70. A circuit supplies a continuous load of 38 amperes and is protected by a 50-amperecircuit breaker. All conductor terminations in the circuit are rated at 75°C. If the circuit conductors are THWN copper, determine the minimum size permitted for the circuit.
70. A circuit supplies a continuous load of 38 amperes and is protected by a 50-amperecircuit breaker. All conductor terminations in the circuit are rated at 75°C. If the circuit conductors are THWN copper, determine the minimum size permitted for the circuit.
Delmar's Standard Textbook Of Electricity
7th Edition
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Stephen L. Herman
Chapter10: Using Wire Tables And Determining Conductor Sizes
Section: Chapter Questions
Problem 4PP: 4. Eight 10 AWG aluminum conductors with Type THWN insulation are installed in a single conduit....
Related questions
Question
Expert Solution
This question has been solved!
Explore an expertly crafted, step-by-step solution for a thorough understanding of key concepts.
Step by step
Solved in 2 steps with 1 images
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Recommended textbooks for you
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:
9781337516549
Author:
Simmons
Publisher:
CENGAGE LEARNING - CONSIGNMENT
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:
9781337516549
Author:
Simmons
Publisher:
CENGAGE LEARNING - CONSIGNMENT