Power System Analysis Problem Soru-6) The single line diagram of the 3-phase system is given below. The reactance values of line 1 and line 2 are 48.4 and 65.43 ohms, respectively. By selecting the base values of the generator as 100 MVA and 22 kV, the unit value of the power system a) b) busbar number 1, c) Draw the single line diagram. The engine works at 10.45 kV with a 0.8 power factor (forward). Accordingly, the voltage of Calculate the internal emfvalues of the generator and engine. T G: 90 MVA X = 18 % 22/220 kV X = 10 % 220/11 kV X = 6.0 % 22/110 kV X = 6.4 % 1 10/11 kV X = 8.0 % 22 kV Line ! T: 50 MVA T2: 40 MVA Тз: 40 MVA T4: 40 MVA M: 66.5 MVA 10.45 kV 220 kV G M 73 Line 2 Load X = 18.5 % %3D 110KV

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter9: Unsymmetrical Faults
Section: Chapter Questions
Problem 9.33P
icon
Related questions
icon
Concept explainers
Question
100%
Power System Analysis Problem
Soru-6) The single line diagram of the 3-phase system is given below. The reactance values of line 1
and line 2 are 48.4 and 65.43 ohms, respectively. By selecting the base values of the generator as 100
MVA and 22 kV, the unit value of the power system
a)
b)
busbar number 1,
c)
Draw the single line diagram.
The engine works at 10.45 kV with a 0.8 power factor (forward). Accordingly, the voltage of
www
Calculate the internal emf values of the generator and engine.
T
T2
G: 90 MVA
22 kV
X = 18 %
22/220 kV X = 10 %
220/11 kV X = 6.0 %
Line !
T: 50 MVA
T2: 40 MVA
T3: 40 MVA
T: 40 MVA
M: 66.5 MVA 10.45 kV
220 kV
%3D
G
M
22/110 kV X = 6.4 %
%3D
T3
5
1 10/11 kV X = 8.0 %
Line 2
Load
X = 18.5 %
110 kV
Transcribed Image Text:Power System Analysis Problem Soru-6) The single line diagram of the 3-phase system is given below. The reactance values of line 1 and line 2 are 48.4 and 65.43 ohms, respectively. By selecting the base values of the generator as 100 MVA and 22 kV, the unit value of the power system a) b) busbar number 1, c) Draw the single line diagram. The engine works at 10.45 kV with a 0.8 power factor (forward). Accordingly, the voltage of www Calculate the internal emf values of the generator and engine. T T2 G: 90 MVA 22 kV X = 18 % 22/220 kV X = 10 % 220/11 kV X = 6.0 % Line ! T: 50 MVA T2: 40 MVA T3: 40 MVA T: 40 MVA M: 66.5 MVA 10.45 kV 220 kV %3D G M 22/110 kV X = 6.4 % %3D T3 5 1 10/11 kV X = 8.0 % Line 2 Load X = 18.5 % 110 kV
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 8 steps with 3 images

Blurred answer
Knowledge Booster
Load flow analysis
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning