Q1) Short answer questions: a. (True or False)A double line to ground short circuit fault at phases A and B will have the same magnitude as a double line to ground short circuit fault at phases A and C at the same location. b. How many unique symmetrical components are there for a set of three unbalanced phasors? c. (True or False)Symmetrical components are used to analyze symmetrical faults. d. (True or False) The negative sequence voltage of a generator have the same voltage magnitude and -120° phase shift between each consecutive phases. e. (True or False) The current passing through the zero sequence equivalent of a delta- delta connected three phase transformer in case of a solid double line to ground fault is larger in magnitude than that of a double line to ground fault through a grounding impedance. f. (True or False) The zero sequence components of three phase components are equal in phase but not equal in magnitude. g. When analyzing unbalanced three phase faults in class we always started with two constraints. What were these constraints on? What did the constraint depend on? h. Can we use the double line to ground fault analysis to analyze all double line faults? i. (True or False)A short circuit fault at a specific bus affects the injection current at all busses in the system. j. (True or False) A short circuit fault at a specific bus affects the voltage at all busses in the system.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter9: Unsymmetrical Faults
Section: Chapter Questions
Problem 9.20P
icon
Related questions
icon
Concept explainers
Question
100%
Power system analysis
Q1)
Short answer questions:
a. (True or False)A double line to ground short circuit fault at phases A and B will have
the same magnitude as a double line to ground short circuit fault at phases A and Cat
the same location.
b. How many unique symmetrical components are there for a set of three unbalanced
phasors?
c. (True or False)Symmetrical components are used to analyze symmetrical faults.
d. (True or False) The negative sequence voltage of a generator have the same voltage
magnitude and -120° phase shift between each consecutive phases.
e. (True or False) The current passing through the zero sequence equivalent of a delta-
delta connected three phase transformer in case of a solid double line to ground fault
is larger in magnitude than that of a double line to ground fault through a grounding
impedance.
f. (True or False) The zero sequence components of three phase components are equal
in phase but not equal in magnitude.
g. When analyzing unbalanced three phase faults in class we always started with two
constraints. What were these constraints on? What did the constraint depend on?
h. Can we use the double line to ground fault analysis to analyze all double line faults?
i. (True or False) A short circuit fault at a specific bus affects the injection current at all
busses in the system.
j. (True False) A short circuit fault at a specific bus affects the voltage at all busses in
the system.
k. Why is the pre-fault voltage at an unfaulted bus in the system assumed to be the same
as the pre-fault voltage at the faulted bus?
Transcribed Image Text:Q1) Short answer questions: a. (True or False)A double line to ground short circuit fault at phases A and B will have the same magnitude as a double line to ground short circuit fault at phases A and Cat the same location. b. How many unique symmetrical components are there for a set of three unbalanced phasors? c. (True or False)Symmetrical components are used to analyze symmetrical faults. d. (True or False) The negative sequence voltage of a generator have the same voltage magnitude and -120° phase shift between each consecutive phases. e. (True or False) The current passing through the zero sequence equivalent of a delta- delta connected three phase transformer in case of a solid double line to ground fault is larger in magnitude than that of a double line to ground fault through a grounding impedance. f. (True or False) The zero sequence components of three phase components are equal in phase but not equal in magnitude. g. When analyzing unbalanced three phase faults in class we always started with two constraints. What were these constraints on? What did the constraint depend on? h. Can we use the double line to ground fault analysis to analyze all double line faults? i. (True or False) A short circuit fault at a specific bus affects the injection current at all busses in the system. j. (True False) A short circuit fault at a specific bus affects the voltage at all busses in the system. k. Why is the pre-fault voltage at an unfaulted bus in the system assumed to be the same as the pre-fault voltage at the faulted bus?
Expert Solution
steps

Step by step

Solved in 3 steps

Blurred answer
Knowledge Booster
Protection System in Power Plant
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning