A three phase 60 Hz transmission line delivers 750 KW at 95% leading power factor and at delta voltage of 6,900 volts. The resistance per conductor is 4.3 ohms and the reactance per conductor is 2.6 ohms. Assuming both source and load are wye connected, what is the load impedance per phase? A. 69 ohms B. 64.5 ohms C. 72.2 ohms D. 60.27 ohms

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter2: Fundamentals
Section: Chapter Questions
Problem 2.26P: A small manufacturing plant is located 2 km down a transmission line, which has a series reactance...
icon
Related questions
icon
Concept explainers
Question

A three phase 60 Hz transmission line delivers 750 KW at 95% leading power factor and at delta voltage of 6,900 volts. The resistance per conductor is 4.3 ohms and the reactance per conductor is 2.6 ohms. Assuming both source and load are wye connected, what is the load impedance per phase?

A. 69 ohms

B. 64.5 ohms

C. 72.2 ohms

D. 60.27 ohms

Expert Solution
steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
Transmission line parameter
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning