Consider a simple power system: two generators (20MVA each at 13.2kV) running in parallel via a combined generator step-up transformer (rated at 30/33.3/36.7 MVA: ONAN/ONAF/ONAF cooling, 13.2 (Delta)/115 (Solidly Grounded Wye) kV). The sub-transmission line is 10.0mi long and rated at 115kV. Estimate (write the assumptions) the 3-phase bolted fault current at the end of the 115kV line

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter5: Transmission Lines: Steady-state Operation
Section: Chapter Questions
Problem 5.37P
icon
Related questions
icon
Concept explainers
Question

Consider a simple power system: two generators (20MVA each at 13.2kV) running in parallel via a combined generator step-up transformer (rated at 30/33.3/36.7 MVA: ONAN/ONAF/ONAF cooling, 13.2 (Delta)/115 (Solidly Grounded Wye) kV). The sub-transmission line is 10.0mi long and rated at 115kV. Estimate (write the assumptions) the 3-phase bolted fault current at the end of the 115kV line.

Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps

Blurred answer
Knowledge Booster
Transmission line parameter
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning