An overhead 3-phase transmission line delivers 5000 kW when a current of 150 A is flowing through the transmission line. If the impedance of the transmission line is 9 Ohm and reactance is 6 Ohm. Determine: (i) Resistance of the transmission line (ii) Three-phase power loss (iii) Percentage Efficiency
Q: A single phase transmission line is delivering 410 kVA load at 10 kV. Its resistance is 5.5 ohm and…
A: Given: A single phase transmission line is delivering 410 kVA load at 10 kV. Its resistance is 5.5…
Q: A single phase wattmeter is used to determine the power taken by a three phase squirrel cage…
A: In this question, We need to determine the line current drawn by the motor. If Line to line voltage…
Q: A single-phase 480020° V bus is connected to a single-phase 100kW motor operating at a lagging power…
A: First calculate active, reactive powers of the each load and than find total complex power of the…
Q: Q2/ A single phase overhead transmission line delivers 1100 kW at 33 kV at 0•8 p.f. lagging. The…
A:
Q: A single phase transmission line is delivering 430 kVA load at 10kV. Its resistance is 6 Q and…
A:
Q: A single phase transmission line is delivering 410 kVA load at 11 kV. Its resistance is 7 Q and…
A:
Q: A single phase transmission line is delivering 450 kVA load at 13 kV. Its resistance is 6.5 N and…
A: Single phase transmission line Power deliver P=450KVA, power factor = 0.9 load voltage V=13KV…
Q: A load of 120 MW at a power factor of 0.75 lagging can be delivered by a 3-phase transmission line.…
A: single phase power =three phase power3. power in 3 phase power =3×Line voltage×line current×power…
Q: A load of 120 MW at a power factor of 0.9 lagging can be delivered by a 3-phase transmission line.…
A:
Q: The following information is given in connection with a parallel connected load of three impedances:…
A:
Q: A load of 130 MW at a power factor of 0.9 lagging can be delivered by a 3-phase transmission line.…
A: Given P3ϕ=130 MWcosϕ=0.9 lagVr=33 KVLosses in the transmission line=7% of power delivered…
Q: Discuss why: (a) All ac transmission and distribution system are 3 phase system. (b) The…
A: a) All ac transmission and distribution system are 3 phase system because in 3 phase system…
Q: A load of 145 MW at a power factor of 0.6 lagging can be delivered by a 3-phase transmission line.…
A: Per phase power = total power /3. Per voltage = line voltage/sqrt(3). Power delivered =…
Q: A load of 130 MW at a power factor of 0.9 lagging can be delivered by a 3-phase transmission line.…
A:
Q: Transmission and Distribution of Electric Power Answer the Following Question Please: Q)…
A:
Q: A load of 125 MW at a power factor of 0.8 lagging can be delivered by a 3-phase transmission line.…
A: A 3 phase -Load 125MW, power factor 0.8 logging, Receiving end voltage VR = 36kV. Loss in…
Q: A 3-phase, 60 Hz, 35 km long overhead line supplies 575 kW at 22 kV, 0.8 p.f. lagging. The line…
A: inductive reactance=2×π×f×L. current flowing in line=power delivered3× voltage× power factor…
Q: A certain generating plant in manila has 40kV, three phase transmission line to supply a 12MVA load…
A:
Q: A load of 120 MW at a power factor of 0.65 lagging can be delivered by a 3-phase transmission line.…
A:
Q: A 3-phase, 60 Hz, 25 km long overhead line supplies 425 kW at 22 kV, 0.6 p.f. lagging. The line…
A: inductive reactance =2×π×f×L. current=power3×voltage×power factor. sending end voltage=receiving end…
Q: A short 3, 3 wire transmission line has an impedance per wire of 15+j20 Ω. The sending end line to…
A: In this question we need to find a load voltage and load power factor for the given transmission…
Q: A 275 kV, 50 Hz, 65 km transmission line has a series impedance of 0.12 + j0.5 O/km. By neglecting…
A: EFFICIENCY: Efficiency of transmission line is defined as the ratio of receiving end power to…
Q: A single phase transmission line is delivering 440 kVA load at 11 kV. Its resistance is 50 and…
A: Sending end voltage =receiving end voltage +drop in the line. Efficiency = output power/input power.…
Q: A load of 135 MW at a power factor of 0.65 lagging can be delivered by a 3-phase transmission line.…
A: Below are the answers calculated for the above given data
Q: A three phase 60 Hz transmission line delivers 750 KW at 95% leading power factor and at delta…
A:
Q: spectively per mile. Find the percent efficiency of the line.
A:
Q: A single phase transmission line is transmitting power to a load of 1,100 KW at 11 KV and at unity…
A: Given Single phase transmission lineLoad power PL=1100 kwvoltage VL=11 kvpower factor PF=1Total…
Q: Q4 Calculate the three-phase voltage drop if the ac resistance is 3 Q/2km and an ac reactance of…
A: In the Star Connection, the 3 winding's similar endpoints are connected to a common point known as…
Q: Q3: A three-phase transmission line delivers 15 MW at 132 kV with 0.8 power factor lagging. The loss…
A: Given that VL=132KVP=15MWcosϕ=0.8 (1) Formula of delivered active power from 3 phase transmission…
Q: A load of 145 MW at a power factor of 0.6 lagging can be delivered by a 3-phase transmission line.…
A: 1 phase power delivered=3 phase power delivered 3. per phase voltage=receiving end line voltage3.…
Q: A load of 120 MW at a power factor of 0.6 lagging can be delivered by a 3-phase transmission line.…
A: Note- as per bartleby policy we are only allowed to solve 1 ques per window. Please post the second…
Q: A load of 135 MW at a power factor of 0.65 lagging can be delivered by a 3-phase transmission line.…
A:
Q: A 3-phase, 60 Hz, 25 km long overhead line supplies 425 kW at 22 kV, 0.6 p.f. lagging. The line…
A: inductive reactance=2×π×f×inductance. current=power delivered3×voltage×power factor.…
Q: An overhead 3-phase transmission line delivers 6000 kW when a current of 180 A is flowing through…
A: Given, 3 phase overhead transmission line Power deliver= 6000 KW Current flowing in line, Il= 180 A…
Q: A three-phase transmission line delivers 15 MW at 132 kV with 0.8 power factor lagging. The loss in…
A:
Q: A load of 125 MW at a power factor of 0.9 lagging can be delivered by a 3-phase transmission line.…
A: Given a three phase transmission line with load 125 MW ,0.9 pf, 57 kv The loss in the transmission…
Q: A single phase transmission line is delivering 460 kVA load at 11 kV. Its resistance is 4.5 Q and…
A: Fig: Equivalent circuit diagram of given single-phase Tr-line (a) current flowing…
Q: A three-phase transmission line delivers 15 MW at 132 kV with 0.8 power factor lagging. The loss in…
A: In this question we need to find a line current and length of the transmission line.
Q: An overhead 3-phase transmission line delivers 6000 kW when a current of 180 A is flowing through…
A: The solution can be achieved as follows.
Q: A load of 145 MW at a power factor of 0.9 lagging can be delivered by a 3-phase transmission line.…
A: The performance of a power system depends mainly on the performance of transmission lines in the…
Q: A load of 130 MW at a power factor of 0.75 lagging can be delivered by a 3-phase transmission line.…
A: Sending end voltage =recieving end voltage +drop Losses =3×I2×Rph
Q: A load of 120 MW at a power factor of 0.8 lagging can be delivered by a 3-phase transmission line.…
A: per phase power =3 phase power 3Given 3 phase power = 120 MWso per phase power = 1203 = 40 MWPer…
Q: A three-phase transmission line receiving end voltage is rated at 22 kV. A load of 1250 KW is…
A: total reactance of line=per km reactance*length sending end voltage=receiving end voltage +drop in…
Q: A load of 145 MW at a power factor of 0.65 lagging can be delivered by a 3-phase transmission line.…
A: single phase power =3 phase power 3. phase voltage=line voltage3. per phase resistance=power loss…
Q: A three-phase transmission line and a telephone line are supported on the same towers a shown in the…
A: Given, frequency = f= 60 Hz Current per phase= I = 200 A Da1=Dc2=42+3.6-0.62 =…
Q: Q2: A low tension system is reduced to a single phase system and connected with a coil of 636.6mH…
A: Calculate the phase voltage of the supply,
Q: A single phase transmission line is delivering 450 kVA load at 12 kV. Its resistance is 4.5 Q and…
A:
Q: A load of 1000 KW is connected at the receiving end of a 3 phase transmission line 80 km long. The…
A: 1000KW load at Receiving end with 20kV voltage. Load power factor 0.65lagging Transmission line =…
Step by step
Solved in 2 steps with 1 images
