A single phase transmission line is delivering 430 kVA load at 10 kV. Its resistance is 5 Q and inductive reactance is 60. If the load power factor is 0.8 lagging. Determine the Current through the line Sending end voltage Sending end power factor
Q: 50 km of single-phase transmission line, 800 kVA power 8 kV, is carried with 0.9 reverse power…
A: The given information in the above problem are 1. Length of the line = 50km 2. Power carried by the…
Q: The sending-end and receiving-end voltages of a three-phase transmission line at a 200 MW load are…
A: According to the question we have to find the value of the maximum steady-state power that can be…
Q: A 69 kV, three-phase transmission line is 16 km long. The line has a per phase series impedance of…
A: A three phase line has, Line length (l)=16 km The per phase series impedance (Z)=0.125+j0.4375…
Q: A single phase transmission line is delivering 430 kVA load at 10kV. Its resistance is 6 Q and…
A:
Q: For Figure 1: A short 3-phase line with an impedance of (6+j8) per line has sending end and…
A: Ans. Is shown below.
Q: A single phase transmission line is delivering 450 kVA load at 13 kV. Its resistance is 7 Q and…
A:
Q: 5. A 3-phase line 3 km long delivers 3000 kW at a p.f. 0-8 lagging to a load. The resistance and…
A: As per Bartleby guidelines we are allowed to solve only one question, please asks the rest again.…
Q: The resistance and reactance of the single- phase 60HZ transmission line conductors are 7.2 ohm and…
A:
Q: For a single phase network shown in the figure below, work in per-unit with 200 VA & 250 V as base…
A: In this question we need to find a load current of the given system.
Q: A load of 145 MW at a power factor of 0.6 lagging can be delivered by a 3-phase transmission line.…
A: Per phase power = total power /3. Per voltage = line voltage/sqrt(3). Power delivered =…
Q: A load of 130 MW at a power factor of 0.9 lagging can be delivered by a 3-phase transmission line.…
A:
Q: The conductor of one phase of a three- phase transmission line operating at a line voltage of 258 kV…
A: Given: Line voltage=258 kV Rated VA=510 MVA CT ratio of current transformer=1000/5
Q: A load of 145 MW at a power factor of 0.9 lagging can be delivered by a 3-phase transmission line.…
A: We are authorized to answer three subparts at a time, since you have not mentioned which part you…
Q: The voltage regulation of a transmission line is negative for lagging power factor. Select one: O…
A: Given Voltage regulator is negative for lagging load True or false
Q: The RL (Resistive and Inductive) Load in the Load Side Section of the Distribution Line Simulator is…
A: This question is based on the load connection in the distribution line simulator. RL load in the…
Q: A single phase transmission line is delivering 440 kVA load at 10 kV. Its resistance is 4.5 Q and…
A: Note: Since we only answer up to 3 sub-parts, we’ll answer the first 3. Please resubmit the question…
Q: A single phase short-transmission line is feeding a load of 12 kW at a 0.8 lagging power factor. The…
A: Given values are - PL=12kWcosϕ=0.8R=5ohmX=10ohmVL=440∠0oV
Q: A single phase transmission line is delivering 440 kVA load at 10 kV. Its resistance is 5Q and…
A:
Q: A single phase transmission line is delivering 470 kVA load at 10 kV. Its resistance is 6.5 N and…
A: Receiving end voltage =10kV. Receiving end power factor=0.8 lag Receiving end power=470kVA So…
Q: A load of 125 MW at a power factor of 0.6 lagging can be delivered by a 3-phase transmission line.…
A: single phase power=3 phase power 3. per phase voltage=Line voltage3. line current=power…
Q: In the above figure, a single line model of a three-phase power system is given. Base power 50MVA,…
A:
Q: A single phase transmission line is delivering 440 kVA load at 11 kV. Its resistance is 50 and…
A: Sending end voltage =receiving end voltage +drop in the line. Efficiency = output power/input power.…
Q: a short three phase transmission line connected to 33kv 50 hertz generating station at starting and…
A: Write the given information from the question.
Q: In single phase AC distribution system, the net drop is the sum of the drop in resistance due to the…
A: In single phase AC distribution system, we will have resistance as well as reactance components.
Q: a single phase transmission line is delivering 500kva load at 2kV It resistance 0.2ohm and inductive…
A: Given data, The value of receiving end voltage is VR = 2 kV = 2000 V. The value of power is P = 500…
Q: Determine the per unit impedance of a transmission line having an impedance of 30 + j110 Ω on 100…
A:
Q: The resistance and reactance of the single-phase 60HZ transmission line conductors are 8.8 ohm and 9…
A: Given single phase transmission lineResistance R=8.8 ΩReactance XL=9 ΩReceiving end voltage VR=56…
Q: A single-phase transmission line has a resistance of 0.22 ohm and inductive reactance of 0.36 ohm.…
A: Write the given values. R=0.22 ΩXL=0.36 ΩSR=500 kVAVR=2000 Vpf=0.707 lagging
Q: A single phase transmission line is delivering 450 kVA load at 13 kV. Its resistance is 7 Q and…
A: Since you have posted a question with multiple sub-parts, we will solve first three sub- parts for…
Q: A load of 120 MW at a power factor of 0.6 lagging can be delivered by a 3-phase transmission line.…
A: Note- as per bartleby policy we are only allowed to solve 1 ques per window. Please post the second…
Q: The resistance and reactance of the single- phase 60HZ transmission line conductors are 7.2 ohm and…
A: inductive reactance=2*π*frequency*inductance. sending end power factor=costan-1sendind end reactive…
Q: A single phase transmission line is delivering 420 kVA load at 11 kV. Its resistance is 5 2 and…
A:
Q: Florida Electrical Transmission Company has to supply the demand of four companies in different…
A: The solution can be achieved as follows.
Q: The annual load duration curve of a power supply system may be considered as straight line from 40…
A: Given: The annual load duration curve of a power supply system may be considered as straight line…
Q: A single phase transmission line is delivering 450 kVA load at 12 kV. Its resistance is 7 0 and…
A: As per our company guidelines we are supposed to answer only first 3 sub-parts. Kindly repost other…
Q: A single phase transmission line is delivering 460 kVA load at 11 kV. Its resistance is 4.5 Q and…
A: Fig: Equivalent circuit diagram of given single-phase Tr-line (a) current flowing…
Q: For a single phase ac voltage controller/chopper, which is designed by using thyristors, with the…
A: A rectifier circuit is used to rectify the AC power generated by this source to the DC power that…
Q: A hypothetical case: A power station generates 50MVA at a voltage of 18.5kV (3-phase, 50HZ). This…
A: A power station generates 50 MVA at a voltage of 18.5 kV (3-phase, 50 Hz). This power must be…
Q: A single phase transmission line is delivering 450 kVA load at 14 kV. Its resistance is 5.5 Q and…
A: Sending end voltage Vs = Receiving end voltage + drop in the line Regulation = Vs -VrVr…
Q: A load of 120 MW at a power factor of 0.6 lagging can be delivered by a 3-phase transmission line.…
A: Since we only answer up to 3 sub-parts, we’ll answer the first 3. Please resubmit the question and…
Q: A load of 120 MW at a power factor of 0.8 lagging can be delivered by a 3-phase transmission line.…
A: per phase power =3 phase power 3Given 3 phase power = 120 MWso per phase power = 1203 = 40 MWPer…
Q: Using a test equipment, Vmax was found to be 5V while Vmin is 1V. The distance between voltage…
A: Given : Note : Please note that for the proper understanding here we have used two methods to…
Q: A 230 kV transmission line has an impedance of 50 cis 78 ohms and a capacitive reactance of 1,200…
A:
Q: Below is a 3-phase, 3 wire system. Compute for the line currents, total real power, total reactive…
A: Given line voltages are Vab =200 ∠0 V Vbc=200 ∠240 V =200 ∠-120° Vca =200 ∠-240 V =200 ∠120 V it…
Q: The conductor of one phase of a three- phase transmission line operating at a line voltage of 324 kV…
A: Given that MVA rating of VT (S) = 930 MVA Primary voltage of VT ,V1 =324 KV CT ratio = 1200/1…
Q: A single phase transmission line is delivering 480 kVA load at 11 kV. Its resistance is 6 n and…
A: In this question, Single phase transmission line Load = 480kVA, at 0.9PF lagging. Find the…
Q: A single phase transmission line is delivering 470 kVA load at 10 kV. Its resistance is 6.5 e and…
A: Dear student as per our guidelines we are supposed to solve only one question in which it should…
Q: A load of 145 MW at a power factor of 0.8 lagging can be delivered by a 3-phase transmission line.…
A:
Please answer all subparts
Step by step
Solved in 2 steps with 1 images
