Question
How does change in frequency affect the operation of a given transformer?
Ans. 1. Iron loss........ increases with a decrease in frequency. A 60-Hz transformer will have nearly
11% higher losses when worked on 50Hz instead of 60 Hz. However, when a 25-Hz trans-
former is worked on 60 Hz, iron losses are reduced by 25%.
2. Cu loss..........in distribution transformers, it is independent of frequecy.
3. Efficiency...........since Cu loss is unaffected by change in frequency, a given transformer effi-
ciency is less at a lower frequency than at a higher one.
4.
Regulation........regulation at unity power factor is not affected because IR drop is independent
of frequency. Since reactive drop is affected, regulation at low power factors decreases with
a decrease in frequency and vice-versa. For example, the regulation of a 25-Hz transformer
when operated at 50-Hz and low power factor is much poorer.
5. Heating..........since total loss is greater at a lower frequency, the temperature is increased with
decrease in frequency.
111
Transcribed Image Text:How does change in frequency affect the operation of a given transformer? Ans. 1. Iron loss........ increases with a decrease in frequency. A 60-Hz transformer will have nearly 11% higher losses when worked on 50Hz instead of 60 Hz. However, when a 25-Hz trans- former is worked on 60 Hz, iron losses are reduced by 25%. 2. Cu loss..........in distribution transformers, it is independent of frequecy. 3. Efficiency...........since Cu loss is unaffected by change in frequency, a given transformer effi- ciency is less at a lower frequency than at a higher one. 4. Regulation........regulation at unity power factor is not affected because IR drop is independent of frequency. Since reactive drop is affected, regulation at low power factors decreases with a decrease in frequency and vice-versa. For example, the regulation of a 25-Hz transformer when operated at 50-Hz and low power factor is much poorer. 5. Heating..........since total loss is greater at a lower frequency, the temperature is increased with decrease in frequency. 111
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Knowledge Booster
Single phase transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
Electric Motor Control
Electric Motor Control
Electrical Engineering
ISBN:
9781133702818
Author:
Herman
Publisher:
CENGAGE L
Electricity for Refrigeration, Heating, and Air C…
Electricity for Refrigeration, Heating, and Air C…
Mechanical Engineering
ISBN:
9781337399128
Author:
Russell E. Smith
Publisher:
Cengage Learning