A) A factory has the following load with power factor of 0.9 lagging in each phase. Red phase 40 A, yellow phase 50 A and blue phase 60 A. If the supply is 400 V, three phase, four-wire, calculate the current in the neutral and the total active power. Draw a phasor diagram for phase and line quantities. Assume that, relative to the current in the red phase, the current in the yellow phase lags by 120° and that in the blue phase leads by 120°. B)  Explain the advantage of connecting the low-voltage winding of distribution transformers in star.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter2: Fundamentals
Section: Chapter Questions
Problem 2.19P: Consider a single-phase load with an applied voltage v(t)=150cos(t+10)volts and load current...
icon
Related questions
Question

 

A) A factory has the following load with power factor of

0.9 lagging in each phase. Red phase 40 A, yellow phase

50 A and blue phase 60 A. If the supply is 400 V, three

phase, four-wire, calculate the current in the neutral

and the total active power. Draw a phasor diagram for

phase and line quantities. Assume that, relative to the

current in the red phase, the current in the yellow phase

lags by 120° and that in the blue phase leads by 120°.

B)  Explain the advantage of connecting the low-voltage

winding of distribution transformers in star.

Expert Solution
steps

Step by step

Solved in 2 steps with 2 images

Blurred answer