A 90-MVA 69.3-KV, three-phase synchronous generator has a synchronous reactance of 11 Ohms/phase and negligible armature resistance. The generator is delivering power to the bus bar at the rated voltage with its field current adjusted for a generated emf (excitation voltage) of 45 kv per phase and a power angle 8 = 13 degree. Thus, the delivered power is the generator armature current is and the power factor is 110.458 MW 36.819 MW 491.031 MW None of these 191.319 MW

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter11: Transient Stability
Section: Chapter Questions
Problem 11.3P
icon
Related questions
Question
A 90-MVA 69.3-KV, three-phase synchronous generator has a synchronous reactance of 11 Ohms/phase and negligible armature resistance. The generator is delivering power to the
bus bar at the rated voltage with its field current adjusted for a generated emf (excitation voltage) of 45 kv per phase and a power angle 8 = 13 degree.
Thus, the delivered power is
the generator armature current is
and the power factor is
110.458 MW
36.819 MW
491 031 MW
None of these
191.319 MW
Transcribed Image Text:A 90-MVA 69.3-KV, three-phase synchronous generator has a synchronous reactance of 11 Ohms/phase and negligible armature resistance. The generator is delivering power to the bus bar at the rated voltage with its field current adjusted for a generated emf (excitation voltage) of 45 kv per phase and a power angle 8 = 13 degree. Thus, the delivered power is the generator armature current is and the power factor is 110.458 MW 36.819 MW 491 031 MW None of these 191.319 MW
EHide b
NG360 Midterm
A 90-MVA 69.3-kv, three-phase synchronous generator has a synchronous reactance of 11 Ohms/phase and negligible armature resistance. The generator is delivering power to the
bus bar at the rated voltage with its field current adjusted for a generated emf (excitation voltage) of 45 kV per phase and a power angle 8 = 13 degree.
Thus, the delivered power is
the generator armature current is
and the power factor is
0.984 < 68.3 (KA)
0.984 <-20.757° (KA)
2.49- 68.3" (KA)
2.49 <-20.757 (KA)
None of these
Transcribed Image Text:EHide b NG360 Midterm A 90-MVA 69.3-kv, three-phase synchronous generator has a synchronous reactance of 11 Ohms/phase and negligible armature resistance. The generator is delivering power to the bus bar at the rated voltage with its field current adjusted for a generated emf (excitation voltage) of 45 kV per phase and a power angle 8 = 13 degree. Thus, the delivered power is the generator armature current is and the power factor is 0.984 < 68.3 (KA) 0.984 <-20.757° (KA) 2.49- 68.3" (KA) 2.49 <-20.757 (KA) None of these
Expert Solution
steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Knowledge Booster
Stability Analysis in Power System
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning