A single-phase, 50 Hz, 120 km transmission line delivers 50 MVA at 0.86 lagging power factor at 132 kV. The resistance and a reactance of the line per phase per km are 0.23 Q and 0.4 Q, respectively. If the capacitive admittance of line is 3 x 10-6 Siemens/phase/km, use T-model method to calculate: a) Sending-end Voltage b) Line efficiency
Q: Q4: A 3-phase, 50Hz, 150 km line has a resistance, inductive reactance and capacitive shunt…
A:
Q: A 230-kV, three-phase transmission line has a per phase series impedance of z = 0.05+j0.45 Ω per Km…
A:
Q: A 3-0, three wire CBA system, with an effective line voltage 200 V, has a balanced A. Connected load…
A: In this question we need to find a line and phase current of given three phase system.
Q: QUESTION 1: For the 3-ph, double circuit O.H.T.L shown below: 1- Find the spacing between the two…
A: According to question, For the 3-ph, double circuit O.H.T.L shown below: 1- Find the spacing between…
Q: A 3-phase overhead transmission line delivers a load of 80 MW at 0.8 p.f. lagging and 220 kV between…
A: Symmetrical T-network- In nominal T-network is an analysis of medium transmission line that is half…
Q: 'a) Bus 1 is connected to bus 2 by a short (less than 50 miles) and lossless transmission line…
A: Part (a): Consider the expression of real power sent by bus 1, P12=V1V2Xsinθ…
Q: A 3 phase line having an impedance of (5+j20)ohm per phase delivers a load of 30MW at a power…
A: It is given that: Z=5+j20 Ω =20.61∠75.96° Ωso, R=5 Ω and X=20j Ωcosϕ=0.3Y=0 (neglected)V=33 KVSo,…
Q: A three-phase power of 460 MW is transmitted to a substation located 500 km from the source of…
A: According to question, find the theoretical three-phase maximum power that can be transferred by the…
Q: 9.33 A three-phase, 60-Hz, 350-km transmission line has the following parameters: R 0.10 /km, XL at…
A:
Q: the
A:
Q: 3-) Three-phase, 100 km long unit length and serial impedance per phase is 0,125+j0.34 2/km. The…
A:
Q: 1. Given a single phase, 138 kV, 60-Hz, 50 km-long transmission line consisting of two aluminum…
A: Solution (2) - Given,A single phase transmissio line consisting two aluminimum…
Q: A 3-ph transmission line has a total length of 200 km. This transmission line has a resistance of…
A: The length of transmission line is 200 km
Q: Q3/ A 3-phase, 50HZ, 150 km line has a resistance, inductive reactance and capacitive shunt…
A: Total resistance 'R' per phase of the line, R=0.1*150 =15Ω Total inductive reactance 'XL'…
Q: The ABCD constants of a lossless three-phase, 500-kV transmission line are A = D = 0.86 + j0 B = 0 +…
A: Solution (a) 3 Vr Ir =1000x106Ir = 1000 x106 x1033x500x103 =1154. 7 A (0.8-j0.6)Vs = AVr+BIr…
Q: Q4. A 3-phase, 60 Hz, 500-kV transmission line is 300 km long. The line inductance is 0.97 mH/km per…
A:
Q: A balanced load of 30MW is supplied at 132 kV, 50Hz and 0.85 p.f. lagging by means of a transmission…
A: According to question: Using nominal 'T' approximation: The sending end voltage is calculated as…
Q: A single-phase transmission line consists of two aluminum conductors with a radius of 2 cm spaced…
A:
Q: A 60 Hz, single-circuit, three-phase transmission line is 150 mi long. The line is connected to a…
A:
Q: A 132-kV, 50HZ, three-phase transmission line has a per phase series impedance of z = 0.11 0/km and…
A:
Q: Question 4 a) A 3-phase, single circuit transmission line, is given with the length somewhere in the…
A:
Q: Give the physical significance of the generalized circuit constant A,B,C and D of a transmission…
A: Give the physical significance of the generalized circuit constant A,B,C and D of a transmission…
Q: A bundled 500kv, 60Hz three phase completely transposed overhead line having three ACSR…
A: Consider the area of the bundle conductor is , A=556.5 mm2πr2=556.5r=556.5πr=13.3093 mm Consider the…
Q: A 3-ph, 50 Hz, 150 km line has resistance, inductive reactance and capacitive admittance of 0.1, 0.5…
A:
Q: A 300 km long 3-phase transmission line of 154 kV is operated at 60 Hz. The line is on average 1200…
A: Given data: f=60 Hz D = 550 cm A=40 mm2 go=30 KV/cm En=1543KV Solution: Area of the conductors,…
Q: The per-phase constants of a 345-kV, three-phase, 150-km-long transmission line are resistance = 0.1…
A: we need to determine the sending-end voltage.
Q: A 69-kV, three-phase short transmission line is 16 km long. The line has a per phase series…
A:
Q: Q. In a three phase 420 kV high-voltage overhead transmission line, the diameter of the conductors…
A:
Q: A 69-kV, three phase short transmission line is 16km long. The line has a per phase series impedance…
A: We need to determine the sending end voltage, voltage regulation, the sending end power, and…
Q: If the per-phase line loss in a 60-km-long transmission line is not to exceed 60 KW while it is…
A: Considering the given data:
Q: Q. In a three phase 345 kV high-voltage overhead transmission line, the diameter of the conductors…
A:
Q: A 220-kV, three-phase transmission line is 40 km long. The resistance per phase is 0.15 N per km and…
A:
Q: A 345-kV transmission line has a series impedance of (4 + j60) Q and a shunt admittance of j2 ×…
A: Given values are - SBase=100MVAVBase=345kVZ=4+j60Y=j2×10-3S
Q: The spacing for a 3-phase horizontally spaced line operating at 50 Hz, 132 kV, is 1.6 m between…
A:
Q: km, and C=8.86nF/km. At full load, the line delivers 250MW at 0.9 pf lagging and 230 kV. Using the z…
A: All the values of R,L and C are given in per unit length. We will multiply them with total length…
Q: P 8.1 Find the regulation and efficiency of an 80-km, 3-phase, 50-c/s transmission line delivering…
A:
Q: A load of 1000 kW at 0·8 p.f. lagging is received at the end of a 3-phase line 20 km long. The…
A:
Q: 3 A 3-phase, 50 Hz transmission line 100 km long, Load current i 5A at 0-9 p.f.lagging and at 110…
A:
Q: A 400 km long, 50 Hz transmission line having series resistance and inductance of 0.12/km and…
A: Given: A 400 km long, 50 Hz transmission line have Resistance, R=0.1 Ω/km Inductance, L=1 mH/km…
Q: A 400kV, 200km, 3-phase transmssion line have the follollowing parameters per phase: z= 0.14+j0.304…
A:
Q: For a given short transmission line of impedance R+jX ohms/phase, the sending end and receiving end…
A: Short transmission line Impedance Z=R+jX ohm/phase Sending end voltage Vs Receiving end voltages VR…
Q: 2. A balanced load of 30 MW is supplied at 132 kV, 50 Hz and 0-85 p.f. lagging by means of a…
A:
Q: power of 90+j70 MVA is drawn from the end of a 220 km three-phase transmission line with a voltage…
A:
Q: A 60 Hz, three-phase transmission line is 100 miles long. It has a total series impedance of {35 +…
A: Given f=50 Hz Z=R+XL =35+ j 120 ohm, Y=j 930×10-6 mho VR, line= 220 kV per phase, VR, = 2203 =127…
Q: QUESTION 4 a) The single-line diagram of a three-phase system is shown in figure below. The…
A: For the given system we need to draw a per unit impedance diagram
Q: A 400kV, 200km, 3-phase transmssion line have the follollowing parameters per phase: z = 0.14+j0.304…
A:
Q: In a transmission line system, the three-phase lines supported by using three identical string…
A: Insulator-Each conductor is provided with a sufficient thickness of insulation depending upon the…
Q: Example 3.2 A three phase 60HZ completely transposed 345kV, 200km line has two 403mm2 26/2 ACSR…
A:
Q: Three-phase transmission line has ABCD constants as shown below. The line is 80 km long. A =…
A: The transmission line problem can be solved easily.
q13
Step by step
Solved in 3 steps with 15 images
- Consider a long radial line terminated in its characteristic impedance Zc. Determine the following: (a) V1/I1, known as the driving point impedance. (b) | V2 |/V1|, known as the voltage gain, in terms of al. (c) | I2 |/| I1 |, known as the current gain, in terms of al. (d) The complex power gain, S21/S12, in terms of al. (e) The real power efficiency, (P21/P12)=, terms of al. Note: 1 refers to sending end and 2 refers to receiving end. (S21) is the complex power received at 2; S12 is sent from 1.A small manufacturing plant is located 2 km down a transmission line, which has a series reactance of 0.5/km. The line resistance is negligible. The line voltage at the plant is 4800V(rms). and the plant consumes 120kW at 0.85 power factor lagging. Determine the voltage and power factor at the sending end of the transmission line by using (a) a complex power approach and (b) a circuit analysis approach.A balanced load of 30 MW is supplied at 132 kV, 50 Hz and 0•85 p.f. lagging by means of a transmission line. The series impedance of a single conductor is (20 + j52) ohms and the total phases-neutral admittance is 315 microsiemens. Shunt leakage may be neglected. Using the nominal T approximation, calculate the line voltage at the sending end of the line. If the load is removed and the sending end voltage remains constant, find the percentage rise in voltage at the receiving end.
- A balanced load of 30MW is supplied at 132 kV, 50Hz and 0.85 p.f. lagging by means of a transmission line. The series impedance of a single conductor is (20+j 52) ohms and the total phase-neutral admittance is 315 micro mho. Shunt leakage may be neglected. Using the nominal T and π approximation, calculate the line voltage at the sending end of the line. If the load is removed and the sending end voltage remains constant, find the percentage rise in the voltage at the receiving end.A short 3 phase transmission line, connected to a 33kV, 50 Hz generating station at the sending end is required to supply a load of 10Megawatts at 0.8 power factor lagging, 30kV at the receiving end. If the minimum transmission line efficiency is to be limited to 96%, estimate the per phase values of resistance and inductance of the line.A 500 kV, 60 Hz uncompensated three-phase transmission line is 500 km long. The line has three ACSR 1113-kcmil (Finch) conductors per phase with parameters Current carrying capability of single ACSR 1113-kcmil (Finch) conductor is 1,110 A. Calculate the theoretical maximum (steady state stability limit) real power that this line can deliver and compare with the thermal limit of the line. Assume VS = VR = 1.0 per unit and unity power factor at the receiving end.
- For a given short transmission line of impedance R+jX ohms/phase, the sendingend and receiving end voltages Vs and Vr are fixed. Derive the expression for themaximum power that can be transmitted over the line.A 46-kv 0.8-lagging power factor load is connected to the end of a short transmission line where the voltage is 230. If the line resistance and reactance are 0.06 and 0.08 ohm, respectively, calculate the voltage at the sending end.A 3-ph, 60 Hz, 200 km long, 220 kV transmission line has per km per phase constants of resistance 0.033 Ω, inductive reactance 0.33 Ω, capacitive susceptance 3.3x10 -6 mho. The load at the receiving end of the line is 500 MW at 0.95 power factor leading and voltage has dropped to 209 kV. Using the PI model, calculate the voltage, current and power factor at the sending end. Please answer in typing format solution please only typing format Please I will like it please reply to
- (Q) A 10 mile transmission line with an impedance of (0.122+j0.849) Ω per mile is delivering 230A at 230kV and 0.8 power factor lagging. Determine: the sending end voltage the line efficiency and regulationS.1) The serial impedance per phase of a three-phase 45 km energy transmission line is 2 + j4 / phase. A load with a power factor of cos2 = 0.8 forward is fed from the end of the line. Since the line voltage at the beginning and end of the line of the energy transmission line is wanted to be kept constant at 115 kV, a) Active and reactive powers drawn from the beginning and end of the line, b) Calculating the power consumed along the energy transmission line and the efficiency of the line. S.2) Line constants of an energy transmission line are given as A = D = 0.8746 + j0, B = 0 + j128.34, C = j0.0018316 S. At the beginning of the line, it is desired to write 1920 MW active power and 600 MVAr reactive power lines under 7650kV line voltage. According to this business, a) Calculate the line end magnitudes (U2, I2 and P2). b) What value does the end voltage take when the load fed from the end of the line is deactivated? S.3) The length of a phased energy transmission line with a…A 60 Hz, three-phase transmission line is 100 miles long. It has a total seriesimpedance of {35 + j120) n and a shunt admittance of j930 μsiemen. It delivers40 MW at 220 kV with 90% lagging power factor. Find the voltage at the sendingend by:(a) short line approximation(b) the nominal rr approximation(c) the nominal T approximationAlso determine the voltage regulation for the given line and the power loss.Assume the sending end voltage remains constant. Expected Answer: (a) 237.67 kV, 1.4284 MW, 8.03%; (b) 225.8 kV, 1.1642 MW, 8.67% (c) 225.10 kV, 1.5095 MW, 8.35% Pls. Provide Full Solution for thumbs up