electric power system is given below:
Vg
Vm
M
G: 50 MVA
20 KV
X= 4%
T: 50 MVA
20/40 KV
X= 4%
43.2 MVA
36 KV
X= 40%
1:49 A
EN
4040
Transcribed Image Text:power before losing synchronism (stability limit). Thus, the maximum generated power is Pmax = + and the armature current is la = A 90-MVA 69.3-kV, three-phase synchronous generator has a synchronous reactance of 10 Ohms/phase and negligible armature resistance. The generator is delivering power to the bus bar at the rated voltage with its field current adjusted for a generated emf (excitation voltage) of 50 kV per phase and a power angle & = 7.1 degree. Thus, the delivered power is the generator armature current is and the power factor is The three phase power and line-line ratings of the below electric power system is given below: Vg Vm M G: 50 MVA 20 KV X= 4% T: 50 MVA 20/40 KV X= 4% 43.2 MVA 36 KV X= 40% 1:49 A EN 4040
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 3 steps with 2 images

Blurred answer
Knowledge Booster
Stability Analysis in Power System
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning