Two transformers, each rated at 100 kVA, 11000/2300 V, 60 Hz, are connected in open delta on primary and secondary side. A 120 kVA, 2300 V, 0.866 lagging power factor, three phase, delta- connected load is connected to the transformer bank. What is the line current on the high-voltage side? O 6.3 A O12.6 A O 3.6 A 10.9 A
Q: The primary and secondary winding resistances of a 30 KVA, 6600 /250 V, 1 phase transformer are 8…
A:
Q: b. A single-phase power system is shown below. The power source feeds a l00-kVA, 14/2.4 - kV…
A: A single-phase power system consist of source, feeder, transformer, and load is shown below. The…
Q: 1. Cotabato Light and Power Company supplies two-single phase transformers at San Pablo Area banked…
A: As per Bartleby guidelines we are allowed to solve only one question, please ask the rest again.
Q: Example 33.7. A 5,000-kVA, 3-phase transformer, 6.6/33-kV, NY, has a no-load loss of and a full-load…
A: In this question , we will find primary voltage for given load of 3 phase transformer....
Q: Two single phase transformers of 1000 kVA and 500 kVA with equal voltage rating 11 kV/ 400V…
A: Given Two single phase transformers of 1000 KVA and 500 KVA with equal voltage rating 11KV/400 v The…
Q: Assuming a secondary system consisting of step down distribution transformer (DT) with line to line…
A: Given VL=380 V Vs=Vph=220 V S1=15 kVA , 0.8 pf S2=30 kVA , 0.8 pf R=0.5 Ω/km ; X=0.2Ω/km
Q: A 3-phase 410, 50HZ supply is given to delta connected load with impedance (6-j11) ohms. The line…
A: Part (a): In a delta connection, an impedance is connected between any two phases. The voltage…
Q: A single phase 100KVA 4000/240V 60 Hz. transformer, whose impedance refered to low voltage side is…
A: We need to find a secondary voltage of Transformer at given loading condition.
Q: A single phase 100KVA 4000/240V 60 Hz. transformer, whose impedance refered to low voltage side is…
A: Transformer is a static electrical device which transfers power from one circuit to another circuit…
Q: A 3-phase, 230 V, 30 KVA, 0.9 PF(lag) load is supplied by three 10 kVA, 1330/230 V, and 60 Hz…
A: Voltage regulation: It means how much fluctuation in the voltage at the receiving terminal. It is…
Q: Two three-phase 11kV/ 380 V transformers are connected in parallel to serve a load of 36 kVA at…
A: The secondary side voltage rating of transformer is 380 V. So equivalent circuit will look like
Q: 2. A 3-phase delta connected load each phase of which has resistor of 10 ohm and inductor of 8 ohm…
A:
Q: A 10 kVA, 1000 V / 200 V, 50 Hz, single phase transformer has HV and LV sidewinding resistances as…
A:
Q: A) Two 1-phase transformers with equal turn ratio have impedances of (0.5 + j3) and (0.6+j10) with…
A: The parallel configuration of transformer in s distribution system or load driving application helps…
Q: Two 200/400 V, transformers are operated in parallel to share a load power factor leading.…
A: Conditions for Parallel Operation- In order that the transformers work satisfactorily in…
Q: 7. A substation receives 6000 kVA at 6 kV, 0.8 p.f. lagging on low voltage side of a transformer…
A: The solution can be achieved as follows.
