3-phase induction motor load takes 900 kVA at a power factor of 0.707. Calculate the KVA rating of the capacitor bank to raise the resultant power factor of the installation of 0.866 lagging. Find also the resultant power factor when the capacitors are in circuit and the motor load has fallen to 300 kVA at 0.5 power facto

Electric Motor Control
10th Edition
ISBN:9781133702818
Author:Herman
Publisher:Herman
Chapter39: Synchronous Motor Operation
Section: Chapter Questions
Problem 14SQ: Induction motors and welding transformers require magnetizing current, which causes a. lagging power...
icon
Related questions
icon
Concept explainers
Question
A 400-V, 3-phase induction motor load takes 900 kVA at a power factor of 0.707. Calculate the KVA rating of the capacitor bank to raise the resultant power factor of the installation of 0.866 lagging. Find also the resultant power factor when the capacitors are in circuit and the motor load has fallen to 300 kVA at 0.5 power factor.
Expert Solution
steps

Step by step

Solved in 4 steps

Blurred answer
Knowledge Booster
Synchronous Motor
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Electric Motor Control
Electric Motor Control
Electrical Engineering
ISBN:
9781133702818
Author:
Herman
Publisher:
CENGAGE L
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning