A three-phase, 4-pole alternator runs at 1,800 RPM. Each phase covers two slots under each pole. The full pitch armature coils have 4 turns per coil and there are 2 coil sides per slot. The flux/pole is 6,000 kilolines distributed sinusoidally. (a) What is the distribution factor? (b) Determine the emf per phase. Ans. 0.966; 494V
A three-phase, 4-pole alternator runs at 1,800 RPM. Each phase covers two slots under each pole. The full pitch armature coils have 4 turns per coil and there are 2 coil sides per slot. The flux/pole is 6,000 kilolines distributed sinusoidally. (a) What is the distribution factor? (b) Determine the emf per phase. Ans. 0.966; 494V
Chapter39: Synchronous Motor Operation
Section: Chapter Questions
Problem 14SQ: Induction motors and welding transformers require magnetizing current, which causes a. lagging power...