An assembly hall was to have an air conditioning unit installed which would be maintained at 24°C dry bulb and at 50% Relative humidity. The unit delivers air at 14°C dry bulb and the calculated sensible heat load is 140 kW and the latent heat load is 50 kW. Twenty five percent by weight of extracted air is made up of outside air at 32°C dry bulb and 18°C welt bulb temperatures while 75% is extracted by the air conditioner from the assembly hall. The atmospheric pressure is 100 kPa and Rair is 287.08 j/kg-k. Using Psychrometric chart determine; a. The mass of circulating air b. The amount of moisture pick-up in the space c. The capacity of the supply fan d. The air conditioning refrigeration capacity in TOR e. The dry bulb temperature entering the air condition

Elements Of Electromagnetics
7th Edition
ISBN:9780190698614
Author:Sadiku, Matthew N. O.
Publisher:Sadiku, Matthew N. O.
ChapterMA: Math Assessment
Section: Chapter Questions
Problem 1.1MA
icon
Related questions
Question
An assembly hall was to have an air conditioning unit installed which would be
maintained at 24°C dry bulb and at 50% Relative humidity. The unit delivers air at
14°C dry bulb and the calculated sensible heat load is 140 kW and the latent heat
load is 50 kW. Twenty five percent by weight of extracted air is made up of outside
air at 32°C dry bulb and 18°C welt bulb temperatures while 75% is extracted by the
air conditioner from the assembly hall. The atmospheric pressure is 100 kPa and
Rair is 287.08 j/kg-k. Using Psychrometric chart determine;
a. The mass of circulating air
b. The amount of moisture pick-up in the space
c. The capacity of the supply fan
d. The air conditioning refrigeration capacity in TOR
e. The dry bulb temperature entering the air condition
Transcribed Image Text:An assembly hall was to have an air conditioning unit installed which would be maintained at 24°C dry bulb and at 50% Relative humidity. The unit delivers air at 14°C dry bulb and the calculated sensible heat load is 140 kW and the latent heat load is 50 kW. Twenty five percent by weight of extracted air is made up of outside air at 32°C dry bulb and 18°C welt bulb temperatures while 75% is extracted by the air conditioner from the assembly hall. The atmospheric pressure is 100 kPa and Rair is 287.08 j/kg-k. Using Psychrometric chart determine; a. The mass of circulating air b. The amount of moisture pick-up in the space c. The capacity of the supply fan d. The air conditioning refrigeration capacity in TOR e. The dry bulb temperature entering the air condition
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 3 steps with 2 images

Blurred answer
Recommended textbooks for you
Elements Of Electromagnetics
Elements Of Electromagnetics
Mechanical Engineering
ISBN:
9780190698614
Author:
Sadiku, Matthew N. O.
Publisher:
Oxford University Press
Mechanics of Materials (10th Edition)
Mechanics of Materials (10th Edition)
Mechanical Engineering
ISBN:
9780134319650
Author:
Russell C. Hibbeler
Publisher:
PEARSON
Thermodynamics: An Engineering Approach
Thermodynamics: An Engineering Approach
Mechanical Engineering
ISBN:
9781259822674
Author:
Yunus A. Cengel Dr., Michael A. Boles
Publisher:
McGraw-Hill Education
Control Systems Engineering
Control Systems Engineering
Mechanical Engineering
ISBN:
9781118170519
Author:
Norman S. Nise
Publisher:
WILEY
Mechanics of Materials (MindTap Course List)
Mechanics of Materials (MindTap Course List)
Mechanical Engineering
ISBN:
9781337093347
Author:
Barry J. Goodno, James M. Gere
Publisher:
Cengage Learning
Engineering Mechanics: Statics
Engineering Mechanics: Statics
Mechanical Engineering
ISBN:
9781118807330
Author:
James L. Meriam, L. G. Kraige, J. N. Bolton
Publisher:
WILEY