Q: Based on the following power system, both transformers are equipped with tap changing facilities…
A: In the given power system, it is given: The impedance of the line and transformers at 132 kV:-…
Q: cotabato light and power company supplies two single phase transformers at san pablo area banked in…
A: Apparent power = voltage ×current. Power delivered to load = voltage ×current ×cos(angle between…
Q: At a certain location in an electric system, the available fault MVA is 400. A 15 MVA, 34.5 kV/6.24…
A: Given, Base MVA rating, Sbase=15 MVA Fault or short circuit MVA rating, Ssc=400 MVA Per unit…
Q: Three identical 400-MVA single-phase transformers, rated at 13.8 kV:199.2 kV are to be connected in…
A: Given The power rating of each single-phase transformer is MVA1-ϕ=400 MVA Rated voltage 13.8 kV :…
Q: 100-kVA 6000/230-V single-phase transformer has the following resistances and mctances: R, = 4.320;…
A:
Q: Two three-phase transformers of equal voltage ratios are operating in parallel. The load draws a…
A: Given: load current IL=200∠-cos-10.9IL=200∠-25.84° AZ1=0.1+j0.3 ΩZ2=0.2+j0.5 Ω
Q: b) Two three-phase 11kV/ 380 V transformers are connected in parallel to serve a load of 36 kVA at…
A: (b) Given, two 3-ph 11kV/380 V transformer are connected in parallel. The total rating or demand of…
Q: Single phase transformer has 24KVA, 2400/240, 50 Hz. Its series impedance Z, 0.15+j0.6pu connected t…
A:
Q: A three-phase transformer bank is connected wye–delta. The primary voltage is 12,470 V, and the…
A: Yes, it is possible to connect the two remaining transformers in the open delta configuration in…
Q: Two single-phase transformers A and B are connected in parallel to serve a 600-A single phase load…
A:
Q: A substation receives 6000 kVA at 6 kV, 0.8 p.f. lagging on low voltage side of a transformer from a…
A: The single line diagram of the system is shown below:
Q: Calculate the ratio of the kW output of transformer A to the kW output of transformer B. Both are…
A:
Q: A 50 Hz, 110 kVA single phase transformer has a voltage ratio of 11000/440 V. The iron loss measured…
A: Given transformer of50 Hz, 110 kVA ,11000/440 vThe iron loss is Pi=1100 wThe full load copper load…
Q: 3. Two 6600/440 Volts transformers, A is 250 KVA and B is 500 KVA, have the following…
A:
Q: 9. A 3-phase transformer rated at 1,000 kVA, 11/3.3 kV has its primary windings wye-connected and…
A:
Q: Three single-phase two winding transformers, each rated 400 MVA, 13.8kV/199.2kV, leakage reactance…
A:
Q: wb at 5o Hz when noLoad the الملوضوع : Single phase transformer has aturns ratio of 144/432 and…
A:
Q: 6. 150 kVA, 2800-240 V, 50 Hz transformer. Req.Ls Step down transformer delivers 135 kW to a load at…
A: “Since you have posted a question with multiple subparts, we will solve the first three subparts for…
Q: A Wye-Delta transformer is connected to a 66 kV input three-phase transmission line. Each…
A: According to company policy , I am solving first 3 sub part According to the above statement, we can…
Q: A small industrial plant draws an average load of 122 A at 0.73 power factor lagging from the…
A: Since we only answer up to 3 sub-parts, we’ll answer the first 3. Please resubmit the question and…
Q: 2. Given three identical ideal single-phase transformers with each rated at 100KVA and 7kV/3.5kV,…
A:
Q: A single phase 100KVA 4000/240V 60 Hz. transformer, whose impedance refered to low voltage side is…
A: Transformer rating=100KVA, 4000/240V, 60Hz Impedance referred to low side=0.0015+i0.002Ω Load side…
Q: A 3-phase transformer, ratio 6.6kV/33, wye/delta, 2 MVA has a primary resistance of 0.08 ohms/phase…
A:
Q: there is a three-phase transformer that supplies 12 kW to a neighborhood supermarket, the same is in…
A:
Q: There single-phase transformers are 3 transformers (Each of them is to be connected Delta-Delta) is…
A: The high voltage side voltage is 2200 where a transmission line of impedance (0.15+j0.80ohms )is…
Q: Two three-phase 11kV/ 380 V transformers are connected in parallel to serve a load of 36 kVA at…
A: To find the load share by both transformer we equate the power drawn by load is equal to power…
Q: 9- The impedance of two single phase transformers referred to secondary are (0.5+j3) and (0.6+j10)Q.…
A: In the question, two parallel transformer are connected to load. If total. Load =100W Find the…
Q: Two synchronous machines are connected through three phase transformer to the transmission line as…
A: Positive sequence network Z1=(0.08+0.15+0.2)∥(0.2+0.08)Z1=0.169Ω
Q: A single-phase transformer rated 2400 – 277 V, 50 kVA, 60 Hz is tested with the following results:…
A: Dear student as per our guidelines we are supposed to solve only one question in which it should…
Trending now
This is a popular solution!
Step by step
Solved in 2 steps
- The ratings of a three-phase three-winding transformer are Primary(1): Y connected 66kV,15MVA Secondary (2): Y connected, 13.2kV,10MVA Tertiary (3): A connected, 2.3kV,5MVA Neglecting winding resistances and exciting current, the per-unit leakage reactances are X12=0.08 on a 15-MVA,66-kV base X13=0.10 on a 15-MVA,66-kV base X23=0.09 on a 10-MVA,13.2-kV base (a) Determine the per-unit reactances X1,X2,X3 of the equivalent circuit on a 15-MVA,66-kV base at the primary terminals. (b) Purely resistive loads of 7.5 MW at 13.2 kV and 5 MW at 2.3kV are connected to the secondary and tertiary sides of the transformer, respectively. Draw the per- unit impedance diagram, showing the per-unit impedances on a 15-MVA,66-kV base at the primary terminals.Three single-phase two-winding transformers, each rated 3kVA,220/110volts,60Hz, with a 0.10 per-unit leakage reactance, are connected as a three-phase extended autotransformer bank, as shown in Figure 3.36(c). The low-voltage winding has a 110 volt rating. (a) Draw the positive-sequence phasor diagram and show that the high-voltage winding has a 479.5 volt rating. (b) A three-phase load connected to the low-voltage terminals absorbs 6 kW at 110 volts and at 0.8 power factor lagging. Draw the per-unit impedance diagram and calculate the voltage and current at the high-voltage terminals. Assume positive-sequence operation.A single-phase step-down transformer is rated 13MVA,66kV/11.5kV. With the 11.5 kV winding short-circuited, rated current flows when the voltage applied to the primary is 5.5 kV. The power input is read as 100 kW. Determine Req1andXeq1 in ohms referred to the high-voltage winding.
