A three-phase Y-connected alternator delivers a unity power-factor load at 230 volts. If the synchronous-reactance voltage drop is 60 volts per phase, calculate the per cent regulation, neglecting the resistance voltage drop. Ans.: 9.77%

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.56P: Three single-phase two-winding transformers, each rated 3kVA,220/110volts,60Hz, with a 0.10 per-unit...
icon
Related questions
Question

A three-phase Y-connected alternator delivers a unity power-factor load at
230 volts. If the synchronous-reactance voltage drop is 60 volts per phase,
calculate the per cent regulation, neglecting the resistance voltage drop.
Ans.: 9.77%