A refrigerated room is kept at -35°C by a vapor-compression cycle with R-134a as the refrigerant. Heat is rejecte to cooling water that enters the condenser at 16°C at a rate of 0.45 kg/s and leaves 26°C. The refrigerant enter the condenser at 1.2 MPa and 50°C and leaves at the same pressure sub-cooled by 5°C. If the compresso consumes 74 kW of power, determine (a) the mass flow rate of the refrigerant, (b) the refrigerant load, (c) the coefficient of performance and, (d) the minimum power input to the compressor for the same refrigerant load.

Refrigeration and Air Conditioning Technology (MindTap Course List)
8th Edition
ISBN:9781305578296
Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Chapter45: Domestic Refrigerators And Freezers
Section: Chapter Questions
Problem 12RQ: Refrigerators currently being manufactured in the United States are using______as their refrigerant.
icon
Related questions
Question

REFRIGERATION ENGINEERING (!)

USE SHAPIRO AND MORAN TABLE

3. A refrigerated room is kept at -35°C by a vapor-compression cycle with R-134a as the refrigerant. Heat is rejected
to cooling water that enters the condenser at 16°C at a rate of 0.45 kg/s and leaves 26°C. The refrigerant enters
the condenser at 1.2 MPa and 50°C and leaves at the same pressure sub-cooled by 5°C. If the compressor
consumes 74 kW of power, determine (a) the mass flow rate of the refrigerant, (b) the refrigerant load, (c) the
coefficient of performance and, (d) the minimum power input to the compressor for the same refrigerant load.
Transcribed Image Text:3. A refrigerated room is kept at -35°C by a vapor-compression cycle with R-134a as the refrigerant. Heat is rejected to cooling water that enters the condenser at 16°C at a rate of 0.45 kg/s and leaves 26°C. The refrigerant enters the condenser at 1.2 MPa and 50°C and leaves at the same pressure sub-cooled by 5°C. If the compressor consumes 74 kW of power, determine (a) the mass flow rate of the refrigerant, (b) the refrigerant load, (c) the coefficient of performance and, (d) the minimum power input to the compressor for the same refrigerant load.
Expert Solution
steps

Step by step

Solved in 2 steps

Blurred answer
Knowledge Booster
Refrigeration and Air Conditioning
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Refrigeration and Air Conditioning Technology (Mi…
Refrigeration and Air Conditioning Technology (Mi…
Mechanical Engineering
ISBN:
9781305578296
Author:
John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:
Cengage Learning