A resistor of 4 ohmsisconnected in parallel with an impedancecoil whose resistance and inductive reactance are 3 ohms and 9 ohms, respectively. Determine the total current, in amperes, taken from a supply voltage of 1 20-V RMS sinusoidal source.
Q: In the circuit shown in the figure, there is a load between the terminals a and b, consisting of the…
A:
Q: A residential four-wire system supplies power at220 V rms to the following single-phase…
A: (b) For first phase total load are – Since loads are bulb so that total power is real and reactive…
Q: Q 2) A 110-V RMS, 60HZ source is applied to a load impedance Z. The apparent power entering the load…
A:
Q: A single-phase circuit is placed across a 120-Vrms, 60-Hz source, with an ammeter, a voltmeter, and…
A: The current in the circuit is 12 A. The voltage across the circuit is 120 V. The active power read…
Q: 9. The two loads in the circuit depicted below absorb the following power. Load, absorbs S = 6+j10…
A:
Q: An industrial load is supplied through a transmission line that has a line impedance of 0.1 + j0.2…
A:
Q: For the circuit shown, what is the complex power, S, consumed by the load impedance? (Assume the…
A: The complex power is given by: S=VI*where,I* is conjugate of current I. Given: Vs=150∠0°R=15ΩC=150…
Q: 3 Two impedances z1 and z2 when connected separately across a 230V 50HZ supply consumed 100w and 60W…
A:
Q: 1. How much value of capacitance should you place to correct the power factor of a load consisting…
A:
Q: The rms value of a three-phase balanced ac voltage source is 173V. Such voltage source is used to…
A: Given RMS value of three phase balanced ac voltage =173V Assuming line to line voltage⇒…
Q: The rms value of a 60HZ single phase ac voltage source is 100V and its internal resistance is 0.1 Q.…
A: In the question, A voltage sources V= 100V & 60Hz is supplied to resistance R= 1ohm Inductance…
Q: 1. A 500-V rms, 60-Hz feeder line supplies an industrial plant consisting of a motor drawing 70 kW…
A: 500V rms, 60Hz feeder line Three type load consist, motor , Capacitor and lightening load.…
Q: The rms value of a 60HZ single phase ac voltage source is 100V and its internal resistance is 0.1 Q.…
A: b)xL=wL=2π×60×10-3 =0.3769ΩZ=0.1+1+j0.3769 =1.1+1+j0.3769…
Q: The phasor voltage Vab in the circuit shown is 24020 ° V (rms) when no external load is connected to…
A: Given Vab=240∠0° VZ=80-j60 Ω (a) When the no-external load is connected When no external load is…
Q: Two balanced loads are connected to a 240-kV rms 50-Hz line. Load 1 draws 30 kW at a power factor of…
A: Ans: a) Complex Power = 123.8 angle(43.86). Real power= 90 kw. Reactive Power = 85 kvar. b) Line…
Q: *P5.97. A balanced wye-connected three-phase source has line-to-neutral voltages of 440 V rms. Find…
A: In this question, A 3 phase star balanced sources is supplied to the 3 phase balanced star load.…
Q: If a current 5.0 A lags the applied voltage 230 V by an angle ϕ, it can be resolved into two…
A: Need to find reactance and current
Q: 2. For the circuit below with source voltage phasor given in Pms, a. Find phasors Is, 12, V1, and V2…
A: (a) For current in source side of the transformer circuit given is calculated as
Q: The load impedance in the circuit shown is shunted by a capacitor having a capacitive reac- tance of…
A: In Network Phasor load current and voltage Real and imaginary power across load , transmission…
Q: Q2: For the circuit shown below, determine the apparent power delivered by the source, power…
A:
Q: The maximum value of the alternating voltage and current are 400V and 20A respectively in a circuit…
A: Given:Vmax=Vm=400VImax=Im=20AAt:t=0, V=283V and 10Af=50 HzSo ω=2πfω=100πω=314
Q: Unless given, use the: POLAR FORM for voltage and current, RECTANGULAR FORM for impedance. Consider…
A:
Q: A single phase AC chopper supplies a pure inductive load of 0.02H from 220V, 50HZ AC supply. The…
A:
Q: The circuit shown in Figure Q5.1 consists of a current source connected to a load via a cable. The…
A: Current is given , On comparing with standard equation. Taking cos as reference current will be,
Q: The load impedance absorbs 2.5 kW and generates 5 kVAR. The sinusoidal voltage source develops 7.5…
A: Given The power absorbed by the load impedance PL=2.5 kW The reactive power generates by the load…
Q: The rms value of a single-phase ac voltage source is V. The voltage source will power two loads in…
A: a)Z,is associated with Resistor (R1) and inductor(L),both are in series Reactance of L, jxL=j 2πf…
Q: a. Vrms = 120445°,Z = 35 +30j Determine the Real Power, Reactive Power, Complex Power, Apparent…
A: This question belongs to basic electrical . It is about calculation of different types of power when…
