Two power system areas operating at a nominal frequency of 60 Hz are connected with a tie line, and have the following characteristics: Area 1: R1 = 0.015 pu and D1 = 0.9 pu on a base of 1500 MVA Area 2: R2 = 0.02 pu and D2 = 1 pu on a base of 400 MVA The power flow direction on the tie line is from Area 1 to Area 2. Using a common base of 1000 MVA, what is the change in prime mover power (in MW) in Area 1 (APmech1) for a load increase of 250 MW in Area 1? Select one: O a. None of these O b. 816.99 MW O c. 164.44 MW O d. 205.33 MW
Q: Suppose two generators supplying a load. Generator-1 has a no-load frequency of 61.5 Hz and a slope…
A: The resulting power frequency diagram is shown below
Q: Three-phase, 4-wire, wye-connected systems are created by connecting ____ single-phase transformers…
A: In the “Y” (wye) configuration, three single-phase transformers to create three-phase, 4-wire,…
Q: 8.1 The load duration curve for a power station is as shown in the below figure. The reserve…
A: we need to determine reserve capacity.
Q: 1-Which function we call for three phase short circuit occurs in synchronous generator armature…
A: When a fault is taking place on a 3 phase system the electrical quantities are severely unbalanced.…
Q: 25 20 15 10 4 12 16 20 24 hours 12 16 24 hours Load curve A Load curve B t the load and duration…
A: In this question, we have given daily load curve of two loads..We have to find out load factor…
Q: Table Qza Time (hours) 0-6 6-12 12-14 14-18 18-24 Load (MW) 45 135 90 150 75 Referring to the Table…
A: Dear student as per our guidelines we are supposed to solve only one question in which it should…
Q: A certain power station has the following daily load cycle:- Time (6-8)am (8-12)am (12-16)pm…
A:
Q: 3. A three-phase 60 Hz Wye connected, 2,000-kVA, 2,300-V alternator give a short circuit-test…
A: The solution is given below
Q: A substation has two feeders, Sub Feeder-A have demand at a time is 35 KW and Sub Feeder-B have…
A: Given data, Individual demand is given, Demand on feeder A is 35 KW Demand on feeder B is 42 KW…
Q: A substation rated 1250 kVA is operating at full-load at 0.8 pf lagging and to carry an addition…
A: A substation is a place included in the electrical power generation system where electrical voltage…
Q: It is desired to correct the 2,400-kVa 0.65 lagging power factor load in a plant to unit
A: The complex power in an AC system is defined as the product of rms value of applied voltage and…
Q: • Choose the correct answer: 1. These substations are usually located at the generating stations a)…
A: In a power system, power generated in power station is to be transmitted to load(consumers). When…
Q: The impedance Z1 and Z2 are connected in parallel across 200 V, 50 HZ single phase ac supply. Z1…
A: Ohm's law: This law states that the current is directly proportional to the voltage and inversely…
Q: Two generators are supplying a load. Both the generators have a no-load frequency of 61.5 Hz and the…
A:
Q: onsider the above approximate equivalent circuit for IM. A six-pole, 220Volt (line to line), 50Hz,…
A: Disclaimer: Since you have asked multipart questions, we will solve the first three subpart for…
Q: 1- Draw the load curve of power station 2- Draw the load curve of loads(A,D) 3- Find the ratio…
A:
Q: A SUBSTATION RATED 1250 KVA IS OPERATING AT FULL LOAD AT 0.8 PF LAGGING AND TO CARRY AN ADDITIONAL…
A: The substation is an electrical substation is a subsidiary station of energy technology,…
Q: Consider the above equivalent circuit of IM, A six pole, 250 volt(line to line), 60Hz, Y connected ,…
A: Dear student as per our guidelines we are supposed to solve only one question in which it should…
Q: Estimate the distance over which a load of 15000 KW at p.f-0.8 lagging can be delivered by a 3-phase…
A:
Q: 2. Generating station at Musandam has the following load cycle. (Refer the data sheet below).…
A:
Q: wo generating stations A and B have the capacities 500MW and 800MW respectively are interconnected…
A: It is given that: 1. Two generating stations A and B have the capacities 500MW and 800MW…
Q: The real power delivered by a source to two impedances, Z1=3+j4 ohm and Z2=10 ohm, connected in…
A: This question belongs to circuit theory . It is based on the concept of power consumption in the…
Q: Question 4 Two single Phase loads have the following characteristics Load 1: 40Kw, pf= 0.8 Lagging,…
A: Transformer is a static device which is used to step up or down the voltage/Current level without…
Q: 2. calculate the n at 25% , 50% , 75% , 100% and 125% full load condition for u.p.f and 0.8 p.f lag…
A:
Q: Electric Machine; Check image, all question there. Consider the above approximate equivalent…
A: Given Data: R1=0.5Ω , R2=0.25 Ω, X1=0.75 Ω, X2=0.5 Ω, Xm=100 Ω, Rc=500 Ω
Q: Q-1: Choose the correct answer: 1. These substations are usually located at the generating stations…
A:
Q: circuit feeding a single-phase load of 2.75 kW at 0.85 power factor and 240 V at an ambient…
A: We are authorized to answer three subparts at a time, since you have not mentioned which part you…
Q: A 3-phase line 30 km long delivers 3000 kW at 33 kV, 50 Hz and p.f. 0.8 lagging. The resistance and…
A:
Q: Problem 2: The following figure shows a power system consisting of two parts, A and B. Bus #1 is…
A: When both circuit breaker will be open then there will be no interconnection between plant A and…
Q: Q2. A series of motor (Load 1) and lighting (load 2) are connected to an AC source as shown in…
A: Since you have asked only for (ii) so I have posted solution only for (ii) . This question belongs…
Q: For which of the following, power flow studies are not undertake Steady state Normal operating…
A: In this we will see in which system power flow studies are not undertaken..
Q: A three phase,Y connected, 215 V (line to line), 7.5 kW, 60 Hz, three pole IM has the following…
A:
Q: 5.5 kW, 1450 rpm. L-type equivalent circuit and parameters for a continuous sinusoidal phase of a…
A: Given: 5.5 kW, 1450 rpm, line voltage 220 V and frequency 50 Hz. R1=0.21Ω, R2=0.18Ω,…
Q: 13/ choose the correct answer The variation of the load is considered over a period of one year…
A:
Q: A substation rated 1250 kVA is operating at full-load at 0.8 pf lagging and to carry an additional…
A: Methods to improve power factor Shunt Capacitor Phase modifier Synchronous condenser ( Floating…
Q: A source of AC emf E₁ = 120/30º volts with an impedance of Z₁ = 2/0° ohms is connected in parallel…
A: In this question we will find load current for parallel connected AC source....
Q: A substation rated 1250 kVA is operating at full-load at 0.8 pf lagging and to carry an additional…
A: Inductive element consume reactive power but Capacitive elements deliver reactive power into the…
Q: QUA power plant has to meet the following load demand: Load A: 100 MW from 8 AM - 6 PM Load B: 150…
A:
Q: A SUBSTATION RATED 1250 KVA IS OPERATING AT FULL LOAD AT 0.8 PF LAGGING AND TO CARRY AN ADDITIONAL…
A: Methods to improve power factor Adding shunt Capacitor Phase advancer Synchronous condenser ( Motor…
Q: . A certain power station has the following daily load cycle:- Time (6-8)am (8-12)am (12-16)pm…
A:
Q: In the chopper circuit shown in figure below, E=220 V, L= 1.5 mH, R=0.5 ohm and it is operating with…
A:
Q: Which form of renewable energy occupies limited space? O Wind Energy with more turbines O Bio energy…
A: As per bartleby guidelines for more than one question asked only first is to be answered please…
Q: 9. The peak load on a power station is 40 MW. The loads having maximum demands of 18, 12, 8 and 9 MW…
A: Given, Peak Load = 40 MW The loads having maximum demands of 18, 12, 8 and 9 MW Capacity of the…
Q: 2 (a) Show that over the length of one transposition cycle of a power line, the total flux linkages…
A: Transmission lines- Transmission lines are basically a part of an electrical system, through which…
Q: A balanced 3-phase load consists of 3 coils each of resistance of 6 Ω and inductive reactance of 8…
A: Given: R=6 Ω and XL=8 Ω
Q: Q5: (A) A 100 KVsurge travels on an overhead line of surge impedance 400 Q.The line is connected to…
A: Note:We are authorized to answer one question at a time since you have not mentioned which question…
Q: A 60Hz sourcewith an effective voltage of 240 volts supplies 4500 volt-amp to a load with a p.f. of…
A: voltage =240 volts p.f. of 0.75 lagging.
Q: In a house there is a three-wire system configured as follows: A refrigerator with an impedance of…
A:
Q: 10A. Calculate the power consumed of the load, load impedance and power factor of the load. c) What…
A: a. Given NP=1NS=240Rm=1 ΩXm=0.5 ΩRz=0.5 ΩXz=0.25 Ω
Trending now
This is a popular solution!
Step by step
Solved in 2 steps with 2 images
- 5.5 kW, 1450 rpm. L-type equivalent circuit and parameters for a continuous sinusoidal phase of a star connected 3-phase ASM with line voltage 220 V and frequency 50 Hz are given as follows, ignoring core (iron) losses: R1=0.21 Ohm, R2=-0.18 Ohm, X1=X2-0.66 Ohm and Xm = 9.9 Ohm How many times the inrush current will be the rated current when the ASM is started directly? Answer options group 8.0815 2.6455 4.3763 7.1534 1.2558 6.3414 5.2280 3.7473Electric Machine; Check image, all question there. Consider the above approximate equivalent circuit for IM. A six-pole, 220Volt (line to line), 50Hz, Y connected, three phase IM has the following on a per phase basis: R1=0.5Ω , R2=0.25 Ω, X1=0.75 Ω, X2=0.5 Ω, Xm=100 Ω, Rc=500 Ω The friction and windage loss is 150 W. Determine the following at its rated slip of 3.5% a)Total Impedance(Zt) b)Rotor Copper Loss c)Core loss(Pm) d)Shaft Power(P0) e)EfficiencyIn a house there is a three-wire system configured as follows: A refrigerator with an impedance of (10 + j 10) Ω is connected to line L1 and to a neutral. And to line L2 and neutral all the lighting in the house consisting of 10 luminaires of 20 W each. In addition, there is a 240 V dryer that consumes 8 kW connected between the two lines. Calculate current in line L1, line L2 and neutral total power consumed Problem was Initially stated in spanish, i will add it in case it works. En una vivienda se tiene un sistema trifilar configurado de la siguientemanera. Se tiene conectada a la línea L1 y a neutro una refrigeradora con impedancia de (10 + j 10)Ω y a la línea L2 y neutro toda la iluminación de la casa consistente en 10 luminarias de 20 W cadauna. Además, se tiene una secadora a 240 V que consume 8 kW. Calcule a) corriente de la línea L1 yde la línea L2 y de neutro b) potencia total consumida.
- A Factory is supplied froma 3-phase, 4-wire, 400 V, simmetrical system. The resistance of each line is 0.4 Ωand of the neutral 0.6 Ω. The power input to the main is as follows: 10 KVA at a laggin poer factor ofd 0.7 to phase R, 10 KVA at a leading power factor of 0.7 to phase S, and 10 KVA at unity power factor to phase T. Calculate the current in the neutral wire and the voltaje between line R and the neutral at the Factory. Phase secuence RST.A three phase,Y connected, 215 V (line to line), 7.5 kW, 60 Hz, three pole IM has the following parameter values in Ohm/phase referred to the statorR₁ = 0.294 Ohm, R₂ = 0.144 Ohm, X₁ = 0.203 Ohm, X₂ = 0.409 Ohm, Xm = 10.25 Ohm.The total friction,windage and core losses may be assumed to be constant at 350 W independent of load. For a slip s = 0.02, compute the followingsa) Stator Currentb) Power Factor(pf)c) Rotor Speedd) Power Output(Shaft)e) Output(Shaft) Torquef) Efficiency(n)For transferring electrical power at 220 kV, six conductors of ACSR Drake constitute a 60Hz double circuit three phase line arranged as shown below. The vertical spacing between consecutive conductors is 14ft; the longer horizontal distance is 32ft whereas the shorter horizontal distance is 25ft. a. Find the inductance per phase per mile and the inductive reactance per phase in ohms per mile. b. Find the capacitive reactance to neutral in ohm-miles. c. Find the resistance per phase per mile in ohms per miles. d. If the length of the line is 90 miles then draw an equivalent circuit of the line and analyse the open circuit and short circuit performance of the line. e. Find the maximum power we can transmit over the line. f. If the line is delivering power to a load of 20MW at 0.8 power factor lagging then find the voltage at the receiving end of the line. Also, Determine the voltage regulation, losses and efficiency of the line. g. If a fixed shunt compensation of 3 MVAr is attached at…
- Which termination would result to a phase change of 180 degrees at the load if Zo = 100 ohm? a. 50 ohm b. short circuit c. 75 ohm d. all of these What is the purpose of impedance matching? a. maximum return loss b. maximum SWR c. maximum load power d. maximum reflection A short piece of transmission line that may be open or shorted and used for impedance matching purposes. a. converter b. decoder c. stub d. transformerThe VSWR on an 50-Ohm transmission line is 5. The distance between successive voltageminima is 80 cm while the distance from the load to the first minimum is 30 cm. What are thereflection coefficient and load impedanceEstimate the distance over which a load of 15000 KW at p.f-0.8 lagging can be delivered by a 3-phase T.L having conductor each of resistance 0.8 2 per km the voltage at the receiving end is to be 132 KV and the losses in the line is to be 5% of received power
- L-type equivalent circuit and parameters for a continuous sinusoidal phase of a 5.5 kW, 1450 rpm, line voltage 220 V and frequency 50 Hz star-connected 3-phase ASM, ignoring core (iron) losses given as follows: R1=0.21 Ohm, R2=0.18 Ohm, X1=X2=0.66 Ohm and Xm=9.9 Ohm How many times the inrush current will be the rated current when the ASM is started directly?L-type equivalent circuit and parameters for a continuous sinusoidal phase of a 5.5 kW, 1450 rpm, line voltage 220 V and frequency 50 Hz star-connected 3-phase ASM, ignoring core (iron) losses given as follows: R1=0.21 Ohm, R2=0.18 Ohm, X1=X2=0.66 Ohm and Xm=9.9 Ohm How many times the rated current will the inrush current be when the ASM is started directly?Electric Machine-check image, all question there. Consider the above equivalent circuit of IM, A six pole, 250 volt(line to line), 60Hz, Y connected , three phase IM has the following parameters on a per phase basis: R1=0.125Ω , R2=0.45 Ω, X1=0.5 Ω, X2=0.75 Ω, Xm=50 Ω, Rc=225 Ω The friction and windage loss is 115 W. Determine the following at its rated slip of 1.5% a)Excitation Circuit b)Power developed by motor(Pd) c)Shaft Power(Pshaft) d)Shaft Torque(Tshaft) e)Efficiency