PROBLEM 6 AL km long, 330kV, three-phase transmission line has a series reactance x = 0.280/km and a shunt admittance y = j3.2 x 10 S/km. 6.1 Calculate the ABCD parameters of the ine. The receiving end conditions are VR= (325+j0) kV and IR= 200 A at a lagging power factor of 0.9. Using the ABCD parameters, calculate the sending end voltage, current and transmission angle, 8. 6.2
PROBLEM 6 AL km long, 330kV, three-phase transmission line has a series reactance x = 0.280/km and a shunt admittance y = j3.2 x 10 S/km. 6.1 Calculate the ABCD parameters of the ine. The receiving end conditions are VR= (325+j0) kV and IR= 200 A at a lagging power factor of 0.9. Using the ABCD parameters, calculate the sending end voltage, current and transmission angle, 8. 6.2
Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter5: Transmission Lines: Steady-state Operation
Section: Chapter Questions
Problem 5.18P
Related questions
Question
parameter : L = 230km
Expert Solution
This question has been solved!
Explore an expertly crafted, step-by-step solution for a thorough understanding of key concepts.
This is a popular solution!
Trending now
This is a popular solution!
Step by step
Solved in 3 steps with 3 images
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning