3 A 3-phase, 50 Hz transmission line 100 km long, Load current i 5A at 0-9 p.f.lagging and at 110 kV. The resistance and reactance of the line per phase per km are 0-2 Q and 0-42 respectively, while capacitance admittance is 2-5 * × 10- 6 siemen/km/phase. then magnitude of V1 is

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter4: Transmission Line Parameters
Section: Chapter Questions
Problem 4.10MCQ: Transmission line conductance is usually neglected in power system studies. True False
icon
Related questions
icon
Concept explainers
Question
3
A 3-phase, 50 Hz transmission line 100 km long, Load current i 5A at 0-9
p.f.lagging and at 110 kV. The resistance and reactance of the line per phase
per km are 0-2 Q and 0-42 respectively, while capacitance admittance is 2-5
* × 10- 6 siemen/km/phase. then magnitude of V1 is
Transcribed Image Text:3 A 3-phase, 50 Hz transmission line 100 km long, Load current i 5A at 0-9 p.f.lagging and at 110 kV. The resistance and reactance of the line per phase per km are 0-2 Q and 0-42 respectively, while capacitance admittance is 2-5 * × 10- 6 siemen/km/phase. then magnitude of V1 is
Expert Solution
steps

Step by step

Solved in 3 steps with 4 images

Blurred answer
Knowledge Booster
Transmission line parameter
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.