Two single-phase transformers having equal turns ratio supply, in parallel a secondary load of 750 A at 0.80 p.f. lagging. For each transformer the secondary are (0.10+j0.20) ohm and (0.05+j0.40) ohm, respectively. Determine the output current for each transformer.
Q: True or False? Consider a 3 phase transformer with same line to line voltage ratio. The delta…
A: Delta to Delta transformer: The primary phase current is,I1=13IL1The secondary phase currennt…
Q: Consider a bank of three single-phase two-winding transformers whose high-voltage terminals are…
A: Two connected windings on the same core are modelled by the single-phase two-winding transformer.…
Q: A three-phase generator step-up transformer i
A:
Q: B: List the location and equation of Economical Number of Transformers operation of distribution…
A: Distribution system: Distribution system is the essential part of power system. It is used to…
Q: Describe the On-load and No-load in transformers
A: On-load in transformer Current flows through the secondary winding and out to the load when an…
Q: 1) What are the advantages and disadvantages of 3- phase transformers over 3 single-phase bank of…
A: 1.) The advantages of 3- phase transformers over 3 single-phase bank of transformers are as follows:…
Q: Neglecting resistance, transformer phase shift, and magnetizing reac- tance, draw the equivalent…
A:
Q: Consider Figure 1 of the text. For an ideal phase-shifting transformer, the impedance is unchanged…
A: Whenever the impedance is seen from the other side of the transformer it is given as:
Q: Q3) What are the elements finding from no-load test of single phase transformer?
A: At no load test rated voltage is applied with secondary open circuited. At no load only magnetizing…
Q: A single-phase transformer bank has a rating of 30 MVA, 132kV/33 kV. By referring to the standard…
A: Given data, Rating of transformer P = 30 MVA Primary voltage Vp= 132 kV Secondary Voltage Vs=33 kV…
Q: 1_ For an unbalanced load connected to a yy transformer, what would be the form/ shape of the output…
A: According to the question we have to discuss about, For an unbalanced load connected to a yy…
Q: Consider that three single-phase transformers are connected as Delta in the primary and Wye in the…
A:
Q: If a 50-turn transformer winding has a 120-V rms applied voltage, and if the peak coupling flux is…
A: Given values are - TurnsN=50Vt=120VoltFluxϕ=20mWb
Q: Derive step by step, the electromotive force equation for a single-phase transformer.
A:
Q: 4. An Open-Wye/Open-Delta transformer, as shown in Figure, is formed by two identical single-phase…
A: Step 1:- Part (a) Assume the 3-phase load is delta connected. Observe that between phase b and c an…
Q: Derive physically the reason of the phase shift in three phase transformer and show the phase shift…
A: The given problem can be laid down into parts. Firstly, the reason of the phase shift in the three…
Q: 1. The RMS value of induced emf in the primary N1 winding is E1 =; E2 = 2. In ideal transformer on…
A:
Q: Why do we represent leakage flux in a transformer by inductive reactance? 2. What will happen if…
A: In the transformer, the magnetic flux is produced by both the primary and secondary winding…
Q: a) An ideal single-phase two-winding transformer with turns ratio a, = N1/N2 is con nected with a…
A: A. The basic relation for a single- phase two winding transformer…
Q: 10 A three-phase transformer is given. The number of turns of the high voltage winding is N1=850 and…
A: In this question we need to find a type of winding connected in LV side.
Q: (c) Explain the losses of a real single-phase transformers.
A: In this question we will write about single phase transformer losses....
Q: Explain the importance of transformer and basic insulation level in the distribution system. Justify…
A: The detailed answer to the given question is solved below according to the given parameters and…
Q: For a conceptual single-phase phase-shifting transformer, the primary voltage leads the secondary…
A: Note: As per our policy, I have attempted the first three subquestions. Given data: E1=E2+308E2=277…
Q: The efficiency of two identical transformers under load conditions can be determine by what test?
A:
Q: Data from short-circuit and open-circuit tests of a 25-kVA, 6900-230 V, 60 Hz transformer are given…
A:
Q: why is there preferable use isolating transformers with cascade transformer unit , if the power…
A: Autotransformers are also known as Isolation Transformer. This is due to the fact that their…
Q: Consider a single phase transformer of rating 150 KVA, 3600/360, 50 Hz. Let the series resistance…
A: Formula to calculate voltage required to produce rated current at short circuit is: VSC=V1×ZPUwhere…
Q: 9. While conducting short short circuit test in a transformer, which side is short circuited?
A: We are authorized to answer one question at a time, since you have not mentioned which question you…
Q: . - what information could be obtained from open circuit test on single phase transformer? · what is…
A: Open circuit test is also known as No load test. It is perform by opening the primary of transformer…
Q: 4. Write a conclusion for the experiment, stating the role of core loss.component and magnetizing…
A:
Q: In the transmission system shown in the figure above, the rated kVA of transformer 1, T1, is 1000…
A:
Q: Given
A:
Q: PROBLEM A 3300V/440V, single-phase transformer takes a no-load current of 0.8A and the iron loss is…
A:
Q: Q1: What is the influence of transformer connections in single-phase transformers connected for 3-…
A: According to the Bartleby guidelines “Since you have asked multiple question, we will solve the…
Q: 2. What are the necessary conditions for successful operation of two single- phase transformers?
A: As per Bartleby guidelines we are allowed to solve only one question, please ask the rest again.
Q: at happens if one phase of a 3-phase transformer fails?
A: Primary delta connected and secondary star connected: If the primary (delta) side loses one phase of…
Q: A single-phase two-winding transformer rated 90 MVA, be connected as an autotransformer rated 80/200…
A:
Q: A three-phase Y-Y transformer is rated at 25 MVA, 13.8-kV:69-kV and has a single-phase equivalent…
A:
Q: A transformer on no-load has a core-loss of 20 W, draws a current of 1 A (rms) and has an induced…
A: According to guidelines we need to solve only the first question. According to the question we have…
Q: a) Discuss two (2) advantages and disadvantages of using three single-phase transformers instead of…
A: NOTE: Since you have asked multiple questions, we will solve the first question for you. If you want…
Q: When the similar terminals of high voltage and low voltage windings of a transformers are diagonally…
A: A transformer is used to either up or down the voltage level. It can also be used to provide…
Q: 02/A/ What are the conditions for satisfying parallel operation of single phase transformer? Deduce…
A: “Since you have asked multiple questions, we will solve the first question for you. If you want any…
Q: A 200 – kVA transformer with impedance of 5 percent and the power factor of the load is 85 percent.…
A: Given, A transformer with KVA rating, S=200 kVA Impedance, Z=5% Power factor, cosϕ=85%=0.85 Primary…
Q: A 50-kVA 13.8-kV/208-V (rms, line-line) ∆−Ythree-phase distribution transformer has a per-unit…
A: Dear student as per our guidelines we are supposed to solve only one question in which it should…
Q: A transformer has a reactive drop of 6% and a resistive drop of 2.5%. Determine the lagging power…
A: The voltage regulation is given by the expression as shown below: In terms of the values of the…
Q: Q2. (a) Explain what is per unit system? What are the advantages of per-unit computations? Prove for…
A: PU system: Per Unit system is a quantity expression system used in an electrical power system which…
Q: e) What are the specifications for new insulating oils for transformer and switchgears? What are the…
A: The transformer oil has excellent electrical insulating properties and it can stand very high…
Q: A 10 MVA three phase load is to be served by a three phase transformer at a line voltage of 13.8 kV.…
A: Transformer is the static device it is used to transfer the electrical power from one terminal to…
Q: in distribution transformers; What is 30 degrees phase shift in delta-star connection? What are the…
A: In the star-delta connection, the primary side of the transformer is in delta configuration while…
- Two single-phase transformers having equal turns ratio supply, in parallel a
secondary load of 750 A at 0.80 p.f. lagging. For each transformer the secondary are
(0.10+j0.20) ohm and (0.05+j0.40) ohm, respectively. Determine the output current
for each transformer.