Q: Exercise#4: A balanced wye-connected three-phase source has line-to-neutral voltages of 440 V rms.…
A:
Q: The instantaneous voltage across a circuit element is v(t) - 359.3 sin(wt + 15°) volts, and the…
A:
Q: Objective 1-Understand ac power concepts, their relationshi 10.4 The load impedance in the circuit…
A:
Q: Problem 1 Businessman Lance Smile own two large malls in Basilan Island. Both malls are connected in…
A: Given,Operating voltage,V=13.8kVrmsImpedance,Z=1+j2.5ΩFor mall 1,P1=400kWcosθ1=0.8 laggingFor mall…
Q: , reactive and apparent power consumed by the lo
A: The given load is an RL load that means the power factor of the load is lagging in nature means the…
Q: An investor own two large stores at Dubai. Both malls are connected in parallel and operating at an…
A: Given: An investor owns two large stores in Dubai. Both malls are connected in parallel and operate…
Q: A balanced wye-connected three-phase source has line-to-neutral voltages of 440 V rms. Find the rms…
A: Given data, The value of line-to-neutral rms voltage is VPrms = 440 V. The value of resistance is R…
Q: An inductive reactance of 10 ohms is connected in parallel with the capacitive reactance of 30 ohms.…
A: The impedances offered by a resistor, capacitor, and inductor are R, jXL and -jXC. Where, XL and XC…
Q: In the case of reactive power compensation in a low voltage distribution network and increasing the…
A: In compensation of reactive power of a network, the active power consumed by network always remains.…
Q: for the circuit shown in the figure below, find I, Vr and Vc, and the corresponding sinusoidal…
A: In this question we need to find a VR , Vc , I and average power.
Q: a) A source voltage of 230V rms at 50HZ is applied to a circuit having an impedance of (10+j12)…
A:
Q: 3 Two impedances z1 and z2 when connected separately across a 230V 50Hz supply consumed 100W and 60W…
A: In this question, We need to determine the total power if both impedance are connected in the…
Q: Unless given, use the: POLAR FORM for voltage and current, RECTANGULAR FORM for impedance. Consider…
A:
Q: A residential electric power monitoring system ratedfor 120-V rms, 60-Hz source registers…
A: a) The RMS current. The average power is given by the expression as shown below: Plugging the…
Q: An industrial process requires a power of 10 kW with a lagging power factor of 0.6 in a single-phase…
A:
Q: Calculate the active power, reactive power, power factor, Reactive factor if: v=100 cos (wt+150)…
A: In this question we need to find a active power, reactive power, power factor, Reactive factor
Q: When connected to 230 V (rms) ,50 Hz power line, a load absorbs 4 kW at a lagging power factor of…
A:
Q: If using the relative maximum power equation RL = V RTH² + (X ± XTh)² If the reactance of the…
A: According to the question suppose load reactance and and thevenin reactance is of inductive type…
Q: Given a sinusoidal voltage source in series with R,L, and C. The sinusoidal frequency is 600 Hz. R=2…
A: Since you have asked multiple questions, we will solve the first question for you. If you want any…
Q: A load Z draws 12 kVA at a power factor of 0.856 lagging from a 120-V rms sinusoidal source.…
A:
Q: 3. An industrial load is supplied through a transmission line that has a line impedance of 0.5 +…
A: The electrical devise which is store a electrical energy in electric field called as a Capacitor.…
Q: Q23. The contract load of a dairy plant at 11 kV, 60 Hz is 800 kW, but the peak demand of plant…
A: "Since you have asked multiple question , we will solve the first question for you. If you want any…
Step by step
Solved in 5 steps with 1 images
- Let a 100V sinusoidal source be connected to a series combination of a 3 resistor, an 8 inductor, and a 4 capacitor. (a) Draw the circuit diagram. (b) Compute the series impedance. (C) Determine the current I delivered by the source. Is the current lagging or leading the source voltage? What is the power factor of this circuit?The real power delivered by a source to two impedances, Z1=4+j5 and Z2=10 connected in parallel, is 1000 W. Determine (a) the real power absorbed by each of the impedances and (b) the source current.Consider a load impedance of Z=jwL connected to a voltage and V let the current drawn be I. (a) Develop an expression for the reactive power Q in terms of ,L, and I, from complex power considerations. (b) Let the instantaneous current be i(t)=2Icos(t+). Obtain an expression for the instantaneous power p(t) into L, and then express it in terms of Q. (c) Comment on the average real power P supplied to the inductor and the instantaneous power supplied.
