A 3-phase three stepped core transformer having a leakage impedance of 0.15 p.u. The positive sequence reactance of the transformer is equal to 0.6 p.u 0.45 p.u 0.15 p.u 0.3 p.u.
Q: Derive the equation of induced voltage in secondary winding of transformer (load side).
A:
Q: A three phase Y/A transformer rated at 50 MVA, 230/34.5 kV is to be protected using biased…
A:
Q: Equivalent circuit diagram and electromotive force phasor for the idle operation of a step-up phase…
A: A transformer is a static device, it consist of two winding interlinked by common magnetic circuit…
Q: Explain the open circuit test on single phase transformer.
A: Open circuit test :- It is carried out at rated frequency & rated voltage to determine the core…
Q: A 200 – MVA, 15/200 kV single-phase power transformer has a per – unit resistance of 1.2 percent…
A:
Q: What is the difference between transformer and 3ph asynchronous motor
A: The primary and secondary windings of a transformer are known as the stator and secondary windings…
Q: "Under saturated core condition, transformer become a source of harmonics" True False
A: In this question , we will write about harmonics in transformer..
Q: 1_ For an unbalanced load connected to a yy transformer, what would be the form/ shape of the output…
A: According to the question we have to discuss about, For an unbalanced load connected to a yy…
Q: A 40000-KVA, 25000-V/600-kV, single phase transformer has the following series impedances: Z1=…
A:
Q: The shell type transformer has less leakage flux compared to the core type transformer True False
A: In the question, choose the correct option? "The shell type transformer has less leakage flux…
Q: Derive physically the reason of the phase shift in three phase transformer and show the phase shift…
A: The given problem can be laid down into parts. Firstly, the reason of the phase shift in the three…
Q: Mutually induced emf is induced in secondary of the transformer by Flemings right hand rule Select…
A: Here No need of given data
Q: Draw the connections for three phase transformer configuration listed below using single phase…
A: The three-phase transformer configure using three single-phase transformers as below, (a) Star/star…
Q: With the neat diagram explain the construction and working of Sumpner’s or Back –to-Back test of…
A: Step-1 Construction The Sumpner’s or back-to-back test of a single phase of a transformer…
Q: A 4400 volts 60 Hz transformer has a core loss of 840 watts, of which one-third of which is eddy…
A:
Q: Short circuit test on a single phase transformer is performed to determine_____________ a.…
A: Need to Find the correct option
Q: For a conceptual single-phase phase-shifting transformer, the primary voltage leads the secondary…
A: Note: As per our policy, I have attempted the first three subquestions. Given data: E1=E2+308E2=277…
Q: When conducting no-load test on a given single-phase transformer, the following test data were…
A: As per the guidelines, we supposed to answer first three part of the question at a time so please…
Q: What's The relation between turn ratio current ratio annd voltage ratio(if it exists) for single…
A: The transformer is a static device that steps up or steps down the voltage depending upon the turn…
Q: Detailed description of open circuit test on single phase transformer
A: In this question we discuss about open circuit test of transformer .
Q: The diagram for a single phase 60 MVA transformer is given below. Convert it to a Step-down…
A: In this question , we will convert single phase transformer into step down auto transformer..
Q: A 15-kVA, 2400/240-V transformer is to be tested to determine its excitation branch components, its…
A: Solution a)- Equivalent circuit of the transformer referred to high voltage side-
Q: Determine the load sharing in MVA for each transformer. Draw the parallel transformer diagram for…
A:
Q: Differentiate Step-down Transformer and Step-up Transformer
A: The transformer is a device that transfers electric energy from one circuit to another. Based on the…
Q: 3.6 For a conceptual single-phase phase-shifting transformer, the primary voltage leads the…
A:
Q: Consider a single phase transformer of rating 150 KVA, 1500/150, 50 Hz. Let the series resistance…
A: Given: Z1=R1+jX1=0.2+j0.45 ΩZ2=R2+jX2=0.002+j0.0045 ΩKVA=150
Q: 3. A 10 kVA, single-phase transformer has a turns ratio of 15:1 and is supplied from a 2,0 kV…
A: Single phase transformer 10KVA , turn ratio 15:1 Primary side voltage 2KV Find the secondary…
Q: Transformer are rated in kilovoltamperes so the sizing of same is independente of the load power…
A: (1) Transformer are rated in kilovolt amperes so the sizing of same is independent of the load power…
Q: A lø transformer has an equivalent leakage reactance of 0.04 per unit. The full-load copper loss is…
A:
Q: When a closed- delta bank is changed to operate as an open-delta bank, the capacity of the…
A: If one of the transformer of delta-delta connection is removed , then also power can be transformed…
Q: The figure below shows the equivalent circuit of a nominal 240V-120V, 1000 VA, single-phase…
A:
Q: at happens if one phase of a 3-phase transformer fails?
A: Primary delta connected and secondary star connected: If the primary (delta) side loses one phase of…
Q: / Short circuit test on a single phase transformer is performed to determine_____________ a.…
A: Given that Short circuit test on a single phase transformer is performed to determine_____________
Q: if the core loss of 1 phase transformer at full load is 42 W, then the core loss at 25% of load is…
A: Given, 1-ph transformer has Full load core loss(Pc)= 42 watts
Q: A three-phase Y-Y transformer is rated at 25 MVA, 13.8-kV:69-kV and has a single-phase equivalent…
A:
Q: Example 22: In a single-phase transformer, the magnitude of leakage reactance is twice that of…
A: Given that magnitude of leakage reactance of transformer is twice that of resistance of primary and…
Q: During the load test of single-phase transformer, when the secondary terminal voltage increases, the…
A:
Q: A 400-MVA, 240-kV/24-KV, three-phase Y-A transformer has an equivalent series impedance of 1.2 + j6…
A: According to the question we have to find the line-to-line voltage at high terminals of the…
Q: A single-phase transformer, working at unity power factor has an efficiency of 90 % at both…
A:
Q: A single - phase transformer has 0.9 power factor and takes a no - load current of 0.8A . Determine…
A: single - phase transformer has power factor cos¢= 0.9and takes a no - load current of Io= 0.8A…
Q: A 50-kVA 13.8-kV/208-V (rms, line-line) ∆−Ythree-phase distribution transformer has a per-unit…
A: Dear student as per our guidelines we are supposed to solve only one question in which it should…
Q: (b) In a transformer test, data from short circuit and open circuit tests of a 75-kVA, 4600-230V,…
A:
Q: A three-phase Y-Y transformer has specifications of 25 MVA, 15/200 kV and an equivalent series…
A: The solution is given below
Q: A quarter wave transformer is connected between a transmission line of characteristic impedance of…
A: A quarter wave transformer is a transmission line and its length is equal to one-fourth of…
Q: transformer on no-load has a core-loss of 70 W, draws a current of 2.5 A (rms) and has an induced…
A:
Q: A 400-MVA, 240-kV/24-KV, three-phase Y-A transformer has an equivalent series impedance of 1.2 + j6…
A: Delta-Star transformer- A Delta-Star transformer is a transformer whose primary side is in delta…
Q: 5. Write down the equations of a single phase transformer at no-load mode. Give the names of the…
A: Transformer is a static device which is used to step up or down the voltage level or current level.…
Step by step
Solved in 2 steps
- The ratings of a three-phase, three-winding transformer are Primary: Y connected, 66kV,15MVA Secondary: Y connected, 13.2kV,10MVA Tertiary: connected, 2.3kV,5MVA Neglecting resistances and exciting current, the leakage reactances are: XPS=0.09 per unit on a 15-MVA,66-kV base XPT=0.08 per unit on a 15-MVA,66-kV base XST=0.05 per unit on a 10-MVA,13.2-kV base Determine the per-unit reactances of the per-phase equivalent circuit using a base of 15 MVA and 66 kV for the primary.The leakage reactance of a three-phase, 300-MVA,230Y/23-kV transformer is 0.06 per unit based on its own ratings. The Y winding has a solidly grounded neutral. Draw the per-unit equivalent circuit. Neglect the exciting admittance and assume the American Standard phase shift.Using the transformer ratings as base quantities, work Problem 3.13 in per-unit.
- A single-phase 50-kVA,2400/240-volt,60-Hz distribution transformer has a 1-ohm equivalent leakage reactance and a 5000-ohm magnetizing reactance referred to the high-voltage side. If rated voltage is applied to the high-voltage winding, calculate the open-circuit secondary voltage. Neglect I2RandGc2V losses. Assume equal series leakage reactances for the primary and the referred secondary.Consider the adopted per-unit system for the transformers. Specify true or false for each of the following statements: (a) For the entire power system of concern, the value of Sbase is not the same. (b) The ratio of the voltage bases on either side of a transformer is selected to be the same as the ratio of the transformer voltage ratings. (c) Per-unit impedance remains unchanged when referred from one side of a transformer to the other.Reconsider Problem 3.64 with the change that now Tb includes both a transformer of the same turns ratio as Ta and a regulating transformer with a 4 phase shift. On the base of Ta, the impedance of the two comp onents of Tb is jO.1 per unit. Determine the complex power in per unit transmitted to the load through each transformer. Comment on how the transformers share the real and reactive pors.
- Three single-phase, two-winding transformers, each rated 450MVA,20kV/288.7kV, with leakage reactance Xeq=0.10perunit, are connected to form a three-phase bank. The high-voltage windings are connected in Y with a solidly grounded neutral. Draw the per-unit equivalent circuit if the low-voltage windings are connected (a) in with American standard phase shift or (b) in Y with an open neutral. Use the transformer ratings as base quantities. Winding resistances and exciting current are neglected.Consider a bank of this single-phase two-winding transformers whose high-voltage terminals are connected to a three-phase, 13.8-kV feeder. The low-voltage terminals are connected to a three-phase substation load rated 2.0 MVA and 2.5 kV. Determine the required voltage, current, and MVA ratings of both windings of each transformer, when the high-voltage/low- voltage windings are connected (a) Y-, (b) -Y, (c) Y-Y, and (d) -.A single-phase 50-kVA,2400/240-volt,60-Hz distribution transformer is used as a step-down transformer at the load end of a 2400-volt feeder whose series impedance is (1.0+j2.0) ohm. The equivalent series impedance of the transformer is (1.0+j2.5) ohms referred to the high-voltage (primary) side. The transformer is delivering rated load at a 0.8 power factor lagging and at a rated secondary voltage. Neglecting the transformer exciting current, determine (a) the voltage at the transformer primary terminals, (b) the voltage at the sending end of the feeder, and (c) the real and reactive power delivered to the sending end of the feeder.
- With the same transformer banks as in Problem 3.47, Figure 3.41 shows the oneline diagram of a generator, a step-up transformer bank, a transmission line, a stepown transformer bank, and an impedan load. The generator terminal voltage is 15 kV (line-to-line). (a) Draw the per-phase equivalent circuit, aounting for phase shifts for positive-sequence operation. (b) By choosing the line-to-neutral generator terminal voltage as the reference, determine the magnitudes of the generator current, transmiss ion-line current, load current, and line-to-line load voltage. Also, find the three-phase complex power delivered to the load.The per-unit equivalent circuit of two transformers Ta and Tb connected in parallel, with the same nominal voltage ratio and the same reactan of 0.1 per unit on the same base, is shown in Figure 3.43. Transformer Tb has a voltage-magnitude step-up toward the load of 1.05 times that of Ta (that is, the tap on the secondary winding of Tb is set to 1.05). The load is represented by 0.8+j0.6 per unit at a voltage V2=1.0/0 per unit. Determine the complex power in per unit transmitted to the load through each transformer, comment on how the transformers share the real and reactive powers.Consider Figure 3.4. For an ideal phase-shifting transformer, the imda nce is unchanged when it is referred from one side to the other. (a) True (b) False