A Single-Phase AC Distributor AB,400 meters long, is fed from end A and is loaded as under: A. 120 A at 0.6 pf lagging 300 m from Point A. B. 80 A at 0.45 pf lagging 400 m from Point A. The Resistance and Reactance of the Distributor is 0.4 Ω and 0.6 Ω per 500 m. Calculate the Total Voltage Drop in the Distributor. The Load Power Factors refer to the Voltage at the Far End

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter6: Power Flows
Section: Chapter Questions
Problem 6.52P
icon
Related questions
icon
Concept explainers
Question
100%
11 A) A Single-Phase AC Distributor AB,400 meters long, is fed from end A and is loaded as under: A. 120 A at 0.6 pf lagging 300 m from Point A. B. 80 A at 0.45 pf lagging 400 m from Point A. The Resistance and Reactance of the Distributor is 0.4 Ω and 0.6 Ω per 500 m. Calculate the Total Voltage Drop in the Distributor. The Load Power Factors refer to the Voltage at the Far End.
Expert Solution
steps

Step by step

Solved in 3 steps with 2 images

Blurred answer
Knowledge Booster
Load flow analysis
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning