A three-phase, wye-connected, 7 kVA, 230 V synchronous generator has a reactance of 7 ohms per phase. Using the rated kVA and voltage as base values, determine the per-unit reactance. Per unit reactance is Xg = p.u Then refer this per-unit value to a 280 V, 9.5 kVA base. Per unit reactance is Xg = p.u Only use numbers and "." for decimal points.
Q: What is Per Unit System? In the given picture, would there be any difference in calculation of the…
A: The per-unit value of any quantity is defined as the ratio of actual value in any unit to the base…
Q: Three zones of a single-phase circuit are identified in Figure. The zones are connected by…
A: per unit system The ratio of actual value to the base or reference value in the same unit is called…
Q: A three-phase, wye-connected, 7 kVA, 230 V synchronous generator has a reactance of 7 ohms per…
A:
Q: Three single-phase two-winding transformers, each rated 400 MVA, 13.8/ 199.2 kV, with leakage…
A:
Q: Neglecting resistance, transformer phase shift, and magnetizing reac- tance, draw the equivalent…
A:
Q: An 11-kV, 1000-kVA, 3-phase, Y-connecied alternator has a resistance of 22 per phase. The…
A: Given, 11kV 1000KVA, 3phase R=2 ohms per phase pf=0.8 lagging
Q: Q4: A power distribution station consisting of 100OKVA, 4500V/225V, and 50 cycles per second…
A: Write the expression for the number of turns,
Q: Power coefficient of a 3-phase, star-connected, salient-pole synchronous generator, ignoring the…
A: Power coefficient of a 3-phase, star-connected, salient-pole synchronous generator, ignoring the…
Q: Question 1: Figure 1 shows a single-line diagram of a three-phase, 60-Hz synchronous generator,…
A: The given single line diagram is shown below:
Q: 2- Why it's imporctical carry out actual load test on large rating transformers ?
A: For large-rated transformer, the value of the rated current is usually very high.
Q: Q2:- a synchronous generator is 25 MVA, 11kV, it is star- connected with the neutral point solidly…
A: Given:X1=X2=0.2puX0=0.08pu Consider power base is 25 MVA and voltage base is 11 KVVoltage PU =1
Q: Three single-phase two-winding transformers,
A:
Q: Three-phase alternator supplying a three wires, CBA system with a line voltage of 100 Volt,…
A:
Q: Three zones of a single-phase circuit are identified in the figure with a generator voltage…
A: For the evaluation of electrical machines, one-of-a-kind values are required, consequently, per unit…
Q: A 250 MVA, 25 kV, 3 phase synchronous generator has a synchronous reactance X, of 1.6 pu. It is…
A: According to company policy, i am solve only first 3 part. We can draw the given power system as a)…
Q: Obtain the per-unit equivalent circuit for the following one-line diagram in Figure 1. Xine = 100 Q…
A:
Q: 4. Why we adopt open delta test instead of direct loading test to calculate the efficiency of large…
A: Transformer tests are performed to determine the performance of transformers. they are of two types,…
Q: A three phase synchronous generator with negligible resistance and Xs=20 ohm has induced voltage as…
A: Given: Per phase quantities, Induced voltage E=230 VTerminal voltage V=230 VSynchronous reactance…
Q: The one line diagram of power system is shown in Figure Q.1. Use a common base MVA of 100 MVA and…
A:
Q: L-type equivalent circuit and parameters for a continuous sinusoidal phase of a 5.5 kW, 1450 rpm,…
A: According to the context of the given question, it is required to determine the number of times…
Q: The one-line diagram of a simple power system is shown in Figure below. The neutral of each…
A: In this question we need to find a 3 phase fault at bus 3 .
Q: 1 MVA, 11kV,three-phase wye-connected synchronous generator has a synchronous reactance of 5 ohms…
A:
Q: A three-phase, 250 MVA, 16 kV rated synchronous generator is feeding into an infinite bus bar at 15…
A: Synchronous generator rating 250MVA and 16 kV Synchronous reactance=1.62 up and E=24 kV a)The line…
Q: In the transmission system shown in the figure above, the rated kVA of transformer 1, T1, is 1000…
A:
Q: What is the per unit impedance of a 50 MVA, 13.8 kV, 1% impedance transformer if the base is change…
A:
Q: Discuss FOUR (4) advantages of per-unit system.
A:
Q: Consider a 3-phase transmission line operating at 66 KV and connected through a 1000 KVA transformer…
A:
Q: Sketch the complete per-phase equivalent circuit of a symmetrical non-salient pole three-phase…
A: Synchronous generator: It is an electromechanical device. This is called a synchronous generator…
Q: Q1. A// Choose the correct answer: 1. One of the advantage of using a per unit system in power…
A: According to guidelines we are allowed to do only first 3 questions , please post again for…
Q: ) the internal voltage of the generator and
A: Per unit (pu) system - Per unit (pu) system is used to express system quantity in the form of ratio…
Q: What is a single phase voltage, current, power factor and power relationships for resistive,…
A:
Q: Four similar synchronous generators are sharing equally the feed to a load of 1 pu referred to the…
A: To find the correct option from the given statements
Q: 7. Which of the following are sometimes installed as an emergency system, legally required standby…
A: In this question, Choose the correct option Which of the following are sometimes installed as an…
Q: Give the main parts (construction) of AC Generator (alternator). Define each.
A:
Q: A three-phase, wye-connected, 6.25kVA, 220-synchronous generator has a reactance of 8.4 ohms per…
A:
Q: A 3-phase, 11 kV, 5 MVA alternator has synchronous reactance of 10 per phase. Its excitation is such…
A: Given a 3-phase, 11 kV, 5 MVA alternator has, Synchronous reactance, X=10 Ω Voltage, E = 11 kV…
Q: Q2. A three phase, 350 MVA, 13.8 kV AC generator has a synchronous reactance of 1.20 per unit. The…
A: The solution is given below
Q: Discuss the principle of operation of pumped storage type hydroelectric power plant and discuss…
A: As per company policy, only the first question will be solved. If the other solution is needed,…
Q: The effective resistance of a 2200 V, 50 Hz, 440 KVA, 1 -phase alternator is 0.5 ohm. On…
A: Synchronous impedance is the ratio of open-circuit voltage to short-circuit current Given Data: V =…
Q: Draw the reactance diagram of the given one-line diagram below marked in appropriate per unit…
A:
Q: A generating system contains three 20 MW generating units each with a 3% FOR and one 45 MW unit with…
A: A table for unit system capacity outage is shown below:
Q: 2.41 A three-phase 25-kVA, 480-V, 60-Hz alternator, operating under bal- anced steady-state…
A: In this question we need to determine a power triangle for the given operating conditions of…
Q: Athree-phase, wye-connected, 6.25 kVA, 220 V synchronous generatorhas a reactance of 8.4 N perphase.…
A: The given system is a three-phase Y connected, the base values are as follows: Vbase=220…
Q: in distribution transformers; What is 30 degrees phase shift in delta-star connection? What are the…
A: In the star-delta connection, the primary side of the transformer is in delta configuration while…
Q: a) The one line diagram of a three phase system is shown below, draw an impedance diagram showing…
A: It is given that:
Q: A 100-MVA, 20-kV synchronous generator is connected through a transmission line to a 100- MVA, 20-kV…
A:
Step by step
Solved in 2 steps
- Consider a single-phase electric system shown in Figure 3.33. Transformers are rated as follows: XY15MVA,13.8/138kV, leakage reactance 10 YZ15MVA,138/69kV, leakage reactance 8 With the base in circuit Y chosen as 15MVA,138kV determine the per-unit impedance of the 500 resistive load in circuit Z, referred to circuits Z, Y, and X. Neglecting magnetizing currents, transformer resistances, and line impedances, draw the impedance diagram in per unit.Consider three ideal single-phase transformers (with a voltage gain of ) put together as three-phase bank as shown in Figure 3.35. Assuming positive-sequence voltages for Va,Vb, and Vc find Va,Vb, and VC. in terms of Va,Vb, and Vc, respectively. (a) Would such relationships hold for the line voltages as well? (b) Looking into the current relationships, express IaIb and Ic in terms of IaIb and Ic respectively. (C) Let S and S be the per-phase complex power output and input. respectively. Find S in terms of S.With the same transformer banks as in Problem 3.47, Figure 3.41 shows the oneline diagram of a generator, a step-up transformer bank, a transmission line, a stepown transformer bank, and an impedan load. The generator terminal voltage is 15 kV (line-to-line). (a) Draw the per-phase equivalent circuit, aounting for phase shifts for positive-sequence operation. (b) By choosing the line-to-neutral generator terminal voltage as the reference, determine the magnitudes of the generator current, transmiss ion-line current, load current, and line-to-line load voltage. Also, find the three-phase complex power delivered to the load.