- A three-phase line, which has an impedance of (2+j4) per phase, feeds two balanced three-phase loads that are connected in parallel. One of the loads is Y-connected with an impedance of (30+j40) per phase, and the other is -connected with an impedance of (60j45) per phase. The line is energized at the sending end from a 60-Hz, three-phase, balanced voltage source of 1203V (rms. line-to-line). Determine (a) the current, real power. and reactive power delivered by the sending-end source: (b) the line-to-line voltage at the load: (C) the current per phase in each load: and (d) the total three-phase real and reactive powers absorbed by each load and by the line. Check that the total three- phase complex power delivered by the source equals the total three-phase power absorbed by the line and loads.A 40-km, 220-kV, 60-Hz, three-phase overhead transmission line has a per-phase resistance of 0.15/km, a per-phase inductance of 1.3263 mH/km, and negligible shunt capacitance. Using the short line model, find the sending-end voltage, voltage regulation, sending-end power, and transmission line efficiency when the line is supplying a three-phase load of (a) 381 MVA at 0.8 power factor lagging and at 220 kV and (b) 381 MVA at 0.8 power factor leading and at 220 kV.A balanced three-phase load is connected to a 4.16-kV, three-phase, fourwire, grounded-wye dedicated distribution feeder. The load can be mode led by an impedance of ZL=(4.7+j9)/phase, wye-connected. The impedance of the phase conductors is (0.3+j1). Determine the following by using the phase A to neutral voltage as a reference and assume positive phase sequence: (a) Line currents for phases A, B, and C. (b) Line-to-neutral voltages for all three phases at the load. (c) Apparent. active, and reactive power dissipated per phase, and for all three phases in the load. (d) Active power losses per phase and for all three phases in the phase conductors.
- Let a series RLC network be connected to a source voltage V, drawing a current I. (a) In terms of the load impedance Z=ZZ, find expressions for P and Q, from complex power considerations. (b) Express p(t) in terms of P and Q, by choosing i(t)=2Icost. (c) For the case of Z=R+jL+1/jC, interpret the result of part (b) in terms of P,QL, and Qc. In particular, if 2LC=1, when the inductive and capacitive reactances cancel, comment on what happens.With generator conyention, where the current leaves the positive terminal of the circuit element, if P is positive then positive real power is delivered. (a) False (b) TrueA balanced -connected impedance load with (12+j9) per phase is supplied by a balanced three-phase 60-Hz,208-V source, (a) Calculate the line current, the total real and reactive power absorbed by the load, the load power factor, and the apparent load power, (b) Sketch a phasor diagram showing the line currents, the line-to-line source voltages, and the -load currents. Use Vab as the reference.
- The three-phase source line-to-neutral voltages are given by Ean=100,Ebh=10+240, and Ecn=10240volts. Is the source balanced? (a) Yes (b) NoConsider a long radial line terminated in its characteristic impedance Zc. Determine the following: (a) V1/I1, known as the driving point impedance. (b) | V2 |/V1|, known as the voltage gain, in terms of al. (c) | I2 |/| I1 |, known as the current gain, in terms of al. (d) The complex power gain, S21/S12, in terms of al. (e) The real power efficiency, (P21/P12)=, terms of al. Note: 1 refers to sending end and 2 refers to receiving end. (S21) is the complex power received at 2; S12 is sent from 1.The units of admittance, conductance, and susceptance are siemens. (a) True (b) False
- While the instantaneous electric power delivered by a single-phase generator under balanced steady-state conditions is a function of time havi ng two components of a constant and a double-frequency sinusoid, the total instantaneous electric power delivered by a three-phase generator under balanced steady-state conditions is a constant. (a) True (b) FalseOne advantage of balanced three-phase systems over separate singlephase systems is reduced capital and operating costs of transmission and distribution. (a) True (b) FalseTwo balanced three-phase loads that are connected in parallel are fed by a three-phase line having a series impedance of (0.4j2.7) per phase. One of the loads absorbs 560 kVA at 0.707 power factor lagging, and the other 132 kW at unity power factor. The line-to-line voltage at the load end of the line is 2203V. Compute (a) the line-to-line voltage at the source end of the line. (b) the total real and reactive power losses in the three-phase line, and (c) the total three-phase real and reactive power supplied at the sending end of the line. Check that the total three-phase complex power delivered by the source equals the total three-phase comp lex power absorbed by the line and loads.