A three-phase, 100-MVA, 20-kV generator is connected to a three-phase, 100-MVA, 20-kV motor through a transmission line. The reactances of the generator and motor are 0.25 and 0.20 per unit, respectively. The line reactance is 0.10 per unit. The motor is taking 50 [MW] at 0.8 power factor leading at rated voltage. Suppose a three-phase short circuit occurs at the generator terminals, determine the transient currents in the generator and motor as well as the short-circuit current.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter7: Symmetrical Faults
Section: Chapter Questions
Problem 7.6P
icon
Related questions
Question

A three-phase, 100-MVA, 20-kV generator is connected to a three-phase, 100-MVA, 20-kV motor through a transmission line. The reactances of the generator and motor are 0.25 and 0.20 per unit, respectively. The line reactance is 0.10 per unit. The motor is taking 50 [MW] at 0.8 power factor leading at rated voltage. Suppose a three-phase short circuit occurs at the generator terminals, determine the transient currents in the generator and motor as well as the short-circuit current.

Expert Solution
steps

Step by step

Solved in 3 steps

Blurred answer
Knowledge Booster
Three Phase Transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning