A three phase distribution board of installed power 50KVA is supplied at 220/380V with a demand factor of 70%. Calculate the current IB and the minimum appropriate circuit breaker (CB). Select one: IB=53.2A, CB = 80A IB=76A, CB = 100A IB-53.2A. CB = 63A IB-48.2A. CB = 63A