Reactive power supplied to improve the powerfactor of a 100W load from 0.7 to 0.9 is ____________ a. unity b. 34.9 VAR c. zero d. 53.58 VAR

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter2: Fundamentals
Section: Chapter Questions
Problem 2.22P: The real power delivered by a source to two impedances, Z1=4+j5 and Z2=10 connected in parallel, is...
icon
Related questions
Question
Reactive power supplied to improve the powerfactor of a 100W load from 0.7 to 0.9 is ____________
a.
unity
b.
34.9 VAR
c.
zero
d.
53.58 VAR
Expert Solution
steps

Step by step

Solved in 2 steps

Blurred answer
Knowledge Booster
Sinusoids and Phasors of Alternating Circuit
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.