Belonging to a phase measured from a 220/48 V phase transformer, no-load (no load) operation and short-circuit test. values are given in the table below. Low voltage by applying rated voltage to the high voltage (primary) winding. voltage (secondary) winding ends were left unloaded and the results of the no-load operation test were obtained. low voltage By applying nominal current to the windings, the high voltage windings are short-circuite and short-circuit test results are obtained. has been done. In addition, the transformer with 5 V direct voltage applied to the high voltage winding is 2.2 A direct current. attracts. Calculate all equivalent circuit elements moved to the high voltage side. Boşta çalışma testi Gerilim 220 V Güç 80 W Akım 0,44 A Kısa devre testi Güç Gerilim Akım 12 V 65 W 16,1 A

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.34P: Three single-phase, two-winding transformers, each rated 450MVA,20kV/288.7kV, with leakage reactance...
icon
Related questions
Question
Belonging to a phase measured from a 220/48 V phase transformer, no-load (no load)
operation and short-circuit test.
values are given in the table below. Low voltage by applying rated voltage to the high
voltage (primary) winding.
voltage (secondary) winding ends were left unloaded and the results of the no-load
operation test were obtained. low voltage
By applying nominal current to the windings, the high voltage windings are short-circuited
and short-circuit test results are obtained.
has been done. In addition, the transformer with 5 V direct voltage applied to the high
voltage winding is 2.2 A direct current.
attracts. Calculate all equivalent circuit elements moved to the high voltage side.
Boşta çalışma testi
Gerilim
220 V
Güç
80 W
Akım
0,44 A
Kısa devre testi
Gerilim
12 V
Güç
Akım
65 W
16,1 A
Transcribed Image Text:Belonging to a phase measured from a 220/48 V phase transformer, no-load (no load) operation and short-circuit test. values are given in the table below. Low voltage by applying rated voltage to the high voltage (primary) winding. voltage (secondary) winding ends were left unloaded and the results of the no-load operation test were obtained. low voltage By applying nominal current to the windings, the high voltage windings are short-circuited and short-circuit test results are obtained. has been done. In addition, the transformer with 5 V direct voltage applied to the high voltage winding is 2.2 A direct current. attracts. Calculate all equivalent circuit elements moved to the high voltage side. Boşta çalışma testi Gerilim 220 V Güç 80 W Akım 0,44 A Kısa devre testi Gerilim 12 V Güç Akım 65 W 16,1 A
Expert Solution
steps

Step by step

Solved in 3 steps with 3 images

Blurred answer
Knowledge Booster
Three Phase Transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning