A 600V supply is coupled to a three-phase induction motor with a nominal rating of 100 horsepower (75 KW) and a synchronous speed of 1800 r/min. The ammeter revealed a line current of 78A, and the two-wattmeter approach showed a total power usage of 70kW. The rotor speed is 1763 revolutions per minute, according to accurate measurements. If the iron losses are 2 kW, and the windage and friction losses are 1.2 KW, (the resistance between the two terminals of the stator is 0.342

Electric Motor Control
10th Edition
ISBN:9781133702818
Author:Herman
Publisher:Herman
Chapter39: Synchronous Motor Operation
Section: Chapter Questions
Problem 14SQ: Induction motors and welding transformers require magnetizing current, which causes a. lagging power...
icon
Related questions
Question

A 600V supply is coupled to a three-phase induction motor with a nominal rating of 100 horsepower (75 KW) and a synchronous speed of 1800 r/min. The ammeter revealed a line current of 78A, and the two-wattmeter approach showed a total power usage of 70kW. The rotor speed is 1763 revolutions per minute, according to accurate measurements. If the iron losses are 2 kW, and the windage and friction losses are 1.2 KW, (the resistance between the two terminals of the stator is 0.342) calculate:
1. The power supplied to the rotor.

2. Rotor cu losses.

3. Torque generated at 1763 revolutions per minute .

4. Efficiency.

Expert Solution
steps

Step by step

Solved in 2 steps

Blurred answer
Knowledge Booster
Three phase Induction Motor
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Electric Motor Control
Electric Motor Control
Electrical Engineering
ISBN:
9781133702818
Author:
Herman
Publisher:
CENGAGE L