- The instantaneous voltage across a circuit element is v(t)=400sin(t+30)volts, and the instantaneous current entering the positive terminal of the circuit element is i(t)=100cos(t+10)A. For both the current and voltage, determine (a) the maximum value, (b) the rms value, and (C) the phasor expression, using cos(t) as the reference.A balanced wye-connected three-phase source has line-to-neutral voltages of 240 V rms. Find the rms line-to-line voltage. This source is applied to a delta-connected load, each arm of which consists of a 10-Ω resistance in parallel with a +j5-Ω reactance. Determine the rms line current magnitude, the power factor, and the total power delivered.If a current 5.0 A lags the applied voltage 230 V by an angle ϕ, it can be resolved into two components, OA in phase with the voltage and OB lagging by 90°. If the phasor diagram in to a circuit possessing resistance and inductance in series, OA and OB must not be labelled and respectively. It has become the practice to say that the power factor is laggingwhen the current lags the supply voltage, and leading when the current leads the supply voltage. This means that the supply voltage is regarded as the reference quantity. (a) A 30 μ F capacitor is connected across the applied voltage, 50 Hz supply. Calculate the reactance of 30 μ F capacitor connected across applied voltage (b) the reactance of the capacitor; (c) the current.
- For the circuit shown in Figure,a. Find the Thévenin equivalent circuit for the source.b. Find the power dissipated by the load resistor. c. What value of load impedance would permitmaximum power transfer?The voltage source is sinusoidal with frequency60 Hz, and its polarity is such that the current fromthe voltage source flows into the 10-Ω resistor.Find the total impedance, voltage drop on the 100-ohm resistor, draw the phasor diagram of the voltage and current at R1, total power (apparent) delivered by the current source, draw the phasor diagram of the voltage and current at the source. Also, is the circuit inductive, capacitive, or neither (resistive)? please give the step-by-step solution NOTE: Polar form for Voltage & Current. Rectangular form for ImpedanceA balanced wye-connected three-phase source has line-to-neutral voltages of 440 V rms. Find the rms line-to-line voltage magnitude. If this source is applied to a wye-connected load composed of three 30-Ω resistances, find the rms line-current magnitude and the total power delivered.
- An industrial installation has a power factor of 0.85 in backward. The demand is 150 KVA, and the operating voltage is 4800 V at 60 Hz. What should be done to bring the power factor to 0.95 in lagging? Indicate what you would connect and with what three-phase power. If the connection of the element to be added is in delta, indicate its reactance and the value of its capacitance or inductance. capacitance or inductance.A current of 10 A rms flows when a single-phasecircuit is placed across a 220-V rms source. Thecurrent lags the voltage by 60◦. Find the powerdissipated by the circuit and the power factor.. Determine the capacitance value that, when placed in parallel with this load, would produce a unity power factor. Assume that the source is 230 V at 60 Hz. The Q shown is a positive Inductive reactive power, which would have to be “offset” by the same value of Reactive Capacitance Power.