Step by step
Solved in 3 steps with 3 images
- Three single-phase, two-winding transformers, each rated 450MVA,20kV/288.7kV, with leakage reactance Xeq=0.10perunit, are connected to form a three-phase bank. The high-voltage windings are connected in Y with a solidly grounded neutral. Draw the per-unit equivalent circuit if the low-voltage windings are connected (a) in with American standard phase shift or (b) in Y with an open neutral. Use the transformer ratings as base quantities. Winding resistances and exciting current are neglected.Consider Figure 3.4. For an ideal phase-shifting transformer, the imda nce is unchanged when it is referred from one side to the other. (a) True (b) FalseA single-phase 50-kVA,2400/240-volt,60-Hz distribution transformer is used as a step-down transformer at the load end of a 2400-volt feeder whose series impedance is (1.0+j2.0) ohm. The equivalent series impedance of the transformer is (1.0+j2.5) ohms referred to the high-voltage (primary) side. The transformer is delivering rated load at a 0.8 power factor lagging and at a rated secondary voltage. Neglecting the transformer exciting current, determine (a) the voltage at the transformer primary terminals, (b) the voltage at the sending end of the feeder, and (c) the real and reactive power delivered to the sending end of the feeder.
- A single-phase 100-kVA,2400/240-volt,60-Hz distribution transformer is used as a step-down transformer. The load, which is connected to the 240-volt secondary winding, absorbs 60 kVA at 0.8 power factor lagging and is at 230 volts. Assuming an ideal transformer, calculate the following: (a) primary voltage, (b) load impedance, (c) load impedance referred to the primary, and (d) the real and reactive power supplied to the primary winding.In developing per-unit equivalent circuits for three-phase transformers. under balanced three-phase operation. (i) A common Sbase is selected for both the H and X terminals. (ii) The ratio of the voltage bases Vbase/VbaseX is selected to be equal to the ratio of the rated line-to-line voltages VratedHLL/VratedXLL. (a) Only one of the above is true. (b) Neither is true. (C) Both statements are true.The leakage reactance of a three-phase, 300-MVA,230Y/23-kV transformer is 0.06 per unit based on its own ratings. The Y winding has a solidly grounded neutral. Draw the per-unit equivalent circuit. Neglect the exciting admittance and assume the American Standard phase shift.
- A single-phase two-winding transformer rated 90MVA,80/120kV is to be connected as an autotransformer rated 80/200kV. Assume that the transformer is ideal. (a) Draw a schematic diagram of the ideal transformer connected as an autotransformer. showing the voltages, currents, and dot notation for polarity. (b) Determine the permissible kVA rating of the autotransformer if the winding currents and voltages are not to exceed the rated values as a two-winding transformer. How much of the kA rating is transferred by magnetic induction?The ideal transformer windings are eliminated from the per-unit equivalent circuit of a transformer. (a) True (b) FalseReconsider Problem 3.64 with the change that now Tb includes both a transformer of the same turns ratio as Ta and a regulating transformer with a 4 phase shift. On the base of Ta, the impedance of the two comp onents of Tb is jO.1 per unit. Determine the complex power in per unit transmitted to the load through each transformer. Comment on how the transformers share the real and reactive pors.
- Consider the oneline diagram shown in Figure 3.40. The three-phase transformer bank is made up of three identical single-phase transformers, each specified by X1=0.24 (on the low-voltage side), negligible resistance and magnetizing current, and turns ratio =N2/N1=10. The transformer bank is delivering 100 MW at 0.8 p.f. lagging to a substation bus whose voltage is 230 kV. (a) Determine the primary current magnitude, primary voltage (line-to-line) magnitude, and the three-phase complex power supplied by the generator. Choose the line-to-neutral voltage at the bus, Va as the reference Account for the phase shift, and assume positive-sequence operation. (b) Find the phase shift between the primary and secondary voltages.A three-phase transformer is rated 1000MVA,220Y/22kV. The Y-equivalent short-circuit impedance, considered equal to the leakage reactance, measured on the low-voltage side is 0.1. Compute the per-unit reactance of the transformer. In a system in which the base on the high-voltage side of the transformer is 100MVA,230kV what value of the per-unit reactance should be used to represent this transformer?For an ideal 2-winding transformer, the ampere-turns of the primary winding, N1I1 is equal to the ampere-turns of the secondary winding, N2I2 (a) True (b) False