The reactance of a generator is given as 0.4 per unit based on the generator's nameplate rating of 100 kV, 200 MVA. The reactance in per unit for a base of 50 kV, 100 MVA is O 1.6 pu O 0.4 pu 0.2 pu O 0.8 pu

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter11: Transient Stability
Section: Chapter Questions
Problem 11.8P
icon
Related questions
icon
Concept explainers
Question
The reactance of a generator is given as 0.4 per unit based on the generator's nameplate rating
of 100 kV, 200 MVA. The reactance in per unit for a base of 50 kV, 100 MVA is
O 1.6 pu
O 0.4 pu
0.2 pu
0.8 pu
Transcribed Image Text:The reactance of a generator is given as 0.4 per unit based on the generator's nameplate rating of 100 kV, 200 MVA. The reactance in per unit for a base of 50 kV, 100 MVA is O 1.6 pu O 0.4 pu 0.2 pu 0.8 pu
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Knowledge Booster
Load flow analysis
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning