A 350KW of an industrial load has a power factor of 0.5 lagging. A group of synchronous motors operating at a power factor of 84% leading is installed and the power factor improves to 70% lagging. Determine the total KVA rating of the synchronous motors installed.
Q: A single-phase electrical load draws 1000KVA at 0.6 power factor lagging Find the real and reactive…
A: Given, A single phase load draws, S=100 kVA Power factor, cosϕ=0.6 lagging
Q: Three Impedances each of (8 - j22)N are connected in mesh across a three-phase 400V ac supply.…
A: According the given equation, we can make the circuit diagram shown below
Q: A single phase a.c. generator supplies the following loads : (a) Lighting load of 40 kW at unity…
A:
Q: One needs a 100 kVAr A-connected TCR for a three-phase distribution system of 2.4 kVu, and 60 Hz.…
A:
Q: Calculate the corresponding apparent power (in KVA) taken by the motor & the power factor at which…
A: In this question we need to find a reactive power taken by motor and it's operating power factor.
Q: If the power received at the MU is lognormal with standard deviation of 10DB, the outage probability…
A: According to the question we have to calculate the value of x.
Q: A 3-phase, 420 V, 60 Hz, Y-connected synchronous generator, with a synchronous reactance of 1.20 Ohm…
A: As we have given: VL=420 Vf=60 HzXs=1.2 ΩZs=j1.2 Ωδ=30°Pout=110 kW Step 1: Find E As we know that,…
Q: An industrial plant consisting primarily of induction motor loads absorbs 500 kW at 0.6 power factor…
A: In this question we need to find a KVA rating of shunt capacitor and overall power factor when…
Q: a. The value of excitation current required for full load current at 0.7 pf lagging (over-excited).…
A: The alternator is a machine which converts mechanical energy to electrical energy. It generates…
Q: In 132 kV transmission system, the phase to ground capacitance is 0.01micro F. The inductance being…
A: A powerful thermionic current that flowed between the electrodes ignited the arc. The resistance of…
Q: A three-phase wye-connected generator is connected to an industrial motor load. The generator has an…
A:
Q: An existing industrial plant has an average load of 900 kW at 0.6 pf lagging. To raise the overall…
A:
Q: Q6. The three-phase average power rating of a central processing unit (CPU) on a mainframe digital…
A: Power = 3×VL× IL×cos(pi) From above find the power factor angle then find the reactive power Q =…
Q: 6. If a power system has 10,000 kVA capacity, operating at 0.7 lagging power factor and cost of…
A: consider the given question 6.
Q: A group of small appliances on a 60 Hz system requires 20 kva at 0.85 lagging power factor when…
A:
Q: J52 Q.37: For the mutual coupled electric circuit shown in figure beside if Vs=2020° Volt, find the…
A: According to question: The current in the circuit is calculated as ∵I2Req=40⇒I2×10=40⇒I=2A The…
Q: A 3 phase 300V, delta connected alternator has a synchronous impedance of (0+j10) ohm per phase. IF…
A:
Q: The power consumption of an industry is 500 kVA, at 0.8 p.f lagging. A synchronous motor is added to…
A: Given that power consumption of industry (Load) is 500 kVA at 0.8 power factor lagging and…
Q: The three-phase average power rating of the central processing unit (CPU) on a mainframe digital…
A: Given data, The value of average power of the CPU is P = 22695 W. The three-phase line voltage is…
Q: If a load absord 20KVA at the leading power factor of 0.6 Write the complex form of power
A:
Q: An industrial load uses 310-kVA at 0.6 pf lagging. A synchronous motor is added to the system to…
A: Hello. Since your question has multiple sub-parts, we will solve the first three sub-parts for you.…
Q: A 3-phase transmission line having a capacity of 10,000KVA serves as a balanced load that draws…
A:
Q: A 8 pole wave wound shunt generator delivers 205A at a terminal voltage of 200V. Ra and Rsh are…
A:
Q: The maximum diversified demand of a range of loads supplied by a power plant over one year is 24000…
A: The load diversity factor is given by the expression as shown below: Load diversity…
Q: A 25 kVA, 240 V single phase source supply the rated power at the rated voltage to a motor at 0.8…
A: As we have given : S=25 kVAV=240 Vcosϕ1=0.8cosϕ2=0.9
Q: An electrical system has a load of 5,000 kw at a lagging power factor of 0.67. If a 3,000-kva…
A:
Q: Q5) Two 300KVA, 1000V, 50Hz alternators operating in parallel to supply a load of 500KW at UPF. 60%…
A: Generator: Any machine that transforms mechanical energy to electricity for transmission and…
Q: 2. An industrial plant consisting primarily of induction motor loads absorbs 1200KVA at 0.85 power…
A: This question belongs to power system . It is based on the concept of calculation of required shunt…
Q: A load of 500 kVA operates on 1100 V, 50 Hz mains with power factor of 0.6 lagging. It is required…
A: We have an load with, KVA rating = 500 KVA Vs = 1100 V Frequency (f) = 50 Hz Power factor (cosϕ1) =…
Q: Problem #15: A manufacturing plant has a load of 3600 kVA at a lagging pf of 0.707. A 500-hp…
A: The solution is given below
Q: 1. A 3phase induction motor load draws a power of 13.33 KVA at 0.75pf from 460V source. If a…
A:
Q: Q3: For the following figure, select the generator rating as base to find the voltage at the…
A:
Q: QI: A synchronous motor having a power consumption of 50 kW is connected in parallel with a load of…
A: In this question we have given parallel connected load and combined power factor....We have to find…
Q: An industrial plant draws 500 kW at 0.6 pf lagging from a 3-phase system. In order to raise the…
A:
Q: A generator is supplying a load of 700 kW at a power factor of 0.9 lagging. If the power factor is…
A: We have been given a generator which is supplying a load of 700 KW with, Cosϕ = 0.9 Lagging and we…
Q: A generating station distributes the following loads. 2500KW, 7500KW, 15000KW and 3500KW, The…
A:
Q: An industrial plant consists of several induction motors. The plant absorbs 300 kW at 0.6 PF lagging…
A:
Q: Problem 4 An electric saw, a wood shaper, and a motor load of a workshop establish a 18 kVA power…
A:
Q: A lightning surge with a peak value of 3600kV strikes a transmission line at point A. Find the…
A: From the transient wave analysis
Q: A three-phase synchronous Y-mounted alternator with constant excitation, driven by a turbine. This…
A:
Q: At an industrial sub – station with a 6 MW load, a capacitor of 2 MVAR is installed to maintain the…
A:
Q: 2. A 400-V, 3-phase induction motor load takes 900 kVA at a power factor of 0.707. Calculate the kVA…
A: Case I S= 900 KVA PF1= 0.707 PF1 = cos ϕ1 = 0.707 Φ1= 45° Real power P1 = S * PF1 = 900k * 0.707 =…
Q: An industrial plant uses two 3-phase induction motors rated at 460 V. At full load one draws 232 A…
A: The solution is given below
Q: A remote property has an ac load profile that can be approximated by the following graph: Load…
A: The load curve of the remote property Z as shown in the question. In the load 1 row represent the…
Q: The 3-phase average power rating of the CPU on a mainframe computer is 22,659 W. The 3- phase line…
A: Determining the value of, We have, Therefore, the value of is 31.544.
Q: I need the answer as soon as possible
A:
Q: If the power received at the MU is lognormal with standard deviation of 9dB, the outage probability…
A: According to the question we have to find the value of outage probability and value of x.
Q: The load in a factory is 300 kW at 0.8 lagging power factor. It is required to improve the overall…
A:
Q: Two buses are interconnected by a transmission line of impedance (0.03 + j0.012) pu. The voltage on…
A: we need to determine the voltage on the second bus, real and reactive power on the first bus.
please answer in full solution
Step by step
Solved in 2 steps with 2 images
- Problem 2. (A 350KW of an industrial load has a power factor of 0.5 lagging. A group of synchronous motors operating at a power factor of 84% leading is installed and the power factor improves to 70% lagging. Determine the total KVA rating of the synchronous motors installed.It is desired to purchase a synchronous condenser to correct the 2,400-KVA 0.67-lagging power factor load in an industrial plant to 0.95 lagging. Neglect losses, calculate: (a) the kilovolt-ampere input rating of the required synchronous condenser; (b) the total kilovoltamperes of the plant. Using the phasor diagram.2) The net inlet to a factory powered by a 2300 volt infinite busis measured as 765 A, for a lag 0.92 power factor. although mostloads is inductive, the input power factor has been improved by installing asynchronous capacitor operating at its nominal value of 1000 KVA. Determine the factor oforiginal factory power.
