Q.1 An air conditioning system supplying air to a space with a sensible heat load of 14 kW and a latent heat load of 9 kW has a cooling coil and a bypass path as shown schematically in Fig. The db- temperature of the space is maintained at 26°C. The dry air mass flow rate of supply air is 1.2kg/s. Outdoor ventilation air at 34°C db-temperature and 50% relative humidity is introduced into the system with a dry air mass flow rate of 0.26 kg/s. The air leaving the cooling coil is fully saturated at a db-temperature of 6°C. The pressure is constant at 101.3 kPa. Determine db-temperature and relative humidity of the supply air to the space, (ii) (1) (ii) (iv) wb-temperature of the space, temperature of the air entering the cooling coil, and refrigeration capacity of the cooling coil.

Principles of Heat Transfer (Activate Learning with these NEW titles from Engineering!)
8th Edition
ISBN:9781305387102
Author:Kreith, Frank; Manglik, Raj M.
Publisher:Kreith, Frank; Manglik, Raj M.
Chapter6: Forced Convection Over Exterior Surfaces
Section: Chapter Questions
Problem 6.8P
icon
Related questions
Question
Q.1 An air conditioning system supplying air to a space with a sensible heat load of 14 kW and a
latent heat load of 9 kW has a cooling coil and a bypass path as shown schematically in Fig. The db-
temperature of the space is maintained at 26°C. The dry air mass flow rate of supply air is 1.2kg/s.
Outdoor ventilation air at 34°C db-temperature and 50% relative humidity is introduced into the
system with a dry air mass flow rate of 0.26 kg/s. The air leaving the cooling coil is fully
saturated at a db-temperature of 6°C. The pressure is constant at 101.3 kPa. Determine
db-temperature and relative humidity of the supply air to the space,
(ii)
(i)
(ii)
(iv)
wb-temperature of the space,
temperature of the air entering the cooling coil, and
refrigeration capacity of the cooling coil.
Transcribed Image Text:Q.1 An air conditioning system supplying air to a space with a sensible heat load of 14 kW and a latent heat load of 9 kW has a cooling coil and a bypass path as shown schematically in Fig. The db- temperature of the space is maintained at 26°C. The dry air mass flow rate of supply air is 1.2kg/s. Outdoor ventilation air at 34°C db-temperature and 50% relative humidity is introduced into the system with a dry air mass flow rate of 0.26 kg/s. The air leaving the cooling coil is fully saturated at a db-temperature of 6°C. The pressure is constant at 101.3 kPa. Determine db-temperature and relative humidity of the supply air to the space, (ii) (i) (ii) (iv) wb-temperature of the space, temperature of the air entering the cooling coil, and refrigeration capacity of the cooling coil.
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 4 steps with 1 images

Blurred answer
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Principles of Heat Transfer (Activate Learning wi…
Principles of Heat Transfer (Activate Learning wi…
Mechanical Engineering
ISBN:
9781305387102
Author:
Kreith, Frank; Manglik, Raj M.
Publisher:
Cengage Learning