Assignment Conductors Part 3 Week 4
Question 1
A 3 conductor #3 AWG copper cable is being run under a driveway, it has been decided that a pressure treated board will be placed over top for protection. What is the minimum allowable depth that this cable can be buried?
750 mm
800 mm
900 mm
1050 mm
Rule 12-012(1) Table 53 Vehicular area 750 or less = 900m
Rule 12-012 (3)(a)
3) Mechanical protection shall consist of one of the following and, when in flat form, shall be wide
enough to extend at least 50 mm beyond the cables or raceways on each side:
a) treated planking at least 38 mm thick;
900+150=1050mm
Question 2
A factory requires a 3Phase Wye 347/600V Service with an amperage of 1500A. This application is considered a continuous load. The installation plan requires 3 conductors run in parallel per phase buried directly underground with the phases grouped together. What diagram is used for spacing and burial depth? What size must the conductors be?
Rule 4-004 1) 8) TD10B Detail 3: 900kcmil @ 500A
Rule 4-004 1) d) TD10B Detail 3: 800kcmil @ 518A
Rule 4-004 1) d) TD10A Detail 3: 750kcmil @ 518A
Rule 4-004 1) d) TD10A Detail 3: 600kcmil @ 500A
Rule 4-004 1) d) TD10A Detail 3
Diagram D10 Detail 3
1500A/3=500A
Table D10A for
518@ detail3) =750 kcmail
Question 3
A 3phase 600 amp service is being fed from a 500KVA pad mounted transformer. The load is a non-continuous load (The equipment will not be on all the time, the demand will vary depending on devices being used). It has been decided to run 3 single aluminum conductors per phase to feed the service. The phase cables will be directly buried together in 3 separate conduits. What diagram is used to determine proper installation (depth and spacing)? And what
is the ampacity of the individual cables with the size?
300 Kcmil TD10 Detail 3
200 kcmil TD11A Detail 3
250 kcmil TD11B Detail 3
3/0 TD 10 Detail 2
3 separate conduits/3phase/aluminum conductors
4-004-(2)(D)
600/3=200Amp
Table D11B
(T11B for 200Amps @ detail 3) =250 Kcmail
Question 5
300KVA Transformer 7200v Delta 600v Wye Parallel 0000 Awg Aluminum (8 Single Conductors) 170ft Long in 4 Inch PVC Duct Type II or DB1 Transformer Z percent 4.7, Main Disconnect 400amp Fused @ 350Amp Time Delay HRC Dual Element. What is the applied Voltage at the Main Disconnect, at all WYE Configuration Connections, assume wires are all exactly the same length.
Hint think outside the box - the answer may be easier than you think - there is no real math involved
Rule 4-004 2) b) d) (Table 2 & Table 5c) 3/0 RWU90. As per 8-102 2) a) as it would meet the 5% maximum Voltage Drop
Rule 4-004 1) b) d) (Table 2 & Table 5c) 3/0 RWU90. As per 8-102 1) a) as it would meet the 5% maximum Voltage Drop
Rule 4-004 2) c) d) (Table 4 & Table 5c) 4/0 RWU90. As per 8-102 1) a) as it would meet the 3% maximum Voltage Drop
Rule 4-014 2) a) b) (Table 2 & Table 5c) 4/0 RWU75. As per 8-101 2) a) as it would meet the 3% maximum Voltage Drop
L= Lt x P DCF x (V/120)
Lt(Table D3) x P (percentage voltage drop) x DCF (Calculated with Tables) x (VApplied/120(Table D3 Voltage))
Rule 4-004 2) c) d) (Table 4 & Table 5c) 4/0 RWU90. As per 8-102 1) a) as it would meet the 3% maximum Voltage Drop
Table D3 170ft =51.8m
LT=51.8 x 3 0.95 x 350/410=
Table d3= 6.2
LT=6.2mx 3 0.95 x 350/410= 88.35 m
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
- Access to all documents
- Unlimited textbook solutions
- 24/7 expert homework help
Related Questions
b. 63
rule where two different temperatures are encountered for the same conductors
38. An exception to the
permits the application of the higher ampacity (lower temperature) if the length of the conductors that enter a
higher temperature is not more than 10 ft (3.0 m) or not more than 10% of the total circuit length.
C.
ampacity rating
d.
flux rating
a.
circuit derating
b. ampacity derating
lood is
arrow_forward
pls help
arrow_forward
QUESTION 15
What is the minimum sized Rigid Metal Conduit we should use for the above wire run if it is 24 inches long?
a
1"
b
1 1/4"
c
1 1/2"
d
2"
arrow_forward
See Figure 4. Determine the minimum size of the tap conductors for the installation. BAAAAA 19 400 THW, AI TAP CONDUCTORS 600 A FEEDER CIRCUIT 200 A PANELBOARD FIGURE 4 25' TO OTHER LOADS
arrow_forward
12 - Due to the effect of the resistance of the cable connected to RTD, two-wire cables up to ……. meters and three-wire cables up to ……... meters are used in standard designs. A) 10-150B) 40-500C) 50-195D) 30-230E) 200-1000
arrow_forward
Which among these statements is false or incorrect?
O A. The bigger the value of the Breaking Stress, the longer the Sag.
O B. The bigger the Safety Factor used, the longer the Sag.
O C. The older the conductor, the longer the Sag.
O D. The heavier the weight per unit length, the longer the Sag.
arrow_forward
Select all that apply
arrow_forward
The course is power transmission system and the topic is Underground cables.
Question : pressure cable are of two types. (i) oil filled cables. (ii) gas pressure cables
What is the difference between two? Which one is good? Kindly explain the difference in detail
arrow_forward
explain substation earthing with diagram
arrow_forward
ENGINEERING UTILITIES (UPVOTE WILL BE GIVEN. PLEASE WRITE THE COMPLETE SOLUTIONS LEGIBLY. NO LONG EXPLANATION NEEDED. ANSWER IN 3 DECIMAL PLACES. BOX THE FINAL ANSWER.)
arrow_forward
Low-voltage conductors. a. are not powerful enough to cause death from electrocution b. must exceed 480V to cause death C. are responsible for most electrocution deaths due to the frequency of contact d. are unlikely to cause injury if rubber-soled shoes are worn
arrow_forward
Skitch a wire of installation
arrow_forward
5) The Murray Loop Test figuer shown below is used to locate ground fault in a telephone communication cable. The total
resistance, R = R₁ + R₂ is measured by Wheatstone Bridge and it is equal to 60092. The conditions for Murray Loop
Test are as follow: R3 = 2k2 and R4 = 1kQ2.
Determine the location of the ground fault in meter and define it from which point, if the length per Ohm = 80m.
Power or
communication cable
Short
circuit
fault
Murray Loop Test
H|H"
arrow_forward
The Bedding protects the Core or Conductor against corrosion and mechanical injury due to armoring.
Select one:
True
False
arrow_forward
A metal wireway is to contain the following listed copper conductors:• eight (8) - size 500 kcmil THWN• twenty-four (24) - size 2 AWG THWNWhich one of the following listed wireways is the required MINIMUM size to house the conductors?
a.
12 in. x 12 in.
b.
10 in. x 10 in.
c.
8 in. x 8 in.
d.
6 in. x 6 in.
arrow_forward
1. Service-drop conductors must have__.
A. Aufficient ampacity to carry the current for the load
B. Adequate mechanical strenghth
C. A or B
D. A and B
arrow_forward
Please solve in 15 min
arrow_forward
3. The zero sequence current is
times the current in neutral wire.
arrow_forward
Calculate element and welding currents with mesh analysis.
arrow_forward
Help with this third one please
arrow_forward
Calculate the actual sag and vertical sag from the following information. (1) Carrying capacity of carrier = 0.9 kg. / meter (2) Weight of ice coating = 0.848 kg. / m (3) Wind pressure = 1.83 kg. / meter (4) Breaking strength of conductor = 5250 kg. ( 5 ) Safety multiplier = 2.5
arrow_forward
Label the parts of Tubular Steel Poles
arrow_forward
F11
F12
INS
HOME
SYSRO
DEL
END
PRTSC
PGUP
PGDN
PAUSE
BREAK
BACK
->
SPACE
NUM
LOCK
P :
{
ENTER
8
9
НOME
个
PGUP
4
->
11-1V
The number of disc insulators used in a suspension insulator setup with string
efficiency 85 %, phase voltage 66 kV, and the voltage across insulator nearest to
conductor 10 kV is .
arrow_forward
SEE MORE QUESTIONS
Recommended textbooks for you
EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:9781337516549
Author:Simmons
Publisher:CENGAGE LEARNING - CONSIGNMENT
Electricity for Refrigeration, Heating, and Air C...
Mechanical Engineering
ISBN:9781337399128
Author:Russell E. Smith
Publisher:Cengage Learning
Related Questions
- b. 63 rule where two different temperatures are encountered for the same conductors 38. An exception to the permits the application of the higher ampacity (lower temperature) if the length of the conductors that enter a higher temperature is not more than 10 ft (3.0 m) or not more than 10% of the total circuit length. C. ampacity rating d. flux rating a. circuit derating b. ampacity derating lood isarrow_forwardpls helparrow_forwardQUESTION 15 What is the minimum sized Rigid Metal Conduit we should use for the above wire run if it is 24 inches long? a 1" b 1 1/4" c 1 1/2" d 2"arrow_forward
- See Figure 4. Determine the minimum size of the tap conductors for the installation. BAAAAA 19 400 THW, AI TAP CONDUCTORS 600 A FEEDER CIRCUIT 200 A PANELBOARD FIGURE 4 25' TO OTHER LOADSarrow_forward12 - Due to the effect of the resistance of the cable connected to RTD, two-wire cables up to ……. meters and three-wire cables up to ……... meters are used in standard designs. A) 10-150B) 40-500C) 50-195D) 30-230E) 200-1000arrow_forwardWhich among these statements is false or incorrect? O A. The bigger the value of the Breaking Stress, the longer the Sag. O B. The bigger the Safety Factor used, the longer the Sag. O C. The older the conductor, the longer the Sag. O D. The heavier the weight per unit length, the longer the Sag.arrow_forward
- Select all that applyarrow_forwardThe course is power transmission system and the topic is Underground cables. Question : pressure cable are of two types. (i) oil filled cables. (ii) gas pressure cables What is the difference between two? Which one is good? Kindly explain the difference in detailarrow_forwardexplain substation earthing with diagramarrow_forward
- ENGINEERING UTILITIES (UPVOTE WILL BE GIVEN. PLEASE WRITE THE COMPLETE SOLUTIONS LEGIBLY. NO LONG EXPLANATION NEEDED. ANSWER IN 3 DECIMAL PLACES. BOX THE FINAL ANSWER.)arrow_forwardLow-voltage conductors. a. are not powerful enough to cause death from electrocution b. must exceed 480V to cause death C. are responsible for most electrocution deaths due to the frequency of contact d. are unlikely to cause injury if rubber-soled shoes are wornarrow_forwardSkitch a wire of installationarrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- EBK ELECTRICAL WIRING RESIDENTIALElectrical EngineeringISBN:9781337516549Author:SimmonsPublisher:CENGAGE LEARNING - CONSIGNMENTElectricity for Refrigeration, Heating, and Air C...Mechanical EngineeringISBN:9781337399128Author:Russell E. SmithPublisher:Cengage Learning
EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:9781337516549
Author:Simmons
Publisher:CENGAGE LEARNING - CONSIGNMENT
Electricity for Refrigeration, Heating, and Air C...
Mechanical Engineering
ISBN:9781337399128
Author:Russell E. Smith
Publisher:Cengage Learning