Outdoor air conditions are: 28°C db, 19.5°C wb Return air conditions are: 22°C db, 50% RH. The mixture air condition outlet the cooling coil are: 10°C db, 0.00735 kg/kgda Draw the system on the Psychrometric chart, then calculate: 1. Cooling coil load. 2. Room sensible heat. 3. Room latent heat. 4. Fresh (outdoor) load. 5. Duct and fan heat gain 6. Sensible heat ratio SHR. If the supply air temperature increases with a value 1°K due to fan motor heat gain and 2°K due to duct heat gain.

Elements Of Electromagnetics
7th Edition
ISBN:9780190698614
Author:Sadiku, Matthew N. O.
Publisher:Sadiku, Matthew N. O.
ChapterMA: Math Assessment
Section: Chapter Questions
Problem 1.1MA
icon
Related questions
Question
Example (1): An air conditioning equipment (figure) have the following:
Supply air mass = 1.26 kg/s.
The cooling coil receives 20 % outdoor air and 80% return air.
Lec. (7)
0
Refrigeration and A/C
Outdoor air conditions are: 28°C db, 19.5°C wb
Return air conditions are: 22°C db, 50% RH.
The mixture air condition outlet the cooling coil are: 10°C db, 0.00735
kg/kgda
Draw the system on the Psychrometric chart, then calculate:
1. Cooling coil load.
2. Room sensible heat.
3. Room latent heat.
4. Fresh (outdoor) load.
5. Duct and fan heat gain
6. Sensible heat ratio SHR.
If the supply air temperature increases with a value 1°K due to fan motor heat
gain and 2°K due to duct heat gain.
0.252 kg/s
1.008 kg/s
Dr. Omar M. Ali
R
الغرفة المراد تكييفها
(22,50%)
1.26 kg/s
B
R
Transcribed Image Text:Example (1): An air conditioning equipment (figure) have the following: Supply air mass = 1.26 kg/s. The cooling coil receives 20 % outdoor air and 80% return air. Lec. (7) 0 Refrigeration and A/C Outdoor air conditions are: 28°C db, 19.5°C wb Return air conditions are: 22°C db, 50% RH. The mixture air condition outlet the cooling coil are: 10°C db, 0.00735 kg/kgda Draw the system on the Psychrometric chart, then calculate: 1. Cooling coil load. 2. Room sensible heat. 3. Room latent heat. 4. Fresh (outdoor) load. 5. Duct and fan heat gain 6. Sensible heat ratio SHR. If the supply air temperature increases with a value 1°K due to fan motor heat gain and 2°K due to duct heat gain. 0.252 kg/s 1.008 kg/s Dr. Omar M. Ali R الغرفة المراد تكييفها (22,50%) 1.26 kg/s B R
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 4 steps with 1 images

Blurred answer
Knowledge Booster
Refrigeration and Air Conditioning
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Elements Of Electromagnetics
Elements Of Electromagnetics
Mechanical Engineering
ISBN:
9780190698614
Author:
Sadiku, Matthew N. O.
Publisher:
Oxford University Press
Mechanics of Materials (10th Edition)
Mechanics of Materials (10th Edition)
Mechanical Engineering
ISBN:
9780134319650
Author:
Russell C. Hibbeler
Publisher:
PEARSON
Thermodynamics: An Engineering Approach
Thermodynamics: An Engineering Approach
Mechanical Engineering
ISBN:
9781259822674
Author:
Yunus A. Cengel Dr., Michael A. Boles
Publisher:
McGraw-Hill Education
Control Systems Engineering
Control Systems Engineering
Mechanical Engineering
ISBN:
9781118170519
Author:
Norman S. Nise
Publisher:
WILEY
Mechanics of Materials (MindTap Course List)
Mechanics of Materials (MindTap Course List)
Mechanical Engineering
ISBN:
9781337093347
Author:
Barry J. Goodno, James M. Gere
Publisher:
Cengage Learning
Engineering Mechanics: Statics
Engineering Mechanics: Statics
Mechanical Engineering
ISBN:
9781118807330
Author:
James L. Meriam, L. G. Kraige, J. N. Bolton
Publisher:
WILEY