A 75 kVA, 13.2 kV/240 V delta-wye distribution transformer has a resistance of 1% pu and reactance of 8% pu. What is the transformer s phase impedance referred to the high voltage side? "     A. 69.70 + j557.57 ohms     B. 67.95 + j543.63 ohms     C. 71.09 + j558.72 ohms     D. 70.58 + j564.54 ohms

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.6MCQ: Consider Figure 3.4. For an ideal phase-shifting transformer, the imda nce is unchanged when it is...
icon
Related questions
Question
A 75 kVA, 13.2 kV/240 V delta-wye distribution transformer has a resistance of 1% pu and reactance of 8% pu. What is the transformer s phase impedance referred to the high voltage side? "
   
A. 69.70 + j557.57 ohms
   
B. 67.95 + j543.63 ohms
   
C. 71.09 + j558.72 ohms
   
D. 70.58 + j564.54 ohms
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps

Blurred answer
Knowledge Booster
Three Phase Transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
Electricity for Refrigeration, Heating, and Air C…
Electricity for Refrigeration, Heating, and Air C…
Mechanical Engineering
ISBN:
9781337399128
Author:
Russell E. Smith
Publisher:
Cengage Learning