- Two buses are interconnected by a transmission line of impedance (0.03 + j0.012) pu. The voltage on one bus is 1/0°, and the load on the other bus is (1 + j0.4) pu. Determine the voltage on the second bus. Also calculate the real and reactive power on the first bus.S.2) The serial impedance of the 300 km power transmission line is 23 + j75 ohm / phase and the shunt acceptance is j500 microS / phase. A power of 50 MW with a power factor of 0.88 under 220 kV interphase voltage from the end of the power transmission line being shot. Using these data of the energy transmission line, a) Characteristic impedance of the energy transmission line, b) Natural apparent power of the energy transmission line according to the 220 kV interphase operating voltage, c) The values of the line parameters A, B, C and D of the transmission line using hyperbolic functions, d) Calculate the maximum power that the power transmission line can transmit.An industrial load of200KW has a powerfactor of 0.5 lagging. Agroup of synchronousmotors operating at apower factor of 0.8leading is installed andthe over-all power factorimproves to 0.75 lagging.Determine the KVArating of the synchronousmotors installed.Answer = 130.2354 KVA
- A three-phase synchronous generator has a synchronous reactance of 50 Ω/phase. It is connected to an infinite bus of line voltage 15,000 V , and it develops a total power of 5 MVA supplying with unity pf. If the armature voltage of the generator is increased by 15%, while the input power to the generator remains constant, determine the new power factor and the apparent power supplied to the grid.it supplies to the network.Electromechanical energy conversion (One AC induction motor and one AC synchronous motor were operated connected to an infinite bus of 600V. Power factor of the induction motor is 0,7 (lagging) and consumes 400 W from the bus. Synchronous motor consumes 300 W from the bus. If the power factor of the synchronous motor is 0,9 (lagging) find the line current from the bus, for the total of two motors (IL total 1) of the line that connects the motors with the bus and find the total appearent power (SL total 1) of the motors consumed from the bus. When the induction motor has the same conditions, if the power factor of the synchronous motor is 0,9 (leading) find the line current from the bus, for the total of two motors (IL total 2) of the line that connects the motors with the bus and find the total appearent power (SL total 2) of the motors consumed from the bus.A three phase, 60 Hz transmission line delivers 20 MW to a load at 66 kV at 80% pf lagging. The total series impedance of each line is 15 + j75 ohms. If a nominal pi circuit is used, what would be the transmission efficiency if the admittance is j0.0006 mhos?
- A 100KVA, 220V, a star-connected alternator is loaded at full load and at 60% pf lagging.The effective AC resistance per phase is 0.01411Ω. If the synchronous reactance is 4.5times the effect of the armature leakage reactance wherein the later is 0.046 Ω perphase, find(a) the phase voltage that would be generated at the load if the circuit were operating normally(b) What no-load open-circuit phase voltage must be present in order to circulate full-load current in short-circuit state while maintaining the same speed and field current?(c) What is the terminal phase voltage of the alternator when it is under a shorted load condition? Give an explanation in support of your response using just one sentence. The IA phasor should be used as the reference one.In 132 kV transmission system, the phase to ground capacitance is 0.01micro F. The inductance being 4 H. Calculate the voltage appearing across the pole of a circuit breaker if a magnetizing current of 9 A is interrupted. Find the value of resistance to be used across contact space to eliminate the striking voltage transient.A three-phase, 17.32kVA, 400V star star connected alternator is delivering rated load at 400V and power factor of 0.8 lagging. Its synchronous impedance is 0.2 + j2 ohms per phase. Find the load angle at which it is opening.