A local ventilation system (a hood and duct system) is used to remove air and contaminants from a pharmaceutical lab (Fig. 1). The inner diameter (ID) of the duct is 129 mm, its average roughness is 0.15 mm, and its total length is L = 24.5 m. There are three elbows along the duct, each with a minor loss coefficient of 0.21. Literature from the hood manufacturer lists the hood entry loss coefficient as 3.3 based on duct velocity. When the damper is fully open, its loss coefficient is 1.8. The minor loss coefficient through the 90° tee is 0.36. Finally, a one-way valve is installed to prevent contaminants from a second hood from flowing “backward” into the room. The minor loss coefficient of the (open) one-way valve is 6.6. The performance data of the fan fit a parabolic curve of the form Havailable = H0 - aV2, where shutoff head H0 = 60.0 mm of water column, coefficient a = 2.50 x 10-7 mm of water column per (Lpm)2 ,available head Havailable is in units of mm of water column, and capacity ?̇ is in units of Lpm of air. Estimate the volume flow rate in Lpm through this ventilation system.

Refrigeration and Air Conditioning Technology (MindTap Course List)
8th Edition
ISBN:9781305578296
Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Chapter8: Leak Detection, System Evacuation, And System Cleanup
Section: Chapter Questions
Problem 2RQ: Name and briefly describe the six classes of leaks.
icon
Related questions
Question
100%

A local ventilation system (a hood and duct system) is used to remove air and contaminants from a pharmaceutical lab (Fig. 1). The inner diameter (ID) of the duct is 129 mm, its average roughness is 0.15 mm, and its total length is L = 24.5 m. There are three elbows along the duct, each with a minor loss coefficient of 0.21. Literature from the hood manufacturer lists the hood entry loss coefficient as 3.3 based on duct velocity. When the damper is fully open, its loss coefficient is 1.8. The minor loss coefficient through the 90° tee is 0.36. Finally, a one-way valve is installed to prevent contaminants from a second hood from flowing “backward” into the room. The minor loss coefficient of the (open) one-way valve is 6.6. The performance data of the fan fit a parabolic curve of the form Havailable = H0 - aV2, where shutoff head H0 = 60.0 mm of water column, coefficient a = 2.50 x 10-7 mm of water column per (Lpm)2 ,available head Havailable is in units of mm of water column, and capacity ?̇ is in units of Lpm of air. Estimate the volume flow rate in Lpm through this ventilation system.

One-way valve
90° Tee
·Branch from
another hood
Fan
Damper
T= 25°C
P = 1 atm
Hood
Figure 1.Schematic for Question
Transcribed Image Text:One-way valve 90° Tee ·Branch from another hood Fan Damper T= 25°C P = 1 atm Hood Figure 1.Schematic for Question
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 8 steps with 9 images

Blurred answer
Knowledge Booster
Applied Fluid Mechanics
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Refrigeration and Air Conditioning Technology (Mi…
Refrigeration and Air Conditioning Technology (Mi…
Mechanical Engineering
ISBN:
9781305578296
Author:
John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:
Cengage Learning