L-type equivalent circuit and parameters for a continuous sinusoidal phase of a 5.5 kW, 1420 rpm, line voltage 220 V and frequency 50 Hz star-connected 3-phase ASM, ignoring core (iron) losses given as follows: R1=0.21 Ohm, R2=0.18 Ohm, X1=X2=0.66 Ohm and Xm=9.9 Ohm i, i, R, R, jX m (1-s) S How many times the rated current will the inrush current be when the ASM is started directly? O 3.7473 O 1.2558 O 6.3414 O 8.0815 O 7.1534 O 2.6455 n 4.3763
Q: An AC three phase distribution system (given in Figure 2), which has end user with balanced three…
A:
Q: A three-phase, wye-connected, 7 kVA, 230 V synchronous generator has a reactance of 7 ohms per…
A:
Q: (a) A single phase, unity power factor load takes 70 A at 25 kV. Using a base voltage of 60 kV and…
A: Per unit
Q: Neglecting resistance, transformer phase shift, and magnetizing reac- tance, draw the equivalent…
A:
Q: Q5: A SL-G fault occurs on the low voltage side of a transformer that connects a motor to a…
A: Given data for generator, Given data for motor,
Q: L-type equivalent circuit and parameters for a continuous sinusoidal phase of a 5.5 kW, 1450 rpm,…
A: According to the question we have to calculate how many times the inrush current will be the rated…
Q: Problem-4: Solve at Home Problem-4, Cont... The one-line diagram of a simple three-bus power system…
A:
Q: Three-phase alternator supplying a three wires, CBA system with a line voltage of 100 Volt,…
A:
Q: Three zones of a single-phase circuit are identified in the figure with a generator voltage…
A: For the evaluation of electrical machines, one-of-a-kind values are required, consequently, per unit…
Q: Is it possible to measure the phase-shift angle in an AC single-phase circuit by an indirect method…
A: The electrical circuits have resistance, inductance and capacitance as their elements. In the…
Q: Obtain the per-unit equivalent circuit for the following one-line diagram in Figure 1. Xine = 100 Q…
A:
Q: A three phase synchronous generator with negligible resistance and Xs=20 ohm has induced voltage as…
A: Given: Per phase quantities, Induced voltage E=230 VTerminal voltage V=230 VSynchronous reactance…
Q: The total instantaneous power absorbed by a three-phase motor (under balanced steady-state…
A: Consider the instantaneous voltage across phase a and the neutral terminal is given by:
Q: Q5) A Three- phase alternator ( Synchronous Generator) SG , 12 KV , 1.5 MVA, star connected armature…
A: Voltage regulation =( (Ef-Vt)/Vt)*100 Where Ef = per phase armature induced voltage and Vt =per…
Q: (b) A 50 Hz synchronous generator with inertia constant H = 6.2 MJ/MVA is connected to an infinite…
A:
Q: For the system shown in figure, voltage V2 and angle 8, are calculated using Newton-Raphson method.…
A: It is given that:
Q: L-type equivalent circuit and parameters for a continuous sinusoidal phase of a 5.5 kW, 1450 rpm,…
A: According to the context of the given question, it is required to determine the number of times…
Q: The one-line diagram of a simple power system is shown in Figure below. The neutral of each…
A: In this question we need to find a 3 phase fault at bus 3 .
Q: Q1. The following figure shows the differential protection of power transformers with specifications…
A:
Q: (a)Determine the voltages at bus 2 and bus 3 after first iterations using Gauss Seidel. Use flat…
A:
Q: The Gauss-Seidel is an iterative method used to solve a set of nonlinear equations in the power…
A: Gauss-Seidel method is used to solve the power flow analysis question in the power system. In two…
Q: Figure below shows a power system where load at bus 5 is fed by generators at bus 1 and bus 4. The…
A: When line L1 has length =100 km, fault current for fault at bus 5 is =2530 A When line L1 reduced to…
Q: Question 1 In the power system network shown in Figurebelowbus 1 is a slack bus with Vi 1.020° per…
A: According to question we need to calculate the value of V21 , and V22.
Q: Figure below shows a power system where load at bus 5 is fed by generators at bus 1 and bus 4. The…
A:
Q: 5.5 kW, 1450 rpm. L-type equivalent circuit and parameters for a continuous sinusoidal phase of a…
A: Given: 5.5 kW, 1450 rpm, line voltage 220 V and frequency 50 Hz. R1=0.21Ω, R2=0.18Ω,…
Q: Sketch the complete per-phase equivalent circuit of a symmetrical non-salient pole three-phase…
A: Synchronous generator: It is an electromechanical device. This is called a synchronous generator…
Q: Figure below shows the one line diagram of a 3-o system. By selecting a common base of 100 MVA and…
A: There will be three sequence networks in the given power system- Positive-sequence network…
Q: (b) A 50 Hz synchronous generator with inertia constant H = 6.2 MJ/MVA is connected to an infinite…
A:
Q: Y-connected, 9. A 3-phase, circuited and operated at rated speed to produce rated current. When the…
A:
Q: The sequence component line-to-line voltages of a three-phase, 4-wire system are the following: Vab0…
A:
Q: What is a single phase voltage, current, power factor and power relationships for resistive,…
A:
Q: Question - Compare the effect of varying resistance, capacitance and inductance in a pararllel and…
A: In this question Compare the effect of varying resistance, capacitance and inductance in a…
Q: A surge of 100 kV travels along an overhead line towards its junction with a cable. The surge…
A: Given, A surge travels along an overhead line towards its junction with a cable is, V= 100 kV The…
Q: Single Phase equivalent Y-Y system is shown in the figure 3 below, operated by a generator with…
A: Single phase equivalent circuit as given in the circuit is shown below
Q: A three-phase, wye-connected, 6.25kVA, 220-synchronous generator has a reactance of 8.4 ohms per…
A:
Q: 5) Non minimum phase systems are also non causal. True False
A: Non-minimum Phase system: They are causal and stable systems whose inverse are causal but unstable.…
Q: UDng a ITIe Core in high frequency transformers. c- Discuss, different applications of iron cores of…
A: C)For magnetizing or demagnetizing a iron material, some energy is expended. The energy expended…
Q: For the power system shown at right the impedance matrix 2 is j0.5 j0.2 3 j0.4 0.145 0.120 0.0692…
A: New voltage at a bus = old bus voltage + change in voltage
Q: The one line diagram of a three phase power system is as shown in Figure 7 Impedances are marked in…
A:
Q: The effective resistance of a 2200 V, 50 Hz, 440 KVA, 1 -phase alternator is 0.5 ohm. On…
A: Synchronous impedance is the ratio of open-circuit voltage to short-circuit current Given Data: V =…
Q: A generating system contains three 20 MW generating units each with a 3% FOR and one 45 MW unit with…
A: A table for unit system capacity outage is shown below:
Q: The following figure shows the differential protection of power transformers with specifications of…
A:
Q: A star connected 3-phase 10 MVA, 6.6 kV alternator is protected by circulating current protection,…
A: In this question , we will find value of earthing resistance required if 85% of stator winding is…
Q: Is it true??
A: For the transmission of the equal power to three loads impedance will need only the half of the…
Q: In a 3-phase Overhead System, each line is suspended by a string of 3 Insulators. The voltage across…
A: Given voltage across top and middle units, using this we will find Ratio of capacitance, string…
Q: Athree-phase, wye-connected, 6.25 kVA, 220 V synchronous generatorhas a reactance of 8.4 N perphase.…
A: The given system is a three-phase Y connected, the base values are as follows: Vbase=220…
Q: In the power system network shown in Figurebelowbus 1 is a slack bus with V = 1.020° per unit and…
A: (a) Given thatV1=1.0∠0°S2=300MW+j80 MvarLine impedance,Z12=0.01+j0.02 p.u.
Q: L-type equivalent circuit and parameters for a continuous sinusoidal phase of a 5.5 kW, 1460 rpm,…
A:
Step by step
Solved in 4 steps
- Consider a single-phase electric system shown in Figure 3.33. Transformers are rated as follows: XY15MVA,13.8/138kV, leakage reactance 10 YZ15MVA,138/69kV, leakage reactance 8 With the base in circuit Y chosen as 15MVA,138kV determine the per-unit impedance of the 500 resistive load in circuit Z, referred to circuits Z, Y, and X. Neglecting magnetizing currents, transformer resistances, and line impedances, draw the impedance diagram in per unit.Figure 3.32 shows the oneline diagram of a three-phase power system. By selecting a common base of 100 MVA and 22 kV on the generator side, draw an impedance diagram showing all impedances including the load impedance in per-unit. The data are given a follows: G:90MVA22kVx=0.18perunitT1:50MVA22/220kVx=0.10perunitT2:40MVA220/11kVx=0.06perunitT3:40MVA22/110kVx=0.064perunitT4:40MVA110/11kVx=0.08perunitM:66.5MVA10.45kVx=0.185perunit Lines I and 2 have series reactances of 48.4 and 65.43, respectively. At bus 4, the three-phase load absorbs 57 MVA at 10.45 kV and 0.6 power factor lagging.Three single-phase two-winding transformers, each rated 25MVA,34.5/13.8kV, are connected to form a three-phase bank. Balanced positive-suence voltages are applied to the high-voltage terminals, and a balanced, resistive Y load connected to the low-voltage terminals absorbs 75 MW at 13.8 kV. If one of the single-phase transformers is removed (resulting in an open connection) and the balanced load is simultaneously reduced to 43.3 MW (57.7 of the original value), determine (a) the load voltages Va,Vb, and Vc; (b) load currents Ia,Ib, and Ic; and (c) the MVA supplied by each of the remaining two transformers. Are balanced voltages still applied to the load? Is the open transformer overloaded?
- Determine the bus admittance matrix (Ybus) for the three-phase power system shown in Figure 6.23 with input data given in Table 6.11 and partial results in Table 6.12. Assume a three-phase 100 MVA per unit base. TABLE 6.11 Bus input data for Problem 6.20 TABLE 6.12 Partially Completed Bus Admittance Matrix (Ybus) for Problem 6.30PowerWorid Simulator case Problem 3_60 duplicates Example 3.13 except that a resistance term of 0.06 per unit has been added to the transformer and 0.05 per unit to the transmission line. Since the system is no longer lossless, a field showing the real power losses has also been added to the oneline. With the LTC tap fixed at 1.05, plot the real power losses as the phase shift angle is varied from 10 to +10 degrees. What value of phase shift minimizes the system losses?Consider the single-Line diagram of a power system shown in Figure 3.42 with equipment ratings given: Generator G1: 50MVA,13.2kV,x=0.15p.u. Generator G2: 20MVA,13.8kV,x=0.15p.u. Three-phase -Y transformer T1: 80MVA,13.2/165YkV,X=0.1p.u. Three-phase Y- transformer T2: 40MVA,165Y/13.8kV,X=0.1p.u. Load: 40MVA,0.8PFlagging,operatingat150kV Choose a base of 100 MVA for the system and 132-kV base in the transmission-line circuit. Let the load be modeled as a parallel combination of resistance and inductance. Neglect transformer phase shifts. Draw a per-phase equivalent circuit of the system showing all impedances in per unit.
- Determine the positive- and negative-sequence phase shifts for the three- phase transformers shown in Figure 3.36.Does an open connection permit balanced three-phase operation? - (a) Yes (b) NoFigure 3.39 shows a oneline diagram of a system in which the three-phase generator is rated 300 MVA, 20 kV with a subtransient reactance of 0.2 per unit and with its neutral grounded through a 0.4- reactor. The transmission line is 64km long with a cries reactance of 0.5-/km. The three-phase transformer T1 is rated 350MVA.230/20kV with a leakage reactance of 0.1 per unit. Transformer T2 is composed of three single-phase transformers, each rated 100 MVA, 127/13.2kV with a leakage reactance of 0.1 per unit. Two 13.2kV motors M1 and M2 with a subtransient reactance of 0.2 per unit for each motor represent the load. M1 has a rated input of 200 MVA with its neutral grounded through a 0.4- current-limiting reactor, M2 has a rated input of 100 MVA with its neutral not connected to ground. Neglect phase shifts associated with the transformers. Choose the generator rating as base in the generator circuit and draw the positive-sequence reactance diagram showing all reactances in per unit.
- Three single-phase two-winding transformers, each rated 3kVA,220/110volts,60Hz, with a 0.10 per-unit leakage reactance, are connected as a three-phase extended autotransformer bank, as shown in Figure 3.36(c). The low-voltage winding has a 110 volt rating. (a) Draw the positive-sequence phasor diagram and show that the high-voltage winding has a 479.5 volt rating. (b) A three-phase load connected to the low-voltage terminals absorbs 6 kW at 110 volts and at 0.8 power factor lagging. Draw the per-unit impedance diagram and calculate the voltage and current at the high-voltage terminals. Assume positive-sequence operation.With the same transformer banks as in Problem 3.47, Figure 3.41 shows the oneline diagram of a generator, a step-up transformer bank, a transmission line, a stepown transformer bank, and an impedan load. The generator terminal voltage is 15 kV (line-to-line). (a) Draw the per-phase equivalent circuit, aounting for phase shifts for positive-sequence operation. (b) By choosing the line-to-neutral generator terminal voltage as the reference, determine the magnitudes of the generator current, transmiss ion-line current, load current, and line-to-line load voltage. Also, find the three-phase complex power delivered to the load.Consider the oneline diagram shown in Figure 3.40. The three-phase transformer bank is made up of three identical single-phase transformers, each specified by X1=0.24 (on the low-voltage side), negligible resistance and magnetizing current, and turns ratio =N2/N1=10. The transformer bank is delivering 100 MW at 0.8 p.f. lagging to a substation bus whose voltage is 230 kV. (a) Determine the primary current magnitude, primary voltage (line-to-line) magnitude, and the three-phase complex power supplied by the generator. Choose the line-to-neutral voltage at the bus, Va as the reference Account for the phase shift, and assume positive-sequence operation. (b) Find the phase shift between the primary and secondary voltages.