- A 130-MVA,13.2-kV three-phase generator, which has a positive-sequence reactance of 1.5 per unit on the generator base, is connected to a 135-MVA,13.2/115Y-kV step-up transformer with a series impedance of (0.005+10.1) per unit on its own base. (a) Calculate the per-unit generator reactance on the transformer base. (b) The load at the transformer terminals is 15 MW at unity power factor and at 115 kV Choosing the transformer high-side voltage as the reference phasor, draw a phasor diagram for this condition. (C) For the condition of part (b), find the transformer low-side voltage and the generator internal voltage behind its reactance. Also compute the generator output power and power factor.Three single-phase, two-winding transformers, each rated 450MVA,20kV/288.7kV, with leakage reactance Xeq=0.10perunit, are connected to form a three-phase bank. The high-voltage windings are connected in Y with a solidly grounded neutral. Draw the per-unit equivalent circuit if the low-voltage windings are connected (a) in with American standard phase shift or (b) in Y with an open neutral. Use the transformer ratings as base quantities. Winding resistances and exciting current are neglected.The per-unit equivalent circuit of two transformers Ta and Tb connected in parallel, with the same nominal voltage ratio and the same reactan of 0.1 per unit on the same base, is shown in Figure 3.43. Transformer Tb has a voltage-magnitude step-up toward the load of 1.05 times that of Ta (that is, the tap on the secondary winding of Tb is set to 1.05). The load is represented by 0.8+j0.6 per unit at a voltage V2=1.0/0 per unit. Determine the complex power in per unit transmitted to the load through each transformer, comment on how the transformers share the real and reactive powers.
- Consider the oneline diagram shown in Figure 3.40. The three-phase transformer bank is made up of three identical single-phase transformers, each specified by X1=0.24 (on the low-voltage side), negligible resistance and magnetizing current, and turns ratio =N2/N1=10. The transformer bank is delivering 100 MW at 0.8 p.f. lagging to a substation bus whose voltage is 230 kV. (a) Determine the primary current magnitude, primary voltage (line-to-line) magnitude, and the three-phase complex power supplied by the generator. Choose the line-to-neutral voltage at the bus, Va as the reference Account for the phase shift, and assume positive-sequence operation. (b) Find the phase shift between the primary and secondary voltages.Consider the single-line diagram of the power system shown in Figure 3.38. Equipment ratings are Generator 1: 1000MVA,18kV,X=0.2perunit Generator 2: 1000MVA,18kV,X=0.2p.u. Synchronous motor 3: 1500MVA,20kV,X=0.2p.u. Three-phase -Y transformers T1,T2,T3,T4,: 1000MVA,500kV,Y/20kV,X=0.1p.u. Three-phase YY transformer T5: 1500MVA,500kV,Y/20kVY,X=0.1p.u. Neglecting resistance, transformer phase shift, and magnetizing reactance, draw the equivalent reactance diagram. Use a base of 100 MA and 500 kV for the 50-ohm line. Determine the per-unit reactances.Three single-phase two-winding transformers, each rated 3kVA,220/110volts,60Hz, with a 0.10 per-unit leakage reactance, are connected as a three-phase extended autotransformer bank, as shown in Figure 3.36(c). The low-voltage winding has a 110 volt rating. (a) Draw the positive-sequence phasor diagram and show that the high-voltage winding has a 479.5 volt rating. (b) A three-phase load connected to the low-voltage terminals absorbs 6 kW at 110 volts and at 0.8 power factor lagging. Draw the per-unit impedance diagram and calculate the voltage and current at the high-voltage terminals. Assume positive-sequence operation.
- Three single-phase two-winding transformers, each rated 25MVA,54.2/5.42kV, are connected to form a three-phase Y- bank with a balanced Y-connected resistive load of 0.6 per phase on the low-voltage side. By choosing a base of 75 MVA (three phase) and 94 kV (line-to-line) for the high-voltage side of the transformer bank, specify the base quantities for the low-voltage side. Determine the per-unit resistance of the load on the base for the low-voltage side. Then determine the load resistance RL in ohms referred to the high-voltage side and the per-unit value of this load resistance on the chosen base.For a balanced three-phase positive-sequence currents Ia,Ib,Ic, does the equation Ia+Ib+Ic=0 hold good?The leakage reactance of a three-phase, 300-MVA,230Y/23-kV transformer is 0.06 per unit based on its own ratings. The Y winding has a solidly grounded neutral. Draw the per-unit equivalent circuit. Neglect the exciting admittance and assume the American Standard phase shift.