- Consider a bank of this single-phase two-winding transformers whose high-voltage terminals are connected to a three-phase, 13.8-kV feeder. The low-voltage terminals are connected to a three-phase substation load rated 2.0 MVA and 2.5 kV. Determine the required voltage, current, and MVA ratings of both windings of each transformer, when the high-voltage/low- voltage windings are connected (a) Y-, (b) -Y, (c) Y-Y, and (d) -.Three single-phase two-winding transformers, each rated 25MVA,54.2/5.42kV, are connected to form a three-phase Y- bank with a balanced Y-connected resistive load of 0.6 per phase on the low-voltage side. By choosing a base of 75 MVA (three phase) and 94 kV (line-to-line) for the high-voltage side of the transformer bank, specify the base quantities for the low-voltage side. Determine the per-unit resistance of the load on the base for the low-voltage side. Then determine the load resistance RL in ohms referred to the high-voltage side and the per-unit value of this load resistance on the chosen base.Three single-phase, two-winding transformers, each rated 450MVA,20kV/288.7kV, with leakage reactance Xeq=0.10perunit, are connected to form a three-phase bank. The high-voltage windings are connected in Y with a solidly grounded neutral. Draw the per-unit equivalent circuit if the low-voltage windings are connected (a) in with American standard phase shift or (b) in Y with an open neutral. Use the transformer ratings as base quantities. Winding resistances and exciting current are neglected.
- A bank of three single-phase transformers, each rated 30MVA,38.1/3.81kV, are connected in Y- with a balanced load of three 1, Y-connected resistors. Choosing a base of 90MVA,66kV for the high-voltage side of the three-phase transformer. spify the base for the low-voltage side. Compute the per-unit resistance of the load on the base for the low-voltage side. Also, determine the load resistance in ohms referred to the high-voltage side and the per-unit value on the chosen base.A single-phase, 50-kVA,2400/240-V,60-Hz distribution transformer has the following parameters: Resistance of the 2400-V winding: R1=0.75 Resistance of the 240-V winding: R2=0.0075 Leakage reactance of the 2400-V winding: X1=1.0 Leakage reactance of the 240-V winding: X2=0.01 Exciting admittance on the 240-V side =0.003j0.02S (a) Draw the equivalent circuit referred to the high-voltage side of the transformer. (b) Draw the equivalent circuit referred to the low-voltage side of the transformer. Show the numerical values of impedances on the equivalent circuits.Determine the positive- and negative-sequence phase shifts for the three- phase transformers shown in Figure 3.36.
- The ratings of a three-phase, three-winding transformer are Primary: Y connected, 66kV,15MVA Secondary: Y connected, 13.2kV,10MVA Tertiary: connected, 2.3kV,5MVA Neglecting resistances and exciting current, the leakage reactances are: XPS=0.09 per unit on a 15-MVA,66-kV base XPT=0.08 per unit on a 15-MVA,66-kV base XST=0.05 per unit on a 10-MVA,13.2-kV base Determine the per-unit reactances of the per-phase equivalent circuit using a base of 15 MVA and 66 kV for the primary.For a short-circuit test on a 2-winding transformer, with one winding shorted, can you apply the rated voltage on the other winding? (a) Yes (b) NoThree single-phase two-winding transformers, each rated 25MVA,34.5/13.8kV, are connected to form a three-phase bank. Balanced positive-suence voltages are applied to the high-voltage terminals, and a balanced, resistive Y load connected to the low-voltage terminals absorbs 75 MW at 13.8 kV. If one of the single-phase transformers is removed (resulting in an open connection) and the balanced load is simultaneously reduced to 43.3 MW (57.7 of the original value), determine (a) the load voltages Va,Vb, and Vc; (b) load currents Ia,Ib, and Ic; and (c) the MVA supplied by each of the remaining two transformers. Are balanced voltages still applied to the load? Is the open transformer overloaded?