- Let a series RLC network be connected to a source voltage V, drawing a current I. (a) In terms of the load impedance Z=ZZ, find expressions for P and Q, from complex power considerations. (b) Express p(t) in terms of P and Q, by choosing i(t)=2Icost. (c) For the case of Z=R+jL+1/jC, interpret the result of part (b) in terms of P,QL, and Qc. In particular, if 2LC=1, when the inductive and capacitive reactances cancel, comment on what happens.A balanced -connected impedance load with (12+j9) per phase is supplied by a balanced three-phase 60-Hz,208-V source, (a) Calculate the line current, the total real and reactive power absorbed by the load, the load power factor, and the apparent load power, (b) Sketch a phasor diagram showing the line currents, the line-to-line source voltages, and the -load currents. Use Vab as the reference.A three-phase line with an impedance of (0.2+j1.0)/ phase feeds three balanced three-phase loads connected in parallel. Load 1: Absorbs a total of 150 kW and 120 kvar. Load 2: Delta connected with an impedance of (150j48)/phase. Load 3: 120 kVA at 0.6 PF leading. If the line-to-neutral voltage at the load end of the line is 2000 v (rms), determine the magnitude of the line-to-line voltage at the source end of the line.
- A transmission line has an actual impedance of 18 ohms, compute for the per unit impedance of this line assume Vbase = 2400, Sbase = 100kVA power factor at unity p.f. round answer to 4 decimal places.A certain generating plant in manila has 40kV, three phase transmission line to supply a 12MVA load at 30kV and 0.8 power factor. Find the resistance and reactance of the line if the length of the transmission line is 4,000 meters and the efficiency is 88%.A 30 mile, 3-phase transmission line delivers 8,000 kW at 33 kV, p.f. 0.8 lagging. The resistance and reactance of single conductor are 0.6 ohm and 0.72 ohm respectively per mile. Find the percent efficiency of the line.
- 2. Solve the following problem: A THREE-PHASE PLANT CONSUMES 600 KVA, WITH A VOLTAGE OF 2400 VOLTS AND A POWER FACTOR OF 0.8 BEHIND. a) DETERMINE THE EQUIVALENT DELTA IMPEDANCE OF THE PLANT. b) IF THE PLANT WERE A STAR, CALCULATE THE RESISTANCE, REACTANCE AND THE CORRESPONDING PASSIVE ELEMENT.A 210V, 50 Hz, single phase radial distribution system, the resistance of the wire is 0.0008 ohm/m supply and return. Two loads are connected and it consumes 10 and 10 A respectively and are fed from the cable at distance of 15 and 15 respectively. Calculate the voltage available across load 1 and 2100 km of single-phase transmission line, 800 kVA power 8 kV, is carried with 0.9 reverse power factor. The resistance of one kilometer of the line is 42 mΩ, and the reactance of one kilometer of the line is 0.646 Ω. Find the voltage at the beginning of the line and the efficiency of the line accordingly.
- 470 kVA load at 12 kV. Its resistance is 7 Ω and inductive reactance is 7 Ω if the load power factor is 0.9 lagging. Determine the Current through the line , Sending end voltage , Sending end power factor , Regulation of transmission line , Efficiency of transmission line Note:please do not handwritingA short 3 phase transmission line, connected to a 33kV, 50 Hz generating station at the sending end is required to supply a load of 10Megawatts at 0.8 power factor lagging, 30kV at the receiving end. If the minimum transmission line efficiency is to be limited to 96%, estimate the per phase values of resistance and inductance of the line.a) High Voltages are preferred for Transmission of Electricity. Why? b) Why Generation Voltage Levels are low in the range of 11 kV/ 33 kV etc? c) Why ACSR Conductors are preferred over Copper Conductors? d) Overhead Transmission Lines are preferred for Transmission of Power for Long Distances, why? e) Alternating Current is preferred over Direct Current in Power System, Why? f) Write the Installed Generation Capacity of Sultanate of Oman with current energy share of Conventional and Non-Conventional Energy Sources. g) Why the Capacitance effect is neglected in Short Transmission Line. h) Distinguish between Lumped or Distributed elements in a Transmission Line.