A 2-pole, 50 Hz, 11 kV synchronous generator with a rating of 120 MW and 0.87 lagging power factor has a moment of inertia of 12,000 kg- . Calculate the constants H and M

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter6: Power Flows
Section: Chapter Questions
Problem 6.65P
icon
Related questions
icon
Concept explainers
Question

A 2-pole, 50 Hz, 11 kV synchronous generator with a rating of 120 MW and 0.87 lagging power factor has a moment of inertia of 12,000 kg- . Calculate the constants H and M A 4-pole synchronous generator supplies over a short line a load of 60 MW to a load bus. If the maximum steady state capacity of the transmission line is 110 MW, determine the maximum sudden increase in the load that can be tolerated by the system without losing stability

Expert Solution
steps

Step by step

Solved in 5 steps with 3 images

Blurred answer
Knowledge Booster
Load flow analysis
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.