The positive, negative and zero sequence reactances of a 15 MVA, 11 kV three-phase wye-connected generator are 11%, 8% and 3% respectively. The neutral of the generator is grounded and is excited to the rated voltage on open circuit. A line to ground fault occurs on phase a of the generator. Calculate the fault current.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter9: Unsymmetrical Faults
Section: Chapter Questions
Problem 9.35P
icon
Related questions
icon
Concept explainers
Question
The positive, negative and zero sequence reactances of a 15
MVA, 11 kV three-phase wye-connected generator are 11%, 8%
and 3% respectively. The neutral of the generator is
grounded and is excited to the rated voltage on open
circuit. A line to ground fault occurs on phase a of the
generator. Calculate the fault current.
Transcribed Image Text:The positive, negative and zero sequence reactances of a 15 MVA, 11 kV three-phase wye-connected generator are 11%, 8% and 3% respectively. The neutral of the generator is grounded and is excited to the rated voltage on open circuit. A line to ground fault occurs on phase a of the generator. Calculate the fault current.
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Knowledge Booster
Fault analysis
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning