Problem 6.4 In a vapour type filled system thermometer (filled with pure water), bulb was located 4.5 m above the indicator. If the actual temperature at the bulb i 200° C. Estimate the effect of relative elevation of the bulb and the indicator. From steam tables, the following data has been recorded. Pressure, kgf/cm? 15 16 17 Saturation temp. °C 197.4 200.0 203.4

Refrigeration and Air Conditioning Technology (MindTap Course List)
8th Edition
ISBN:9781305578296
Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Chapter11: Calibrating Instruments
Section: Chapter Questions
Problem 7RQ: Accuracy of a thermometer is more important in the ______temperature ranges.
icon
Related questions
Question
answer quickly
Problem 6.4 In a vapour type filled system thermometer (filled with pure water)
bulb was located 4.5 m above the indicator. If the actual temperature at the bulh i
200° C. Estimate the effect of relative elevation of the bulb and the indicator.
From steam tables, the following data has been recorded.
Pressure, kgf/cm?
15
16
17
Saturation temp. °C
197.4
200.0
203.4
Transcribed Image Text:Problem 6.4 In a vapour type filled system thermometer (filled with pure water) bulb was located 4.5 m above the indicator. If the actual temperature at the bulh i 200° C. Estimate the effect of relative elevation of the bulb and the indicator. From steam tables, the following data has been recorded. Pressure, kgf/cm? 15 16 17 Saturation temp. °C 197.4 200.0 203.4
Expert Solution
steps

Step by step

Solved in 2 steps with 2 images

Blurred answer