Q/ 30-kVA, 2200/220-V, 50-Hz distribution transformer is tested for efficiency : and regulation as follows O.C. test( Low voltage side ) : 220 V 4.2 A, 148 W 10.5 A, 360 W S.C. test ( Low voltage side ) : 86 V نقطتان )2( Equivalent reactance referred to primary & referred to * secondary. .ohm, .ohm 6.71 , 0.0671 9.51 , 0.0951 7.51 , 0.0751 8.51 , 0.0851 نقطتان )2( The working current and resistance component of no-load are.. .amper, . .ohm 0.87, 556.89 0.67, 436.89 0.76, 326.89 0 57 236 89

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.4P: A single-phase 100-kVA,2400/240-volt,60-Hz distribution transformer is used as a step-down...
icon
Related questions
Question
2:01 1
ull LTE O
A docs.google.com
نقطة واحدة
Regulation of transformer at 0.5 p.f.
* lagging current
5.043%
2.942%
3.043%
4.942%
نقطتان )2(
Equivalent resistance referred to
primary & referred
secondary..ohm, .ohm
4.26 , 0.0426
3.26 , 0.0326
2.26 , 0.0226
5.26 , 0.0526
نقطتان )2(
The magnetizing current and
reactance component of no-load
are. .amper , . .ohm
6.14 , 74.1
3.14, 44.1
5.14 , 64.1
4.14, 53.1
Transcribed Image Text:2:01 1 ull LTE O A docs.google.com نقطة واحدة Regulation of transformer at 0.5 p.f. * lagging current 5.043% 2.942% 3.043% 4.942% نقطتان )2( Equivalent resistance referred to primary & referred secondary..ohm, .ohm 4.26 , 0.0426 3.26 , 0.0326 2.26 , 0.0226 5.26 , 0.0526 نقطتان )2( The magnetizing current and reactance component of no-load are. .amper , . .ohm 6.14 , 74.1 3.14, 44.1 5.14 , 64.1 4.14, 53.1
Q/ 30-kVA, 2200/220-V, 50-Hz distribution transformer is
tested for efficiency
: and regulation as follows
O.C. test( Low voltage side ) : 220 V 4.2 A, 148 W
10.5 A, 360 W
S.C. test ( Low voltage side ) : 86 V
نقطتان )2(
Equivalent reactance referred to
primary & referred to
secondary. .ohm, .ohm
6.71 , 0.0671
9.51 , 0.0951
7.51 , 0.0751
8.51 , 0.0851
نقطتان )2(
The working current and resistance
component of no-load
are.. .amper , .. .ohm
0.87 , 556.89
0.67, 436.89
0.76 , 326.89
0.57, 236.89
Transcribed Image Text:Q/ 30-kVA, 2200/220-V, 50-Hz distribution transformer is tested for efficiency : and regulation as follows O.C. test( Low voltage side ) : 220 V 4.2 A, 148 W 10.5 A, 360 W S.C. test ( Low voltage side ) : 86 V نقطتان )2( Equivalent reactance referred to primary & referred to secondary. .ohm, .ohm 6.71 , 0.0671 9.51 , 0.0951 7.51 , 0.0751 8.51 , 0.0851 نقطتان )2( The working current and resistance component of no-load are.. .amper , .. .ohm 0.87 , 556.89 0.67, 436.89 0.76 , 326.89 0.57, 236.89
Expert Solution
steps

Step by step

Solved in 2 steps with 4 images

Blurred answer
Knowledge Booster
Single phase transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Electricity for Refrigeration, Heating, and Air C…
Electricity for Refrigeration, Heating, and Air C…
Mechanical Engineering
ISBN:
9781337399128
Author:
Russell E. Smith
Publisher:
Cengage Learning