Hw2.1-3: Derive the following: ing. The shift angle of line voltages for delta/star transformer using drawing.
Q: 1. Consider a three-phase transformer with a rating of 700 MVA and a secondary voltage of 145 kv.…
A:
Q: 1- The transformer called step-up transformer, when the number of. greater than winding winding.
A: As per our policy i have attempted only one question Step-up transformer: Step up transformer is a…
Q: Q2/A/ What are the conditions for satisfying parallel operation of single phase transformer? Deduce…
A:
Q: electrical what is the disadvantages of potential transformer ?
A: Potential transformer : The definition of a potential transformer is a device used to transmit…
Q: Consider Figure 1 of the text. For an ideal phase-shifting transformer, the impedance is unchanged…
A: Referring to the given hints, the impedance of the secondary side seen from the primary side:
Q: True or False? There are fewer number of turns in Y-Y transformer required than in delta-delta…
A:
Q: Explain the open circuit test on single phase transformer.
A: Open circuit test :- It is carried out at rated frequency & rated voltage to determine the core…
Q: The full load voltage drop in a single phase transformer are 2% and 4% due respectively to…
A: Given values are - Voltage dropR%=2%%R=2%Voltage dropX%=4%%X=4%
Q: Q2. (a) Explain what is per unit system? What are the advantages of per-unit computations? Prove for…
A: Per unit system:-Per unit system is the value expressing system used in an electrical Power systems…
Q: Q3) What are the elements finding from no-load test of single phase transformer?
A: At no load test rated voltage is applied with secondary open circuited. At no load only magnetizing…
Q: "Under saturated core condition, transformer become a source of harmonics" True False
A: In this question , we will write about harmonics in transformer..
Q: 1. What is the difference between power transformer and distribution transformer in core losses and…
A: Power transformers are generally high voltage transformers which are used stepping up and down of…
Q: A 3-phase transformer bank will be created with three 600 VA, 120/240 v one-phase transformers.…
A: 3 single phase transformers are connected to form a 3-ph. transformer. Rating of single phase…
Q: A 40000-KVA, 25000-V/600-kV, single phase transformer has the following series impedances: Z1=…
A:
Q: Consider that three single-phase transformers are connected as Delta in the primary and Wye in the…
A:
Q: What conclusions you can come up with after implementing open circuit test on single phase…
A: Conclusions from open circuit test on single phase transformer
Q: Derive physically the reason of the phase shift in three phase transformer and show the phase shift…
A: The given problem can be laid down into parts. Firstly, the reason of the phase shift in the three…
Q: Q2: Draw the circuit diagram, write down the governing equations, and draw the phasor diagram with…
A: Equivalent circuit diagram. Let the turn ratio is a,
Q: Why do we represent leakage flux in a transformer by inductive reactance? 2. What will happen if…
A: In the transformer, the magnetic flux is produced by both the primary and secondary winding…
Q: With the neat diagram explain the construction and working of Sumpner’s or Back –to-Back test of…
A: Step-1 Construction The Sumpner’s or back-to-back test of a single phase of a transformer…
Q: 1. Consider a three-phase transformer with a rating of 700 MVA and a secondary voltage of 145 kv.…
A:
Q: Questions:- 1. What happen when the two transformers are operated in parallel having un equal turn's…
A: According to the bartleby's guidelines we have to solve only one question posted by students so…
Q: The one line diagram of power system is shown in Figure Q.1. Use a common base MVA of 100 MVA and…
A:
Q: We wish to connect a 6 kVA, 120/240 V transformer as an autotransformer to a 120 V source to supply…
A: "Since you have posted a question with multiple sub parts we will solve first three subpart for you…
Q: what is the Formulae of short test of single phase transformer and Formulae to determine efficiency…
A: If, Wsc = Full load copper losses Isc = short circuit current Vsc = short circuit voltage Equivalent…
Q: 4. What do you mean by transformer connection Ydl and Dy11?
A:
Q: 1-which side is short cct.in short cct. test ? why? 2- Draw the exact equivalent circuit of the…
A: Answer(1) A short circuit test is conducted to find out variable losses in the transformer. So, to…
Q: . - what information could be obtained from open circuit test on single phase transformer? · what is…
A: Open circuit test is also known as No load test. It is perform by opening the primary of transformer…
Q: Discuss the potential transformer with neat schematic diagram.
A:
Q: In the transmission system shown in the figure above, the rated kVA of transformer 1, T1, is 1000…
A:
Q: A 200 – MVA, 15/200 kV single-phase power transformer has a per – unit resistance of 1.2 percent and…
A:
Q: Determine: A2rdg, A3rdg, IL(ave), PL(ave), & turn ratio of transformer
A: For a given circuit, Vp(rms) =220 V f=50 Hz A1 =400 mA load resistance RL =120 Ω
Q: Q1: What is the influence of transformer connections in single-phase transformers connected for 3-…
A: According to the Bartleby guidelines “Since you have asked multiple question, we will solve the…
Q: Three Phase Transformer connections: Discuss Fully the various methods available for transforming…
A: The methods of transformation of a 3-phase voltage into higher or lower 3-phase voltages is done…
Q: Consider a 3-phase transmission line operating at 66 KV and connected through a 1000 KVA transformer…
A:
Q: The figure below shows the equivalent circuit of a nominal 240V-120V, 1000 VA, single-phase…
A:
Q: at happens if one phase of a 3-phase transformer fails?
A: Primary delta connected and secondary star connected: If the primary (delta) side loses one phase of…
Q: Explain the difference between transformer equivalent circuit and IM equivalent circuit.
A: Equivalent circuit- An equivalent circuit is a simplified circuit (or model) that is easier to…
Q: Justify if in a Yy transformer (without neutral wire on the supply side) there are homopolar…
A: Here it is mentioned that in a three Yy transformer there are homopolar components of fluxes,…
Q: a) Discuss two (2) advantages and disadvantages of using three single-phase transformers instead of…
A: NOTE: Since you have asked multiple questions, we will solve the first question for you. If you want…
Q: Let a 5-kVA, 400/200-V transformer be approximately represented by a 2-2 reactance referred to the…
A: Equivalent model oftransformer- Since no load current is very small 2 to 5% of full load current. No…
Q: During the load test of single-phase transformer, when the secondary terminal voltage increases, the…
A:
Q: A single-phase transformer, working at unity power factor has an efficiency of 90 % at both…
A:
Q: Q2. (a) Explain what is per unit system? What are the advantages of per-unit computations? Prove for…
A: PU system: Per Unit system is a quantity expression system used in an electrical power system which…
Q: A 50-kVA 13.8-kV/208-V (rms, line-line) ∆ − Y three-phase distribution transformer has a per unit…
A: Given,High voltage side, line voltage(Base) =13.8 kVApparent power (S)(Base)=50 kVAa) As primary is…
Q: A 60-MVA, 280-kV/500-kV, single-phase transformer has the series impedance referred primary side is…
A: Base impedance=Vbase2MVAbase. per unit impedance=impedance in ohmsbase impedance.
Q: The per-unit system calculations method allows to: Select one: O a. improve the efficiency of the…
A: In the power systems analysis, Per Unit values are defined for per phase only not for 3 phase . A…
Q: Q2. (a) Explain what is per unit system? What are the advantages of per-unit computations? Prove for…
A:
Q: A 50-MVA, 190-kV/500-kV, single-phase transformer has the series impedance referred primary side is…
A: Given single phase transformer with50 MVA,190-kv/500-kvSeries impedance referred to primary side…
Derive the following
Step by step
Solved in 3 steps with 3 images
- Consider the single-line diagram of the power system shown in Figure 3.38. Equipment ratings are Generator 1: 1000MVA,18kV,X=0.2perunit Generator 2: 1000MVA,18kV,X=0.2p.u. Synchronous motor 3: 1500MVA,20kV,X=0.2p.u. Three-phase -Y transformers T1,T2,T3,T4,: 1000MVA,500kV,Y/20kV,X=0.1p.u. Three-phase YY transformer T5: 1500MVA,500kV,Y/20kVY,X=0.1p.u. Neglecting resistance, transformer phase shift, and magnetizing reactance, draw the equivalent reactance diagram. Use a base of 100 MA and 500 kV for the 50-ohm line. Determine the per-unit reactances.PowerWorid Simulator case Problem 3_60 duplicates Example 3.13 except that a resistance term of 0.06 per unit has been added to the transformer and 0.05 per unit to the transmission line. Since the system is no longer lossless, a field showing the real power losses has also been added to the oneline. With the LTC tap fixed at 1.05, plot the real power losses as the phase shift angle is varied from 10 to +10 degrees. What value of phase shift minimizes the system losses?Consider the oneline diagram shown in Figure 3.40. The three-phase transformer bank is made up of three identical single-phase transformers, each specified by X1=0.24 (on the low-voltage side), negligible resistance and magnetizing current, and turns ratio =N2/N1=10. The transformer bank is delivering 100 MW at 0.8 p.f. lagging to a substation bus whose voltage is 230 kV. (a) Determine the primary current magnitude, primary voltage (line-to-line) magnitude, and the three-phase complex power supplied by the generator. Choose the line-to-neutral voltage at the bus, Va as the reference Account for the phase shift, and assume positive-sequence operation. (b) Find the phase shift between the primary and secondary voltages.
- The per-unit equivalent circuit of two transformers Ta and Tb connected in parallel, with the same nominal voltage ratio and the same reactan of 0.1 per unit on the same base, is shown in Figure 3.43. Transformer Tb has a voltage-magnitude step-up toward the load of 1.05 times that of Ta (that is, the tap on the secondary winding of Tb is set to 1.05). The load is represented by 0.8+j0.6 per unit at a voltage V2=1.0/0 per unit. Determine the complex power in per unit transmitted to the load through each transformer, comment on how the transformers share the real and reactive powers.Consider the single-Line diagram of a power system shown in Figure 3.42 with equipment ratings given: Generator G1: 50MVA,13.2kV,x=0.15p.u. Generator G2: 20MVA,13.8kV,x=0.15p.u. Three-phase -Y transformer T1: 80MVA,13.2/165YkV,X=0.1p.u. Three-phase Y- transformer T2: 40MVA,165Y/13.8kV,X=0.1p.u. Load: 40MVA,0.8PFlagging,operatingat150kV Choose a base of 100 MVA for the system and 132-kV base in the transmission-line circuit. Let the load be modeled as a parallel combination of resistance and inductance. Neglect transformer phase shifts. Draw a per-phase equivalent circuit of the system showing all impedances in per unit.Reconsider Problem 3.64 with the change that now Tb includes both a transformer of the same turns ratio as Ta and a regulating transformer with a 4 phase shift. On the base of Ta, the impedance of the two comp onents of Tb is jO.1 per unit. Determine the complex power in per unit transmitted to the load through each transformer. Comment on how the transformers share the real and reactive pors.
- Consider three ideal single-phase transformers (with a voltage gain of ) put together as three-phase bank as shown in Figure 3.35. Assuming positive-sequence voltages for Va,Vb, and Vc find Va,Vb, and VC. in terms of Va,Vb, and Vc, respectively. (a) Would such relationships hold for the line voltages as well? (b) Looking into the current relationships, express IaIb and Ic in terms of IaIb and Ic respectively. (C) Let S and S be the per-phase complex power output and input. respectively. Find S in terms of S.With the same transformer banks as in Problem 3.47, Figure 3.41 shows the oneline diagram of a generator, a step-up transformer bank, a transmission line, a stepown transformer bank, and an impedan load. The generator terminal voltage is 15 kV (line-to-line). (a) Draw the per-phase equivalent circuit, aounting for phase shifts for positive-sequence operation. (b) By choosing the line-to-neutral generator terminal voltage as the reference, determine the magnitudes of the generator current, transmiss ion-line current, load current, and line-to-line load voltage. Also, find the three-phase complex power delivered to the load.In developing per-unit circuits of systems such as the one shown in Figure 3.10. when moving across a transformer, the voltage base is changed in proportion to the transformer voltage ratings. (a) True (b) False
- Figure 3.39 shows a oneline diagram of a system in which the three-phase generator is rated 300 MVA, 20 kV with a subtransient reactance of 0.2 per unit and with its neutral grounded through a 0.4- reactor. The transmission line is 64km long with a cries reactance of 0.5-/km. The three-phase transformer T1 is rated 350MVA.230/20kV with a leakage reactance of 0.1 per unit. Transformer T2 is composed of three single-phase transformers, each rated 100 MVA, 127/13.2kV with a leakage reactance of 0.1 per unit. Two 13.2kV motors M1 and M2 with a subtransient reactance of 0.2 per unit for each motor represent the load. M1 has a rated input of 200 MVA with its neutral grounded through a 0.4- current-limiting reactor, M2 has a rated input of 100 MVA with its neutral not connected to ground. Neglect phase shifts associated with the transformers. Choose the generator rating as base in the generator circuit and draw the positive-sequence reactance diagram showing all reactances in per unit.1. What are the applications for stripline and microstrip transmission lines? 2. Give 2 examples of characteristic impedance application for each stripline and microstrip transmission lines.The single line diagram of a power system is shown in Figure Q2.1 includinggenerator and transformer winding connection and earthing details. The parametersfor this system have been calculated on a common 100 MVA base and are given inTable Q2.1. All resistances and shunt susceptances are neglected. This systemexperiences a single line to ground fault at a point F on line L1. The point F is at adistance d from Bus 4 along the line L1. The total length l of the line L1 is 50 km.Note that the location of d is not drawn to scale in Figure Q2.1. The fault current atthe fault point F is measured to be 6.106 kA. i) Determine the zero, positive, and negative sequence Thevenin equivalentimpedances as seen at the fault point F. These should be evaluated in per unitand shown as a function of d.ii) Use the sequence impedances calculated in part (i) to determine the distance dof the fault (in km) from Bus 4. It's different from the answer, please don't send it