Question 5 If a building or structure is supplied by a feeder from an outdoor separately derived system, a system bonding jumper at both the source and the first disconnecting means shall be permitted if doing so does not establish a parallel path for the grounded conductor. True B False Last saved 6:44:15 PM O138 minutes remaining
Q: A transmission line conductor at the water crossing was supported by two towers of height 35 m and…
A:
Q: What is the minimum-size supply-side bonding jumper required if installed on the line side of a…
A: The supply-side bonding jumper is installed on the line side of a 300-ampere service disconnecting…
Q: 5. What is the minimum depth that a USEB90 cable, used as a service conductor, can be buried…
A: USEB 90 cable is used as underground cable to transfer electrical power in houses. These types of…
Q: In the conduit layout shown in picture attached, determine how many wires are contained in each…
A: The circuit is shown below: Between the three-phase line and the disconnect switch. The switch is…
Q: Expansion fittings and telescoping sections of metal raceways shall be made electrically continuous…
A: In Bonding loosely jointed metal raceways, grounding electeode and grounded current carrying…
Q: If a 1 1/4-in. EMT raceway containing three conductors is already filled to 20%, what is the…
A: Need to find cross sectional area of raceaway
Q: an unintentional electrically conducting connection between and ungrounded conductor of an…
A: The fault occurs due to connection between the ungrounded conductor and the metallic raceways,…
Q: The minimum size raceway for the following branch circuit conductors is: Twelve, 6 AWG conductors…
A: The transmission of power from one place to another is very necessary, usually, the voltage level of…
Q: The frames of ranges, wall-mounted ovens, counter-mounted cooking units, and clothes dryers under…
A: Materials that allow current to flow through them are called conductors. The materials that do not…
Q: 8- Generally as of the operating voltage which of the following options are the correct words that…
A:
Q: Which of the following statements about equipment grounding conductors (EGCs) is true? A. The…
A: Statement about the equipment grounding conductors (EGCs)
Q: Which of the following is not a criteria for the mechanical design of an overhead line? O Minimum…
A: over head lines are designed based on distance between conductor and earth , tensile stress ,…
Q: 1) What is the allowable ampacity of a single #2 THHN conductor that is installed in a conduit with…
A: It is asked to find the the allowable ampacity of a single #2 AWG THHN conductor that is installed…
Q: Using bundled conductors, corona effect will ______________ 1- increase 2- not change 3-…
A: - Bundling of conductors is done to increase the current carrying capacity of transmission lines and…
Q: - The figure below shows the structure of which busbar? If CBF has occurred, please explain how many…
A:
Q: 12. What is the conduit and wire equivalent to a 400A bus duct with both copper and aluminum?…
A: The National Electrical Code (NEC) is a collection of rules for the secure electrical wiring wiring…
Q: Restrictions on types of conduits used for installing service, sub panel, emergency service panel.
A: We are authorized to answer one question at a time, since you have not mentioned which question you…
Q: The line described is 845 mi in length.The line contains four conductors, each weighing 2526 lb per…
A: since 1 mi = 5280 ft so 845 mi = 845×5280 = 4461600 ft so the length of the line =…
Q: List the methods by which an equipment grounding conductor is connected to a device box
A:
Q: b) Differentiate between Insulated-Neutral and Earthed-Neutral systems as applied to electrical…
A: Question. b) Differentiate between Insulated-Neutral and Earthed-Neutral systems as applied to…
Q: A conductor with continuous white or gray covering shall be used only for the grounded circuit…
A: According to article NEC 200.6, the facts about the identification of the Grounded conductors are…
Q: How far can a 230V, 50A, three-phase load be located from a panelboard if it's fed with 3 AWG…
A: The Length of the load from the panel board is calculated as shown below
Q: Basically, ______receptacles are required to be installed if an equipment grounding conductor is…
A: Article 406 of NEC covers the installation of receptacles of both grounded type and non-grounded…
Q: The Voltage Regulation of a Transmission Line should be _____? A. very high percentage. B. more than…
A: C. Zero or nil Option C is correct.
Q: mast-type service entrance
A: The service raceway according to NEC is defined as an enclosed channel specially designed to hold…
Q: What's the required bend radius for three-conductor, 3/0 AWG service entrance cable that's…
A: Given, Three-conductor, 3/0 AWG service entrance cable that's approximately 1 inch in diameter.
Q: How many conductor volume allowances should be applied for the equipment grounding conductors in the…
A: We need to answer how many conductor volume allowances should be applied for the equipment grounding…
Q: 20. If a cable assembly such as a metal-clad (MC) cable includes an equipment grounding conductor…
A: given a mcq on optical cables and the coloured used for MC cables.
Q: L1. Boxes are classified by type, construction, and A. installation location. B. luminaire support…
A: 1) Boxes are referred as a electrical boxes are of plastic or metallic, Boxes are used in light…
Q: A protective conductor connecting exposed conductive parts of equipment to the main earthing…
A: In earthing a conductor is used to connect the exposed conductive parts(metallic parts) of various…
Q: How does rise in voltage at the receiving end of an open circuited line depend upon the length of…
A: Given:-
Q: Which of the following is a term missing from the National Electrical Code but used by manufacturers…
A: ANSWER (1) Grounding Triad is the term which is missing in NATIONAL…
Q: Connections from headers to cabinets and other enclosures, in cellular concrete floor raceways,…
A: To explain the means of connection made from header to cabinets and other enclosures, in cellular…
Q: Which of the following is an installation requirement for the grounding electrode conductor in a…
A: ANSWER - (A,C,D) is correct EXPLANATION- Option (A)- Grounding…
Q: 19.a. Which term relates to the conductors connected to the output side of a separately derived…
A: A power station is to provide electricity to a huge number of people. Different customer’s power…
Q: In an ungrounded electrical systems with conductors installed in grounded metal raceways and…
A: In an ungrounded system, the system has no direct connection with the grounding electrode. When the…
Q: The air interface connecting phones, antennas, and towers in mobile networks is completely devoid of…
A: Mobile Backhaul:- The transport network that links the mobile network's core network and RAN (Radio…
Q: Briefly discuss the loaded and non-loaded telephone cables
A: Loading is the process to increase inductance of line by adding lumped inductors atpredefined…
Q: What is the box fill volume allowance for each conductor originating outside and terminating inside…
A: We need to answer what is the box fill volume allowance for each conductor originating outside and…
Q: Which of the following criteria is correct for the electrical design of the overhead line? O Tensile…
A: Need to find the criteria for Electrical design of overhead line
Q: 15 A certain type of Suspension Type Insulator is used to sustain heavy tensile loads of conductors…
A: Given that Suspension type insulator is used to sustain heavy tensile loads of conductors when the…
Q: What is the largest solid (not stranded) conductor approved for installation in raceways?
A: Solid conductor are made with a single conductive material while stranded conductor are made with…
Q: is the required size of THHN copper conductors for a feeder serving two 208Y/120V, four-wire,…
A:
Q: How many 14 AWG THHN conductors, including an equipment grounding conductor, can be installed in a…
A: Here we have to refer standard tables, When determining the maximum number of conductors permitted…
Q: The copper line with a total length of 20 meters operates in the 220 volt city network. If three…
A:
Q: Please provide Handwritten answer Question: NEC Reference Answer __________ __________ _____ is…
A: Although, Patient equipment grounding point is used ,to the eliminate the electromagnetic…
Trending now
This is a popular solution!
Step by step
Solved in 2 steps
- A ______ is a raceway containing the service entrance conductors that is run through the roof of a building to a height sufficient to obtain the necessary clearances for the service-drop conductors. a. service lateralb. mast-type service entrancec. service point6. Which type of cable would you use to connect two buildings in an office installation?A. Buried loose-tube cableB. Aerial armored cableC. OFNP cableD. Tight-buffered cableWhich of the following is a term missing from the National Electrical Code but used by manufacturers of equipment that's suitable for use as service equipment? Micro-grid Selective coordination Neutral disconnect link Grounding triad The _______ is required to be connected to the grounded conductor of the sensitive electronic system on the line side of the separately derived system disconnecting means. main bonding jumper equipment grounding terminal bus neutral ground strap neutral disconnect link
- Determine the minimum number of cubic inches required for two 10 AWG conductors passing through a box, four 14 AWG conductors spliced in the box, two 12 AWG conductors terminating to a receptacle, and one 12 AWG equipment bonding jumper from the receptacle to the box.It is generally understood that grounding and bonding together all metal parts of an electrical system and the metal shield of the cable television cable to the same grounding reference point in a residence will keep both systems at the same voltage level should a surge, such as lightning, occur. Therefore, if the incoming cable that has been installed by the CATV cable company installer has the metal shield grounded to a driven ground rod, does this installation conform to the NEC? ___________5. Identify and describe the step-by-step process used to install cable in the NCT Colledge buildings? Note: Please do not handwritten.
- If a 1 1/4-in. EMT raceway containing three conductors is already filled to 20%, what is the raceway's cross-sectional area?2.a. What's defined as an assembly consisting of a service raceway, guy wires or braces, service head, andany fittings necessary for the termination and support of overhead service conductors?A. Drip loopB. Service lateralC. Service dropD. Service mast 2.b. What's likely to happen when connected parallel conductors are different lengths?A. An NEC violationB. Misidentification of conductor cablesC. An uneven distribution of currentD. Conductor terminationWhat size equipment grounding conductor is used with # 8 AWG nonmetallic-sheathed cable?
- A Type NM cable carries a branch circuit to the outside of a building, where it terminates in a metal weatherproof junction box. From this box, a short length of EMT is installed upward to another metal weatherproof junction box on which is attached a cluster of outdoor floodlights. The first box is located approximately 24 in. (600 mm) above the ground. To Meet Code, do the metal boxes and metal raceway have to be grounded? Yes _______________ No _______________ NEC _______________.a. How many feet of 2-conductor bell wire cable are required? ______ b. How many feet of 3-conductor bell wire cable are required? ______10.a. Which of the following is a condition of the exception that allows the grounded conductor of feeders tobe used for grounding at separate buildings or structures?A. There are common electrically continuous metallic paths between the feeder source and the destination at the structure served.B. There are common electrically continuous nonmetallic paths between the equipment grounding conductor and the destinationat the structure served.C. An equipment grounding conductor isn't included with the supply circuit to the separate structure.D. Ground-fault protection of equipment is provided on the supply side of the feeder.10.b. A service disconnection means must be installed adjacent to, within sight of, and no more than_______ feet from a mobile home.A. 20B. 30C. 10D. 50