A factory has an electrical load of 1600 kW at a lagging power factor of 0.8 and fed from a line having an impedance of 0.05+j0.4 N. The voltage at the factory is maintained at 2350 V (rms). An additional variable power factor load is to be added to the factory. The new load will add 320 kW to the real power load of the factory. The power factor of the added load is to be adjusted so that the overall power factor of the factory is 0.96 lagging.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter2: Fundamentals
Section: Chapter Questions
Problem 2.30MCQ: Under balanced operating conditions, consider the three-phase complex power delivered by the...
icon
Related questions
Question
100%

Answer both options for thumbs up

A factory has an electrical load of 1600 kW at a
lagging power factor of 0.8 and fed from a line having
an impedance of 0.05+j0.4 N. The voltage at the
factory is maintained at 2350 V (rms). An additional
variable power factor load is to be added to the
factory. The new load will add 320 kW to the real
power load of the factory. The power factor of the
added load is to be adjusted so that the overall power
factor of the factory is 0.96 lagging.
A. Find the average power loss in the line before and after the load is added.
Express your answers in kilowatts to three significant figures separated by a comma.
Pbefore, Pafter =
B. Find the rms magnitude of the voltage at the sending end of the line before and after the load is added.
Express your answers in volts to three significant figures separated by a comma.
|Vs rms before|, |Vs rms after|
Transcribed Image Text:A factory has an electrical load of 1600 kW at a lagging power factor of 0.8 and fed from a line having an impedance of 0.05+j0.4 N. The voltage at the factory is maintained at 2350 V (rms). An additional variable power factor load is to be added to the factory. The new load will add 320 kW to the real power load of the factory. The power factor of the added load is to be adjusted so that the overall power factor of the factory is 0.96 lagging. A. Find the average power loss in the line before and after the load is added. Express your answers in kilowatts to three significant figures separated by a comma. Pbefore, Pafter = B. Find the rms magnitude of the voltage at the sending end of the line before and after the load is added. Express your answers in volts to three significant figures separated by a comma. |Vs rms before|, |Vs rms after|
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 4 steps

Blurred answer
Knowledge Booster
Analog to digital converters
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning