Part A A total of 3900 W of power is to be supplied through the wires of a flat to the household electridal appliances. If the potential difference across the group of appliances is 230 V, determine the cross-sectional area of the thinnest permissible wire that can be used. Express your answer to millimeters squared. ? ΑΣφ A mm? %3D Part B Suppose the wire used in this fat is of the size found in part A and has total length 44.0 m At what rate is energy dissipated in the wires? Express your answer in watts. P- 90.11 W • Part C The consumer cost of electrical energy is £0 125 per kilowatt-hour If the flat was built with wire of the next larger cross- sectional area than that was found in part A what would be the savings in electricity costs in one year? Assume that the appliances are kept on for an average of 12 hours a day Express your answer in pounds. saving in electricity costs = 18.5 £ per year

Delmar's Standard Textbook Of Electricity
7th Edition
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Stephen L. Herman
Chapter10: Using Wire Tables And Determining Conductor Sizes
Section: Chapter Questions
Problem 4PA: Using the above example, determine the wire size needed for the 400-ampere service in accordance...
icon
Related questions
Question
Part A
A total of 3900 W of power is to be supplied through the wires
of a flat to the household electrial appliances. If the potential
difference across the group of appliances is 230 V, determine
the cross-sectional area of the thinnest permissible wire that can
be used.
Express your answer to millimeters squared.
--
?
ΑΣφ
A
mm2
Part B
Suppose the wire used in this fat is of the size found in part A and has total length 44.0 m At what rate is energy disspated in
the wires?
Express your answer in watts.
P= 90.11 W
• Part C
The consumer cost of electrical energy is £0 125 per kilowatt-hour If the flat was built with wire of the next larger cross- sectional
area than that was found in part A what would be the savings in electricity costs in one year? Assume that the appliances are
kept on for an average of 12 hours a day
Express your answer in pounds.
saving in electricity costs = 18.5 £ per year
Transcribed Image Text:Part A A total of 3900 W of power is to be supplied through the wires of a flat to the household electrial appliances. If the potential difference across the group of appliances is 230 V, determine the cross-sectional area of the thinnest permissible wire that can be used. Express your answer to millimeters squared. -- ? ΑΣφ A mm2 Part B Suppose the wire used in this fat is of the size found in part A and has total length 44.0 m At what rate is energy disspated in the wires? Express your answer in watts. P= 90.11 W • Part C The consumer cost of electrical energy is £0 125 per kilowatt-hour If the flat was built with wire of the next larger cross- sectional area than that was found in part A what would be the savings in electricity costs in one year? Assume that the appliances are kept on for an average of 12 hours a day Express your answer in pounds. saving in electricity costs = 18.5 £ per year
According to the UK wiring regulations, copper wire
used for interior wiring of houses is permitted to
carry no more than a specified maximum amount of
current. The table below shows the values of the
maximum current Imax for several common sizes
of PVC-insulated and sheathed wire.
Cross-sectional area (mm2) Imax (A)
1
11.5
1.5
14.5
2.5
20
4
26
32
44
10
57
16
Transcribed Image Text:According to the UK wiring regulations, copper wire used for interior wiring of houses is permitted to carry no more than a specified maximum amount of current. The table below shows the values of the maximum current Imax for several common sizes of PVC-insulated and sheathed wire. Cross-sectional area (mm2) Imax (A) 1 11.5 1.5 14.5 2.5 20 4 26 32 44 10 57 16
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps

Blurred answer
Knowledge Booster
Dielectric breakdown
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
EBK ELECTRICAL WIRING RESIDENTIAL
EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:
9781337516549
Author:
Simmons
Publisher:
CENGAGE LEARNING - CONSIGNMENT